Specifications for REZNOR models including: REZNOR, UDX Series, Unit Heaters, Power, Vented, Low, Static, Axial, Fan, Commercial, Industrial, 82 - 83, Thermal, Efficiency

UDX Unit Heater Technical Specifications

UDX

UDX Unit Heater Technical Specifications - Power Equipment ...

Sep 20, 2021 —

Reznor UDX Submittal

Reznor UDX-200-AA2 UDX Power Vented Gas Fired Unit Heater, Low Static Axial Fan, LP, Aluminized Heat Exchanger - 200,000 BTU

Reznor UDX-400-AA2 UDX Power Vented Gas Fired Unit Heater, Low Static Axial Fan, LP, Aluminized Heat Exchanger - 400,000 BTU


File Info : application/pdf, 8 Pages, 543.80KB

PDF preview unavailable. Download the PDF instead.

c0378c35e12687d8ace55e5eef8b78e1
TECHNICAL SPECIFICATIONS

UDX Series
Power Vented, Low Static Axial Fan Commercial/Industrial Unit Heaters 82 - 83% Thermal Efficiency
Reznor® Model UDX gas-fired unit heaters are available in 14 sizes ranging from 30,000 to 400,000 BTUH gas input. Model UDX heaters are approved for installation in the United States and Canada by ETL. Each size cabinet is easily suspended from either 2 or 4 suspension points. Or, an optional hanger kit for Sizes 30-125 allows for ceiling mounting. The low voltage terminal strip on the outside of the cabinet makes connecting control wiring easy with no panels to remove. The addition of a "G" terminal to the strip, along with the new design of the circuit board, allows for fan only operation (without adding relays). Reznor model UDX unit heaters feature a two-tone black and white powder coated, scratch-resistant paint scheme. Each unit has clean rounded corners and edges with no visible screws or fasteners. Model UDX unit heaters provide the same superior performance customers have relied on for more than 100 years along with added features that make servicing the unit easier, installation safer and improve monitoring capabilities.

FEATURES and BENEFITS
· Sizes 30-400 MBTUH certified for commercial/industrial heating application
· Sizes 30-125 MBTUH carry an additional approval for use in residential garage/workshop heating applications
· 50-60°F Rise range · Integrated circuit board with 7 segment display · External status indicating LED · Hinged door with ¼ turn latch · Improved cabinet design with removeable front face and
two tone white and black powder paint. · Tcore2 titanium stabilized aluminized steel heat exchanger · Patented single burner combustion system including a
one-piece burner assembly · 115V, 1 phase, 60 Hz supply voltage · 115 Volt open fan motor with internal overload protection · Transformer for 24-volt controls · Multi-try direct spark ignition with timed lockout · Fan relay (included on the circuit board) · Single-stage natural gas valve (field adjustable for
operation to 9,000 ft. elevation)* · Vibration/noise isolated fan and venter motors ~ designed
for low noise operation · 2-pt and 4-pt Suspension ~ standard on all sizes · External terminal strip for 24-volt wiring · External gas pipe connection · Full fan guard
OPTIONAL FEATURES
· Single-stage propane gas valve (field adjustable for operation to 9,000 ft.)*
· Two-stage gas valve (sizes 60-400) · 409 or 316 stainless steel heat exchangers · Totally enclosed fan motor (sizes 30-400) · Vent cap · Thermostat · Integrated vertical louvers · Integrated 30° & 60° downturn nozzles · Gas conversion kits (natural and propane) · Primary/secondary controls for zoning up to six units · Ceiling suspension kit - Sizes 30-125 · Hanger kits for 1" pipe · Stepdown transformer (for 208/115, 230/115 or 460/115
supply voltage) · Manual shutoff valves
*Note: Pressure switch change required for installations above 6,000 ft.

MODEL IDENTIFICATION CODES

Unit Heater
D - 82-83% Axial Fan B - 82-83% Blower Fan E - 93% Axial

U D X 150
X - Power Vented Z - Seperated Combustion

Input Heating

Capacity

30

45

60

75

100 125

150 175

200 225

250 300

350 400

2

TECHNICAL DATA

Size

Input Heating Capacity

BTUH kw/h

Thermal Efficiency (%)

Output Heating Capacity C

BTUH kw/h

Gas Connection (inches) D

Natural Propane

Vent Connection SizeE (inches diameter)

Control Amps (24 volt)

Full Load Amps (115 volt)

Maximum Over Current Protection (115V) F

Normal Power Consumption (watts)

