Installation Guide for Braeburn models including: Programmable, Thermostats, Braeburn

Detailed SREMIER Installer Guide

For use only as described in this manual. Any other use will void warranty. 5020 Up to 2 Heat / 1 Cool Heat Pump 1 Heat / 1 Cool Conventional 5220 Up to 3 Heat / 2 Cool Heat Pump Up to 2 Heat / 2 Cool Conventional Warning For installation by experienced service technicians only. This thermostat is compatible with:

5020 5220 Installer Manual - Braeburn Systems

settings that do not apply to your setup will be skipped. These settings are indicated below with comments. More detail on each setting follows this table. Installer Guide. 10. 1. Press ...


File Info : application/pdf, 15 Pages, 1.03MB

PDF preview unavailable. Download the PDF instead.

5020 Installer WEB 0
Detailed Installer Guide

®
PREMIER SERIES

Programmable Thermostats
5020 Up to 2 Heat / 1 Cool Heat Pump 1 Heat / 1 Cool Conventional
5220 Up to 3 Heat / 2 Cool Heat Pump Up to 2 Heat / 2 Cool Conventional
Model number is located on back of thermostat.
1 Specifications 2 Installation and Wiring 3 Quick Reference 4 Installer Settings 5 System Testing

Warning For installation by experienced service technicians only.
Caution · Possible electric shock or damage to equipment can occur. · Disconnect power before beginning installation.
This thermostat requires 24 Volt AC Power or 2 properly installed "AA" Alkaline batteries for proper operation. When connecting 24 Volt AC Power the batteries may be installed as a backup.
For use only as described in this manual. Any other use will void warranty.

1 Specifications
This thermostat is compatible with: · Single stage heat / cool conventional and heat pump systems · Single stage heat pumps with auxiliary heat · Heat pump systems up to 3 stages of heating and 2 stages of cooling (5220 only) · 250 ­ 750 millivolt heating only systems · 2 or 3 wire hydronic zone systems
Electrical and control specifications: · Electrical Rating: 24 Volt AC · 1 amp maximum load per terminal · AC Power: 18 ­ 30 Volts AC · DC Power: 3.0 Volt DC (2 "AA" Alkaline Batteries Included) · Control Range: 45° ­ 90° F (7° ­ 32° C) · Temperature Accuracy: +/- 1° F (+/- .5° C) · Outdoor Temperature Display Range: -40° - 120° F (-40° - 49° C)
Terminations · 5020: Rc, Rh, W1/E, C, Y1, O/B/V3, G, S2, S1 · 5220: Rc, Rh, W2, W1/E/W3, C, L, Y2, Y1, O/B/V3, G, S2, S1

5020W-100-05

2 Installation and Wiring
Warning Disconnect power before beginning installation.
Thermostat Location Install the thermostat approximately 5 feet (1.5m) above the floor in an area that has a good amount of air circulation and maintains an average room temperature. Avoid installation in locations where the thermostat can be affected by drafts, dead air spots, hot or cold air ducts, sunlight, appliances, concealed pipes, chimneys and outside walls.

Install your new Braeburn thermostat in 4 basic steps: 1 Install the Sub-Base 2 Provide Power 3 Connect Your Wires 4 Attach Thermostat to Sub-Base
1 Install the Sub-Base:
· Remove the sub-base from the body of the thermostat. · Mount the sub-base as shown below:
Drill 3/16" pilot holes in your desired location. Use supplied anchors for drywall or plaster.

UP

UP

Installer Guide

2

2 Provide Power
C +

+

24VAC Power Terminal (C)

Batteries Installed as Shown

· For 24 Volt AC power, you must connect the common side of the transformer to the C terminal on the thermostat sub-base. In dual transformer installations, the transformer common must come from the cooling transformer.
· For battery power, insert the 2 supplied "AA" type alkaline batteries into the battery compartment located in the rear housing of the thermostat. Make sure to position the Positive (+) and Negative (-) sides of the batteries correctly with the +/- symbols in the battery compartment.

