Installation Guide for EMERSON models including: CAN Bus Communication Port Usage and Wiring Between iPro and Site Supervisor, Port Usage and Wiring Between iPro and Site Supervisor, Wiring Between iPro and Site Supervisor, iPro and Site Supervisor, Site Supervisor, Supervisor

CANBus Wiring Guide

CAN Bus Communication Port Usage and ...


File Info : application/pdf, 5 Pages, 1.36MB

PDF preview unavailable. Download the PDF instead.

026-4173-can-bus-wiring-guide-between-ipro-site-supervisor-ipx-modules-en-7588518
CAN Bus Communication Port Usage and Wiring Between iPro and Site Supervisor with IPX Modules
Best Practices Guide
Recommendations · Recommended Belden 8772 or 8771 cable with three wires plus shield. · Do not connect the Belden cable shield to the ground or to other terminals to avoid unwanted current return path. Clip and insulate shield at both ends of the cable. · Line terminations for the two end of line devices ONLY of the CAN Bus cable are recommended for all installations and is mandatory for cable lengths over 100 meters. · The maximum length the CANBUS network is 400 meters. · Maximum of 15 IPX devices on CAN Bus network with Site Supervisor.
iPro System has a dedicated jumper to terminate the line

IPX Expansion Module has a dedicated jumper to terminate the line

Document Part # 026-4173 Rev 4

Page 1 of 5

©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.

Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Site Supervisor has a dedicated mini dip-switch to terminate the line
· To correct faulty termination switch or jumper, connect external 150 ohms from CAN Bus + to CAN Bus - terminals. · With power OFF and CAN cable connector removed, the ohm meter can be used to verify termination switch of
Site Supervisor. Test from the CAN Bus + to CAN Bus - terminals. · Termination is approximately 130 ohms, and No Termination is approximately 1000 ohms or greater.
Example of Daisy-chain Cable with TWO End of Line Terminations
· Termination must be connected only to the first and to the last device in the daisy-chain cable. Having more than two terminations in a daisy-chain may cause communication errors.

Document Part # 026-4173 Rev 4 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 2 of 5

CAN Bus Quick Troubleshooting Guide The following use cases report communication problems:
1. IPro: If the TX and RX LEDs of the iPro do not blink · CAN Bus has not been enabled on the Isagraf Application. · There is a wiring issue in the system. Verify the following: wiring polarity is correct, only two terminations are in the cable, and cable is wired daisy-chain.
2. IPX: If the TX and RX LEDs of the IPX do not blink ·There is an issue in address setting. On IPX, the address of the device is set via a dip-switch and numbering is binary as shown in the table below:

Adr.

0

Adr.

1

Adr.

2

Adr.

3

Adr.

4

Adr.

5

Adr.

6

Adr.

7

Adr.

8

Adr.

9

Adr. 10

Adr. 11

Adr. 12

Adr. 13

Adr. 14

Adr. 15

1 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON

2 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON

3 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON

4 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON

·There is a wiring issue in the system. Verify the following: wiring polarity is correct, only two terminations are in the cable, and cable is wired daisy-chain.
3. Site Supervisor: If the LEDs of the Site Supervisor do not blink
·There is a wiring issue in the system. Verify the following: wiring polarity is correct, only two terminations are in the cable, and cable is wired daisy-chain.
·If no IPX devices are defined in Site Supervisor, CAN Bus is not launched - no LEDs. ·If a device is defined and polarity is reversed, LEDs illuminate at approximately 1 Hz.

Document Part # 026-4173 Rev 4 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 3 of 5

Supervisor and IPX215D Module
Document Part # 026-4173 Rev 4 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 4 of 5

Supervisor and IPX115D Module

Document Part # 026-4173 Rev 4

Page 5 of 5

This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
Join Emerson Technical Support on Facebook http://on.fb.me/WUQRnt For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson reserves the right to modify the designs or specifications of such products at any time without notice. Responsibility for proper selection, use and maintenance of any product
remains solely with the purchaser and end-user. ©2022 Emerson is a trademark of Emerson Electric Co.



References

Adobe PDF Library 15.0