30 30,000
8.8 82 24,600 7.2 1/2 1/2
4
1.0 1.9
15
109

45 45,000
13.2 83 37,350 11.0 1/2 1/2
4
1.0 2.4
15
155

60 60,000
17.6 83 49,800 14.6 1/2 1/2
4
1.0 2.4
15
155

75 75,000
22.0 83 62,250 18.3 1/2 1/2
4
1.0 3.7
15
217

100 105,000
30.8 83 87,150 25.6 1/2 1/2
4
1.0 4.3
15
276

125 120,000
35.2 83 99,600 29.2 1/2 1/2
4
1.0 5.6
15
354

Discharge Air Temperature Rise (°F)

50

55

60

60

60

60

Air Volume
Discharge Air Opening Area
Output Velocity
Fan Motor HPG
Fan Motor RPM Fan Diameter (inches) Sound Level Approximate Net Weight Approximate Ship Weight

CFM M3/minute
ft2 M2 FPM M/minute Open Enclosed
dba @ 15 ft lbs kg lbs kg

456 12.9 0.96 0.09 475 145 0.02 0.06 1550 10 40 57 26 63 29

629 17.8 0.96 0.09 656 200 0.03 0.06 1550 10 40 62 28 68 31

769 21.8 1.25 0.12 616 188 0.03 0.06 1550 12 40 71 32 76 34

961 27.5 1.25 0.12 770 238 0.06 0.06 1550 12 49 76 34 81 37

1345 36.7 2.01 0.19 668 196 1/30 1/4 1050 16 54 101 46 120 54

1537 45.9 2.01 0.19 763 245 1/20 1/4 1050 16 55 106 48 125 57

C ETL rating for altitudes to 2000 ft. D Size shown is for gas connection to a single stage gas valve, not supply line size. E Smaller or larger vent pipe diameters may be allowed; refer to the Venting Installation Manual, Form I-V-PV. If vent diameter is different from vent connection, reducer/ enlargers will be field-required. F MOP = 2.25 x largest motor FLA + remaining load. Answer is rounded down to the next size of commercially available circuit breaker or fuse. G All other information in this table is based on a heater equipped with a standard 115 volt open fan motor."

3

TECHNICAL DATA (Continued)

Size

Input Heating Capacity

BTUH kw/h

Thermal Efficiency (%)

Output Heating Capacity C

BTUH kw/h

Gas Connection (inches) D

Natural Propane

Vent Connection SizeE (inches diameter)

Control Amps (24 volt)

Full Load Amps (115 volt)

Maximum Over Current Protection (115V) F

Normal Power Consumption (watts)

150 150,000
43.9 83 124,500 36.4 1/2 1/2
5
1.0 3.8
15
392

175 175,000
51.2 83 145,250 42.5 1/2 1/2
5
1.0 3.8
15
392

200 200,000
58.6 83 166,000 48.6 1/2 1/2
5
1.0 4.6
15
491

225 225,000
65.9 83 186,750 54.7 3/4 3/4
5
1.0 7.5
15
747

250 250,000
73.2 83 207,500 60.8 3/4 3/4
5
1.0 7.5
15
747

300 300,000
87.8 83 249,000 72.9 3/4 3/4
6
1.0 11.0
20
1086

350 350,000
102.5 83
290,500 85.1 3/4 3/4
6
1.0 11.0
20
1086

400 400,000
117.1 83
332,000 97.2 3/4 3/4
6
1.0 11.0
20
1086

Discharge Air Temperature Rise (°F)

60

60

60

60

60

60

60

60

Air Volume
Discharge Air Opening Area
Output Velocity
Fan Motor HPG
Fan Motor RPM Fan Diameter (inches) Sound Level Approximate Net Weight Approximate Ship Weight