3 Connect Your Wires Wiring Terminations for model 5020

Terminal Rc
Rh
G W1 / E
O / B / V3
Y1 C S1 S2

Function Input Input Output Output Output
Output Input Input

Description 24 Volt AC Cooling Transformer (Dual Transformer Systems Only) Power Connection (24 Volt AC Heating Transformer or Millivolt Power Source) Fan Control (W1) Conventional Heat Relay (E) Auxiliary/Emergency Heat (O) Cool Active Reversing Valve (B) Heat Active Reversing Valve (V3) Zone Valve Power Close Compressor Relay 24 Volt AC Transformer Common
Optional Remote Sensor (indoor or outdoor)

3

Installer Guide

3 Connecting Your Wires (continued)

Wiring Terminations for model 5220

Terminal Rc

Function Input

Rh

Input

G W1 / E / W3

Output Output

W2 O / B / V3

Output Output

Y1

Output

Y2

Output

L

Input

C

Input

S1

Input

S2

Description 24 Volt AC Cooling Transformer (Dual Transformer Systems Only) Power Connection (24 Volt AC Heating Transformer or Millivolt Power Source) Fan Control (W1) 1st Stage Conventional Heat, (E) Emergency Heat, (W3) 3rd Stage Auxiliary Heat 2nd Stage Conventional Heat (O) Cool Active Reversing Valve (B) Heat Active Reversing Valve (V3) Zone Valve Power Close 1st Stage Compressor 2nd Stage Compressor System Malfunction Indicator 24 Volt AC Transformer Common
Optional Remote Sensor (indoor or outdoor)

Installer Guide

4

Conventional Systems
Typical Wiring Configurations
NOTE: The "System Type" option will be configured in the Installer Settings section. Shaded areas do not apply to the 5020.

Heat Only or Millivolt Set System Type to 11CONV Rh Power Connection [note 2] W1 Heat Relay G Fan Relay [note 4] C 24 Volt AC Transformer Common [note 1, 3]
Hydronic Heat Only Set System Type to 1HD
Rh 24 Volt AC Power (heating transformer) [note 2] W1 Zone Valve Power Open V3 Zone Valve Power Close G Fan Relay [note 4] C 24 Volt AC Transformer Common [note 1]
Hydronic Heat / 1 Cool Set System Type to 11HD
Rh 24 Volt AC Power (heating transformer) [note 2] Rc 24 Volt AC Power (cooling transformer) [note 2] W1 Zone Valve Power Open V3 Zone Valve Power Close Y1 Compressor Relay G Fan Relay (cooling fan only) C 24 Volt AC Transformer Common [note 1, 3]

1 HEAT / 1 COOL Single or Dual Transformer Set System Type to 11CONV
Rh 24 Volt AC Power (heating transformer) [note 2] Rc 24 Volt AC Power (cooling transformer) [note 2] W1 Heat Relay Y1 Compressor Relay G Fan Relay C 24 Volt AC Transformer Common [note 1, 3]
2 HEAT / 2 COOL Single or Dual transformer Set System Type to 22CONV (5220 Only)
Rh 24 Volt AC Power (heating transformer) [note 2] Rc 24 Volt AC Power (cooling transformer) [note 2] W1 Heat Relay Stage 1 W2 Heat Relay Stage 2 Y1 Compressor Relay Stage 1 Y2 Compressor Relay Stage 2 [note 4] G Fan Relay C 24 Volt AC Transformer Common [note 1, 3]
NOTES - Conventional Systems [1] Optional 24 Volt AC common connection. [2] Only remove factory installed jumper for dual
transformer systems. [3] In dual transformer systems, transformer
common must come from cooling transformer. [4] If needed for system. Provide disconnect and overload protection as required.

Additional Wiring Options

NOTE: Additional options are configured in the Installer Settings section.
S1 Indoor or Outdoor Remote Sensor [note 1]
S2

NOTES - Additional Wiring Options [1] These terminals can be used to connect a
Braeburn® indoor or outdoor remote sensor.

5

Installer Guide

Heat Pump Systems - Typical Wiring Configurations

NOTE: The "System Type" option will be configured in the Installer Settings section. Shaded areas do not apply to the 5020.