CFM M3/minute
ft2 M2 FPM M/minute Open Enclosed
dba @ 15 ft lbs kg lbs kg

1921 54.4 2.56 0.24 752 229 1/6 1/4 1050 18 51 178 81 206 93

2242 63.5 2.56 0.24 877 267 1/6 1/4 1050 18 52 193 88 221 100

2562 72.5 2.56 0.24 1003 306 1/6 1/4 1050 18 53 193 88 221 100

2882 81.6 3.51 0.33 820 250 1/4 1/4 1050 20 56 211 96 247 112

3202 90.7 3.51 0.33 911 278 1/4 1/4 1050 20 56 223 101 259 117

3843 108.8 4.79 0.45 802 244
1/2 1/2 1050 24 59 277 126 323 147

4483 126.9 4.79 0.45 936 285
1/2 1/2 1050 24 61 303 137 348 158

5123 145.1 4.79 0.45 1069 326
1/2 1/2 1050 24 62 316 143 360 163

C ETL rating for altitudes to 2000 ft. D Size shown is for gas connection to a single stage gas valve, not supply line size. E Smaller or larger vent pipe diameters may be allowed; refer to the Venting Installation Manual, Form I-V-PV. If vent diameter is different from vent connection, reducer/ enlargers will be field-required. F MOP = 2.25 x largest motor FLA + remaining load. Answer is rounded down to the next size of commercially available circuit breaker or fuse. G All other information in this table is based on a heater equipped with a standard 115 volt open fan motor."

4

DIMENSIONS

Size (in) A

B

C

D

E

F

G

H

J

K

M

N

P

Q

R

S

T

30, 45 13 3/4

10

60

16 3/4

13

75

27

100

24 3/4

21

125

150, 175, 200

20 1/8 38 3/16

16

225, 250 26 1/8

22

300, 350, 400

34 1/8

41

30

29 3/4

6

3 1/2

3 3/4

27

13 13/16

8 11/16

27 5/8 25 9/16

5 15/16

6

3 11/32 17 3/8 1 9/16 4 9/32

13

4 1/16

9 9/16

2 15/16

34 9/32

15 5/16

8 29/32

5 15/32

23

48 7/16

40

9 5/8

5 3/8

8 5/16

13 1/16

9

6 1/2

25 11/16

1 13/32

8 1/8

16 3/8 22 3/16

5 1/2 8 1/16

4 1/4 4 5/16

48 29/32

17 1/16 8 1/2

11 13/16

7 5/16

27 11/16

16 1/4 11 9/16 16 3/16

Size (mm) A

B

C

D

E

F

G

H

J

K

M

N

P

Q

R

S

T

-

-

30,45
60
75
100
125 150, 175,
200 225,250 300, 350,
400

349 425
686 629 511
970 664 867 1041
N

254 330
351 533 406 559 584 762
M

756 831 810
871

UNIT SIZE
06304, 9045
060
075

152
A
213213/4
(349)
31(6842935/)4

B
151
27 (686)

89
C
11502
(254)
(23123306)

D

E

29 3/4
85 (74546)1
32 23/32 (831)
13 13/16 31 29/32 (351) (810)

F
40
25 9/16 (649)

DIMENSIONS - MODELS UDX AND UDZ95

G

H

J

K

M

N

INCHES ( 1/16) (mm ( 2))

6

3 1/2

103

(15120)9 330 (892)43

75

8 11/16 (221)

5 15/16 (151)

6 (152)

3 11/13239 17 3/8

(85)

(441)

1 9/16 (40)

P 4 9/32 (109)

1230 1243

100
1011256
150,175,200 225,250
300,350,400

224443/4
(629)
332
20 1/8
42(6351311/)8
(664)
34 1/8 (867)

211
32(891376/01)6
41 (1041)

12317
(533)
229
16
(34200260)
(559)
30 (762)

165 1283 6
(584)

3(486975/13)22 36

4(8172730/013)6
48 29/32 (1243)

40 (1016)

15 5/16 (389)
206
9 5/8 (244) 13 1/16 (332) 17 1/16 (433)

8 (2292/463)12 6

140

108

564
8 5/16 (211)

5 3/8
(13947)13
(229)

205 110 (6116/522)9425(61512/1)116 4 1 13/32
(36)

8 1/2 11 13/16 7 5/16 27 11/16 (216) (300) (186) (703)

8 1/8 (206)

M AND N - HANGER DIMENSIONS FOR BOTH 2-PT AND 4-PT SUSPENSION

P AND Q HANGER
DIMENSIONS FOR 4-PT
SUSPENSION (4-PT IS
REQUIRED IF INSTALLING OPTIONAL
NOZZLE.)

Q

P

TOP VIEW
3/8-16 FEMALE THREAD - ALL SUSPENSION POINTS

R

R - HANGER DIMENSION FOR 2-PT SUSPENSION
THERMOSTAT CONNECTION

S

T

COMBUSTION

AIR INLET

REAR VIEW

G

J

LINE VOLTAGE INLET (CONNECTS AT CIRCUIT BOARD)

K H

VENT COLLAR EXTERNAL GAS CONNECTION

B D

E F

FRONT VIEW

RIGHT SIDE VIEW (ACCESS PANEL)

C

A

CLEARANCES FROM COMBUSTIBLES

REV.

REVISION RECORD

DATE

BY

ENGR.

ECM

DEBUR AND BREAK SHARP EDGES

PROJECT No.

UNLESS OTHEWISE SPECIFIED DIMENSIONS ARE IN INCHES
TOLERANCE UNLESS OTHERWISE SPECIFIED FOR HOLE DIAMETERS
UP TO .250 .005, 250-1.000 .010, OVER 1.000 .015
TOLERANCE UNLESS OTHERWISE SPECIFIED FOR LINEAR DIMENSIONS AND SQUARENESS IS .04
TOLERANCE UNLESS OTHERWISE SPECIFIED FOR ANGLE IS 1.5

MATERIAL: See Parts
FINISH:

DRAWN
HCL

CHK'D

DA

12/29

WEIGHT: lbs

Size
30-125 150-400

Top

inches

mm

1

25

4

102

Flue Connector

inches

mm

6

152

6

152

Access Panel J

inches

mm

18

457

18

457

Non-Access Side

inches

mm

1

25

2

51

J Access Panel clearance is required for service clearance to controls K Suspend the heater so that the bottom is a minimum of 5' (1.5M) above the floor. L Rear clearance is required for air movement. Rear clearance should be measured from the fan motor.

Bottom K

inches

mm

1

25

1

25

Rear L

inches

mm

18

457

18

457

5

THROW/FLOOR COVERAGE
H

H Height measured from the floor to the bottom of the unit heater. X Point where heated air from the heater reaches the floor. Y Point where heated air tends to rise from the floor. Z Point where the air velocity drops below 50 feet per minute (254 mm/sec).

X Y Z

Dimensions in Feet

Size

30

45

60

75

100

125

150

Mounting Height

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

5

6 14 30 -21° 7 16 40 -20° 8 18 45 -16° 9 20 57 -14° 9 20 59 -18° 10 22 65 -14° -- -- -- --

8

7 13 26 -39° 9 16 37 -34° 10 18 42 -29° 12 22 54 -25° 11 21 56 -28° 12 23 63 -24° 13 24 73 -26°

10

6 11 22 -52° 9 15 33 -43° 10 17 39 -37° 12 22 52 -32° 12 20 52 -36° 13 24 60 -30° 14 24 69 -32°

12

-- -- -- -- 8 12 27 -55° 10 16 34 -46° 12 21 48 -39° 11 19 47 -44° 14 23 57 -36° 14 24 64 -39°

14

-- -- -- -- -- -- -- -- 9 14 29 -56° 12 19 44 -46° 11 17 42 -51° 14 22 53 -43° 14 22 59 -45°

16

-- -- -- -- -- -- -- -- -- -- -- -- 11 17 38 -54° 10 14 34 -58° 13 20 47 -50° 13 20 53 -51°

18

-- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 11 17 40 -57° 11 17 44 -58°

Size

175

200

225

250

300

350

400

Mounting Height

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

8

15 28 90 -22° 16 30 93 -20° 14 27 86 -24° 16 29 93 -21° 15 28 94 -24° 17 31 105 -20° 18 34 113 -17°

10 17 29 87 -27° 17 31 91 -25° 15 27 82 -30° 17 30 90 -26° 16 28 89 -29° 18 32 103 -25° 20 35 110 -21°

12 18 29 84 -32° 18 31 88 -30° 16 27 78 -35° 18 30 87 -31° 17 28 85 -34° 19 32 98 -30° 21 36 108 -25°

14 18 28 79 -37° 19 30 84 -34° 16 26 73 -41° 18 30 83 -36° 17 27 80 -40° 20 32 95 -34° 23 35 105 -29°

16 18 27 74 -42° 19 29 79 -39° 16 24 67 -47° 19 28 78 -41° 17 25 74 -45° 21 31 90 -38° 23 35 101 -33°

18 17 26 68 -48° 19 28 74 -44° 14 22 60 -53° 18 27 72 -46° 16 24 66 -51° 20 30 85 -43° 23 35 97 -37°

Dimensions in Meters

Size

30

45

60

75

100

125

150

Mounting Height

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

1.5 1.8 4.3 9.1 -21° 2.1 4.9 12.2 -20° 2.4 5.5 13.7 -16° 2.7 6.1 17.4 -14° 2.7 6.1 18.0 -18° 3.0 6.7 19.8 -14° -- -- -- --