1 HEAT / 1 COOL - No Auxiliary Heat Set System Type to 11HP Rh 24 Volt AC Power Rc Connected to Rh with supplied Jumper Wire O/B Changeover Valve [note 2] Y1 Compressor Relay G Fan Relay C 24 Volt AC Transformer Common [note 1]
2 HEAT / 1 COOL - Including Auxiliary Heat Set System Type to 21HP (5020 Only) Rh 24 Volt AC Power Rc Connected to Rh with supplied Jumper Wire O/B Changeover Valve [note 2] Y1 Compressor Relay (1st stage heating/cooling) E Auxiliary/Emergency Heat Relay [note 6] G Fan Relay C 24 Volt AC Transformer Common [note 1]
2 HEAT / 1 COOL - Including Auxiliary Heat Set System Type to 22HP (5220 Only) Rh 24 Volt AC Power Rc Connected to Rh with supplied Jumper Wire O/B Changeover Valve [note 2] Y1 Compressor Relay (1st stage heating/cooling) W2 Auxiliary Heat Relay (2nd stage heating) [note 3] E Emergency Heat Relay [note 3] G Fan Relay C 24 Volt AC Transformer Common [note 1] L Optional System Fault Monitor [note 4]

2 HEAT / 2 COOL - No Auxiliary Heat Set System Type to 32HP (5220 Only)
Rh 24 Volt AC Power Rc Connected to Rh with supplied Jumper Wire O/B Changeover Valve [note 2] Y1 Compressor 1 Relay (1st stage heating/cooling) Y2 Compressor 2 Relay (2nd stage heating/cooling) G Fan Relay C 24 Volt AC Transformer Common [note 1] L Optional System Fault Monitor [note 4]
3 HEAT / 2 COOL ­ Including Auxiliary Heat Set System Type to 32HP (5220 Only)
Rh 24 Volt AC Power Rc Connected to Rh with supplied Jumper Wire O/B Changeover Valve [note 2] Y1 Compressor 1 Relay (1st stage heating/cooling) Y2 Compressor 2 Relay (2nd stage heating/cooling) E/W3 Auxiliary Heat Relay (3rd stage heating) [note 5] G Fan Relay C 24 Volt AC Transformer Common [note 1] L Optional System Fault Monitor [note 4]
NOTES - Heat Pump Systems [1] Optional 24 Volt AC common connection. [2] O (cool active) or B (heat active) is selected in
the Installer Settings menu. [3] Install a field supplied jumper between the
W2 and W1/E/W3 terminals if there is no separate emergency heat relay installed. [4] If the L terminal is used, the 24 Volt AC common must be connected (C terminal). [5] If a separate emergency heat relay is installed, the W1/E/W3 terminal should have both the auxiliary heat 1 relay and emergency heat relay connected. [6] If a separate emergency heat relay is installed, the W1/E terminal should have both the auxiliary heat 1 relay and emergency heat relay connected. Provide disconnect and overload protection as required.

Additional Wiring Options

NOTE: Additional options are configured in the Installer Settings section.
S1 Indoor or Outdoor Remote Sensor [note 1]
S2

NOTES - Additional Wiring Options [1] These terminals can be used to connect a
Braeburn® indoor or outdoor remote sensor.

Installer Guide

6

4 Attach Thermostat to Sub-Base

UP

L

S1

C

S2

W1/E

G

/AUX1

W2/

Y1

AUX2

W3/

Y2

O/B

RH

A

RC

H

UP

INSTRUCTIONS

1) Line up the thermostat body with the sub-base. 2) Carefully push the thermostat body against the
sub-base until it snaps in place.

DAY/TIME
3) Insert Quick Reference Card into slot on top of thermostat.

NOTE: This thermostat ships configured as a 1H/1C conventional thermostat. Confirm installer settings. See page 10.