2.4 2.1 4.0 7.9 -39° 2.7 4.9 11.3 -34° 3.0 5.5 12.8 -29° 3.7 6.7 16.5 -25° 3.4 6.4 17.1 -28° 3.7 7.0 19.2 -24° 4.0 7.3 22.3 -26°

3.0 1.8 3.4 6.7 -52° 2.7 4.6 10.1 -43° 3.0 5.2 11.9 -37° 3.7 6.7 15.8 -32° 3.7 6.1 15.8 -36° 4.0 7.3 18.3 -30° 4.3 7.3 21.0 -32°

3.7 -- -- -- -- 2.4 3.7 8.2 -55° 3.0 4.9 10.4 -46° 3.7 6.4 14.6 -39° 3.4 5.8 14.3 -44° 4.3 7.0 17.4 -36° 4.3 7.3 19.5 -39°

4.3 -- -- -- -- -- -- -- -- 2.7 4.3 8.8 -56° 3.7 5.8 13.4 -46° 3.4 5.2 12.8 -51° 4.3 6.7 16.2 -43° 4.3 6.7 18.0 -45°

4.9 -- -- -- -- -- -- -- -- -- -- -- -- 3.4 5.2 11.6 -54° 3.0 4.3 10.4 -58° 4.0 6.1 14.3 -50° 4.0 6.1 16.2 -51°

5.5 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 3.4 5.2 12.2 -57° 3.4 5.2 13.4 -58°

Size

175

200

225

250

300

350

400

Mounting Height

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

X

Y

Z

Lvr. Angle

2.4 4.6 8.5 27.4 -22° 4.9 9.1 28.3 -20° 4.3 8.2 26.2 -24° 4.9 8.8 28.3 -21° 4.6 8.5 28.7 -24° 5.2 9.4 32.0 -20° 5.5 10.4 34.4 -17°

3.0 5.2 8.8 26.5 -27° 5.2 9.4 27.7 -25° 4.6 8.2 25.0 -30° 5.2 9.1 27.4 -26° 4.9 8.5 27.1 -29° 5.5 9.8 31.4 -25° 6.1 10.7 33.5 -21°

3.7 5.5 8.8 25.6 -32° 5.5 9.4 26.8 -30° 4.9 8.2 23.8 -35° 5.5 9.1 26.5 -31° 5.2 8.5 25.9 -34° 5.8 9.8 29.9 -30° 6.4 11.0 32.9 -25°

4.3 5.5 8.5 24.1 -37° 5.8 9.1 25.6 -34° 4.9 7.9 22.3 -41° 5.5 9.1 25.3 -36° 5.2 8.2 24.4 -40° 6.1 9.8 29.0 -34° 7.0 10.7 32.0 -29°

4.9 5.5 8.2 22.6 -42° 5.8 8.8 24.1 -39° 4.9 7.3 20.4 -47° 5.8 8.5 23.8 -41° 5.2 7.6 22.6 -45° 6.4 9.4 27.4 -38° 7.0 10.7 30.8 -33° 5.5 5.2 7.9 20.7 -48° 5.8 8.5 22.6 -44° 4.3 6.7 18.3 -53° 5.5 8.2 21.9 -46° 4.9 7.3 20.1 -51° 6.1 9.1 25.9 -43° 7.0 10.7 29.6 -37°

Louver angle listed in the table is relative to the top of the unit heater.
6

GENERAL INFORMATION
WARNING: Gas-fired appliances are not designed for use in hazardous atmospheres containing flammable vapors or combustible dust, or atmospheres containing chlorinated or halogenated hydrocarbons. Installations in public garages or airplane hangars are permitted when in accordance with ANSI Z223.1 and NFPA 54 codes or CAN1-B149 and enforcing authorities.
FOR YOUR SAFETY
What to do if you smell gas: · Do not try to light any appliance. · Do not touch any electrical switch; do not use any phone in your building. · Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. · If you cannot reach your gas supplier, immediately call your fire department.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment. Requirements for installation vary depending on the model of heater and the type of installation. Follow the manufacturer's instructions and comply with all applicable codes.
7

For complete catalog information including submittals, energy calculations, dimension drawings, and more go to www.ReznorHVAC.com or call 800-695-1901.

Note: In keeping with our policy of continuous product improvement, we reserve the right to alter, at any time, the design, construction, dimensions, weights, etc., of equipment information shown here.

© 2021 Nortek Global HVAC, LLC. Reznor is a registered trademark of Nortek Global HVAC, LLC. All other trademarks are the property of their respective owners. All rights Reserved. Printed in U.S.A.

652F-0521 (Replaces 652F-0321)



References