7

Installer Guide

3 Quick Reference

7

8

1 9 10 11
12 13 2 14

BACK NEXT

3

45

6

Thermostat Display
1 Room Temperature ...................... Displays the current room temperature 2 Set Temperature .......................... Displays the current set point temperature 3 BACK Indicator* ........................... BACK button is active 4 NEXT Indicator*............................ NEXT button is active 5 Outdoor Temperature Indicator... Displays along with the outdoor temperature reading** 6 Service Indicators ...................... Displays various service/maintenance information 7 Fan Indicator................................ Indicates when the system fan is running 8 Low Battery Indicator.................. Indicates when the batteries need to be replaced 9 Hold Mode Indicator ................... Indicates if the thermostat is in HOLD mode 10 Lock Mode Indicator ................... Indicates if the thermostat is locked 11 System Status Indicator ............. Displays information about the status of the system 12 Day of the Week........................... Displays the current day of the week 13 Program Event Indicator.............. Displays the program event 14 Time of Day ................................. Displays the current time of day
* BACK and NEXT are secondary functions of the PROG and HOLD buttons. When in programming or configuration modes, BACK and NEXT appear in the display screen indicating that the PROG and HOLD buttons now function as BACK and NEXT. ** Also see #24 on page 9.

Installer Guide

8

INSTRUCTIONS

22

23
15 BACK NEXT

DAY/TIME

16

17 18 19 20

21

24

Thermostat
15 Reset Button ............................... Resets current time, program and user settings 16 SYSTEM Button ............................ Selects the system you want to control 17 DAY/TIME Button.......................... Sets the current time and day of the week
PROG Button................................. Selects programming mode or press for 3 seconds to select SpeedSet® 18 BACK Button*............................... Secondary function of the PROG button - moves back a setting
HOLD Button................................. Enters/Exits the HOLD mode (program bypass) 19 NEXT Button* ............................... Secondary function of the HOLD button - moves to next setting 20 RETURN Button ............................ Returns to normal mode from program or setting modes 21 FAN Button ................................... Selects the system fan mode 22 Quick Reference Instructions...... Stored in slot located at top of thermostat 23 SpeedBar® ................................... Increases or decreases settings (time, temperature, etc.) 24 Outdoor Temperature................... If a Braeburn® outdoor sensor was connected you can view the outdoor
temperature by pressing the PROG and HOLD buttons at the same time. Battery Compartment .................. Located in the back of thermostat

* BACK and NEXT are secondary functions of the PROG and HOLD buttons. When in programming or configuration modes, BACK and NEXT appear in the display, indicating that the PROG and HOLD buttons now function as BACK and NEXT.

9

Installer Guide

4 Installer Settings
The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer Settings are menu driven. The portion of these settings that do not apply to your setup will be skipped. These settings are indicated below with comments. More detail on each setting follows this table.

1. Press and hold down the RETURN and buttons for 3 seconds.
2. Release both buttons and the first installer setting will be displayed.
3. Change settings as required using the or portion of the SpeedBar®.
4. Press NEXT (HOLD) or BACK (PROG) to move to the next or previous setting, press RETURN to exit.
BACK NEXT

INSTRUCTIONS

DAY/TIME

TIME

NOTE: Shaded areas below do not apply to the 5020.

No. Installer Setting (Notes follow this table)
1 Residential or or Commercial Profile
2 Programming Mode [note 1]

Factory Default RES
7 PROG

3 Clock Format

12 HR

4 Temperature Scale

F DEG

5 Auto Changeover

oF AUTO

6 System Type

11CONV

Setting Options
RES COMM
7 PROG 52 PROG NO PROG
12 HR 24 HR
F DEG C DEG
oF AUTO ON AUTO 11CONV 22CONV
11HP 21 HP 22HP 32HP 1HD 11HD

Comments (More information follows this table)
Select for Residential profile Select for Commercial profile
Select for 7 day programming mode Select for 5-2 day programming mode Select for non-programmable mode
Select for 12 hour clock Select for 24 hour clock
Select for Fahrenheit display Select for Celsius display
Disables Auto Changeover mode Enables Auto Changeover mode Select for 1H/1C Conventional system Select for 2H/2C Conventional system
Select for 1H/1C Heat Pump system Select for 2H/1C Heat Pump system (5020 Only) Select for 2H/2C Heat Pump system Select for 3H/2C Heat Pump system Select for Heat Only Hydronic system Select for Hydronic Heat/1C system

Installer Guide

10

No. Installer Setting (Notes follow this table)
7 1st Stage Differential

Factory Default
0.5 DIF1

8 2nd Stage Differential [note 2]

2.0 DIF2

9 3rd Stage Differential [note 2]

2.0 DIF3

10 1st Stage Fan Control HG FAN 1

[note 3]

11 Emergency Heat] Fan Control [note 4]

HE EMER

12 Reversing Valve

REVO

(O/B Terminal) [note 5]

13 Fossil Fuel Backup Heat [note 4]

AE AUX

14 Compressor Power Outage oF CPOP Protection [notes 4, 6]

15 AC Power Interrupt Warning [note 6]

AC oF MONR

16 Compressor Short

5 CSCP

Cycle Protection [note 7]

17 Residual Cooling Fan Delay [note 7]

60 FAN

18 Circulating Fan Lock

oF CIRC

19 Adaptive Recovery

oF REC

Mode (ARMTM) [note 8]

20 Indoor Remote Sensor Control* [note 9]

I SENS

21 Lockout Security Level 2 LOCK

22 Auto Changeover Dead Band [note 10]
23 Compressor Balance Point [notes 4, 11]
24 Auxiliary Heat Balance Point [notes 4, 11]

3 BAND NO BALC NO BALA

25 Heat Set Point Upper Limit 90LIM

26 Cool Set Point Lower Limit 45LIM [note 7]

Setting Options

Comments (More information follows this table)

0.5, 1.0 or 2.0 DIF1

Select a 1st stage temperature differential of .5°, 1° or 2° F (0.2°, 0.5° or 1.0° C)

1.0, 2.0, 3.0, Select a 2nd stage temperature differential of

4.0, 5.0 or 1°, 2°, 3°, 4°, 5° or 6° F (0.5°, 1.0°, 1.5°, 2.0°,

6.0 DIF2

2.5° or 3.0° C)

1.0, 2.0, 3.0, Select a 3rd stage temperature differential of 1°, 2°, 4.0, 5.0 or 3°, 4°, 5° or 6° F (0.5°, 1.0°, 1.5°, 2.0°, 2.5° 6.0 DIF3 or 3.0°C)

HG FAN 1 HE FAN 1

Select for 1st stage Gas heating Select for 1st stage Electric heating

HE EMER HG EMER

Select for Electric Emergency Heat Select for Gas Emergency Heat

REVO REVB

Select for cool active Reversing Valve (O terminal) Select for heat active Reversing Valve (B terminal)

AE AUX AG AUX

Select for Electric Auxiliary heat (with compressor) Select for Gas Auxiliary heat (without compressor)

oF CPOP on CPOP

Disables Power Outage Lockout Delay Enables Power Outage Lockout Delay

AC oF MONR Disables AC Power Interrupt Warning AC on MONR Enables AC Power Interrupt Warning

5, 4, 3, 2 or Select a compressor short cycle protection delay

0 CSCP

of 5, 4, 3, 2 or 0 minutes

90, 60, 30 Select a Residual Cooling Fan Delay of 90, 60, or 0 FAN 30 or 0 seconds.

oF CIRC on CIRC

Disables Circulating Fan Lock mode Enables Circulating Fan Lock mode

oF REC on REC

Disables Adaptive (early) Recovery mode Enables Adaptive (early) Recovery mode

I SENS E SENS A SENS

Temperature is sensed from thermostat only. Temperature is sensed from remote sensor only. Temperature is combined with the thermostat and the remote sensor.

2 LOCK 1 LOCK

If locked ­ Complete lockout is enabled If locked ­ Partial lockout is enabled (SpeedBar® is still functional)

2, 3, 4 or 5 Select a Dead Band of 2°, 3°, 4° or 5° F

BAND

(1°, 2° or 3° C) for Auto Changeover mode.

NO BALC Disables Balance Points 15-50 BALC Select a Compressor Balance Point of 15°- 50°F
(-9°-10° C)

NO BALA Disables Balance Points 70-40 BALA Select a Auxiliary Heat Balance Point of 70°- 40° F
(21°- 4° C)

90-60 LIM Select a Heat Set Point Upper Limit of 90°-60° F (32°-10° C)

45-80 LIM Select a Cool Set Point Lower Limit of 45°-80° F (7°-27° C)

*When a Braeburn® outdoor sensor is connected, the thermostat automatically recognizes it. Press PROG and HOLD at the same time to display outdoor temperature.
NOTE: Additional options such as Service Monitors, setting the lock code, etc. are located in the User Settings ­ See User manual for information on setting these options.

11

Installer Guide

NOTES - Installer Settings
1 Only available if Residential profile was selected in option 1. 2 Only available if a 2 or 3 stage system type was selected in option 6. 3 Only available if a Conventional system was selected in option 6. 4 Only available if a 2 or 3 stage Heat Pump system was selected in option 6. 5 Only available if a Heat Pump system was selected in option 6. 6 Only available if the 24 Volt AC common wire is connected to the C terminal. 7 Not available if a heat only hydronic system is selected in option 6. 8 Only available if a programmable profile was selected in option 2. 9 Only available if a Braeburn® indoor remote sensor was connected. 10 Only available if auto changeover was enabled in option 5. 11 Only available if a Braeburn outdoor sensor was connected.
Detailed Explanation of Installer Settings (also see NOTES above):
1 Profile ­ Selects a residential (RES) or commercial (COMM) profile. If residential is selected, 4 programming events per day are available. If commercial is selected, 2 event, 7 day programming is available.
2 Programming Mode [note 1] ­ Selects the programming mode, either full 7 day or 5-2 day (weekday/ weekend) programming or non-programmable.
3 Clock Type ­ Selects either a 12 hour or 24 hour clock.
4 Temperature Scale ­ Selects a temperature scale of either °F or °C.
5 Auto Changeover ­ Selects auto changeover on or off. When auto changeover mode is enabled and selected, the system automatically switches between heating and cooling modes. There is a 5 minute delay when switching from heating to cooling or cooling to heating in auto changeover mode. NOTE: Also see "Auto Changeover Dead Band" in option 22.
6 System Type ­ Selects the system type for your installation. NOTE: Changes made to this option will reset options 7 through 15 back to their default values dependant on the system type.
7 1st Stage Differential ­ Selects a 1st stage temperature differential.
8 2nd Stage Differential [note 2] ­ Selects a 2nd stage temperature differential.
9 3rd Stage Differential [note 2] ­ Selects a 3rd stage temperature differential.
10 1st Stage Fan Control [note 3] ­ Selects a 1st stage fan control of either gas or electric heat.
11 Emergency Heat Fan Control [note 4] ­ Selects emergency heat fan control of either gas or electric heat.
12 Reversing Valve [note 5] ­ Selects the output state of the O/B terminal. Select O for this terminal to be active in the cool mode or select B for this terminal to be active in the heat mode.
13 Auxiliary Fossil Fuel Heat Pump Control [note 4] ­ When set to electric (AE AUX), both the compressor (1st stage) and auxiliary stage(s) will run when a call for auxiliary heat is made. When set to gas (AG AUX), the compressor stage(s) will be locked out one minute after a call for auxiliary heat. NOTE: This option can be overridden if setting an auxiliary heat balance point in Option 24.
14 Compressor Power Outage Protection [notes 4, 6] ­ Selects power outage protection on or off. When enabled, this thermostat will provide cold weather compressor protection by locking out the compressor stage(s) of heating for a period of time after a power outage greater than 60 minutes.

Installer Guide

12

15 AC Power Interrupt Warning [note 6] ­ When enabled, the thermostat will display an outage warning when AC power to the thermostat is lost.
16 Short Cycle Protection [note 7] ­ Selects the number of minutes the cooling compressor will be locked out after turning off. This short cycle protection is also active in the heat mode if a heat pump system was selected in Option 6.
17 Residual Cooling Fan Delay [note 7] ­ Selects a delay for the system fan after the cooling compressor has turned off. This delay will help remove the remaining cool air out of the ductwork providing additional efficiency.
18 Circulating Fan Lock ­ When enabled, the only user fan options available are ON and CIRC (Circulation). The AUTO option is not available with this option enabled.
19 Adaptive Recovery Mode (early recovery) [note 8] ­ Enables or disables the ARMTM (adaptive recovery mode) feature. During ARM, room temperature is recovered by turning on the heating or cooling before the end of the set back period. The set point temperature is changed to that of the upcoming program temperature.
20 Indoor Remote Sensor Control [note 9] ­ If a Braeburn® indoor remote sensor is connected during installation, the thermostat will automatically detect the sensor. When an indoor sensor is detected, you may select between thermostat only (I SENS), remote sensor only (E SENS) or combining the thermostat and the remote sensor (A SENS). NOTE: This option does not apply to a Braeburn outdoor sensor. When an outdoor sensor is connected the thermostat automatically recognizes it and no further configuration is necessary.
21 Lockout Security Level ­ Selects the level of keypad lockout when the thermostat is locked. Level 2 locks the entire thermostat (including the front reset button). Level 1 locks everything except the SpeedBar® allowing for up and down temperature adjustment. NOTE: The lock code is set in the User Settings mode (see User Manual).
22 Auto Changeover Dead Band [note 10] ­ When auto changeover mode is enabled in option 5 and selected, the system automatically switches between heating and cooling when the room temperature meets the normal criteria for either a heating or cooling call. There is a forced separation (dead band) between the heating and cooling set points so that the systems do not work against each other. This option selects the amount of this dead band in degrees with the default being 3° F.
23 Compressor Balance Point [notes 4, 11] ­ Locks out the use of the compressor heat stage when the outside air temperature is less than the selected setting of 15° F to 50° F (-9° C to 10° C)
24 Auxiliary Heat Balance Point [notes 4, 11] ­ Locks out the use of the auxiliary heat stage when the outside air temperature exceeds the selected setting of 70° F to 40° F (21° C to 4° C). NOTE: This balance point overrides the fossil fuel compressor lockout in option 13. If this option is set to gas and the outdoor temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
25 Heat Set Point Upper Limit ­ Selects the heating set point upper adjustment limit.
26 Cool Set Point Lower Limit [note 7] ­ Selects the cooling set point lower adjustment limit.

13

Installer Guide

5 System Testing
Warning Read Before Testing
· Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
· Do not select the COOL mode of operation if the outside temperature is below 50º F (10º C). This could possibly damage the controlled cooling system and may cause personal injury.
· This thermostat includes an automatic compressor protection feature to avoid potential damage to the compressor from short cycling. When testing the system, make sure to take this delay into account.
NOTE: The compressor delay can be bypassed by pressing the reset button on the front of the thermostat. All user settings will be returned to factory default, however all Installer settings will remain as originally programmed in section 4.
1 Press the SYSTEM button until the thermostat is in HEAT mode. 2 Using the SpeedBar® raise the set temperature a minimum of 3 degrees above the current room
temperature. The system should start within a few seconds. With a gas heating system, the fan may not start right away. 3 Press SYSTEM until the thermostat is in the OFF mode. Allow the heating system to fully shut down. 4 Press SYSTEM until the thermostat is in the COOL mode. 5 Using the SpeedBar lower the set temperature a minimum of 3 degrees below the current room temperature. The system should start within a few seconds (unless compressor short cycle protection is active ­ See note above). 6 Press SYSTEM until the thermostat is in the OFF mode. Allow the cooling system to fully shut down. 7 Press FAN until the thermostat is in FAN ON mode. The system fan should start within a few seconds. 8 Press FAN until the thermostat is in FAN AUTO mode. Allow the system fan to turn off.

Installer Guide

14

®

Limited Warranty

When installed by a professional contractor, this product is backed by a 5 year limited warranty. Limitations apply. For limitations, terms and conditions, you may obtain a full copy of this warranty:
· Visit us online: www.braeburnonline.com/warranty

5 YEAR LIMITED WARRANTY

· Phone us: 866.268.5599

· Write us: Braeburn Systems LLC 2215 Cornell Avenue Montgomery, IL 60538

Store this manual for future reference.

®
Braeburn Systems LLC 2215 Cornell Avenue · Montgomery, IL 60538 Technical Assistance: www.braeburnonline.com Call us toll-free: 866-268-5599 (U.S.) 630-844-1968 (Outside the U.S.)
©2020 Braeburn Systems LLC · All Rights Reserved.

5020W-100-05

