A19QSC Series Temperature Controls with Type 4X Enclosures Installation Guide

Applications
Important: Use this A19QSC Series Temperature Control only as an operating control. Where failure or malfunction of the temperature control could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the temperature control. Important: Utiliser ce A19QSC Series Temperature Control uniquement en tant que dispositif de contrôle de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du temperature control risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du temperature control. You can use the A19QSC Series Temperature Controls for many agricultural applications. For installations that require compliance with Article 547 of the National Electrical Code (NEC), use an A19P or T19P series control. The A19QSC Controls use polycarbonate enclosures and are UL listed as Type 4X. For more information, see Dimensions and Technical specifications. The A19QSC Controls include internal setpoint adjustment dials and range scales.

24-7664-2667 Rev D
2022-12-01
Dimensions
See the following figure for the dimensions of the A19QSC controls: Figure 1: Dimensions for A19QSC Temperature Controls with Type 4X Enclosures, in. (mm)

Callout A B C

Description 3 in. x 1/2 in. conduit knockout Four 0.20 in. (5 mm) mounting holes 0.06 in. (1.5 mm) OD, length varies by model

Mounting

CAUTION
Risk of Environmental and Property Damage. Avoid sharp bends in the capillary tubes. Sharp bends can weaken or kink capillary tubes, which may result in refrigerant leaks or restrictions of flow.

A19QSC

ATTENTION
Risque de dommages environnementaux et dégâts matériels. Éviter de former des coudes serrés avec les tubes capillaires. Les coudes serrés peuvent affaiblir les tubes capillaires ou engendrer des pliures, ce qui risque de provoquer des fuites de réfrigérant ou d'en gêner l'écoulement.
CAUTION
Risk of Environmental and Property Damage. Coil and secure excess capillary tubing away from contact with sharp or abrasive objects or surfaces. Vibration or sharp or abrasive objects in contact with capillary tubes can cause damage that may result in refrigerant leaks (or loss of element charge), which may result in damage to the environment or property.
ATTENTION
Risque de dommages environnementaux et dégâts matériels. Enrouler et fixer l'excédent de tubes capillaires de manière à éviter tout contact avec des objets coupants ou des surfaces abrasives. Des vibrations ou des objets coupants ou abrasifs en contact avec les tubes capillaires risque d'endommager ceuxci et d'occasionner des fuites de réfrigérant (ou des pertes de charge), susceptibles de provoquer des dommages environnementaux ou des dégâts matériels.
CAUTION
Risk of Property Damage. Do not dent or deform the sensing bulb. Dents or deformations in the sensing bulb can change the calibration, may cause the control to operate at temperatures other than the set point, and may result in other property damage.

ATTENTION
Risque de dégâts matériels. Ne pas bosseler ou déformer le bulbe thermostatique. Tout bosselage ou toute déformation du bulbe thermostatique risque de modifier les paramètres d'étalonnage, d'induire des températures de fonctionnement du dispositif de contrôle différentes du point de consigne et de provoquer d'autres dégâts matériels.
Important: Do not install the A19QSC Control where the maximum temperature exceeds 140°F (60°C). If you installing the device where temperatures exceed 140°F (60°C) you could cause damage to the A19QSC Control and you void the warranty. · To mount the temperature control to a flat surface, insert screws through the mounting ears on the back of the case. For more information, see Figure 1.
Wiring
Before you begin:
WARNING
Risk of Electric Shock. Disconnect the power supply before making electrical connections. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
AVERTISSEMENT
Risque de décharge électrique. Débrancher l'alimentation avant de réaliser tout branchement électrique. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles.
Important: Use copper conductors only. Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the A19QSC Control's electrical ratings. Important: Use the terminal screws supplied in the contact block. If you use other terminal screws, you could damage the switch and you void the warranty.

2

A19QSC Series Temperature Controls with Type 4X Enclosures Installation Guide

The Type 4x enclosure includes three 1/2 in. (1.27 cm) trade-size conduit knockouts. To make wiring connections, perform the following procedure:
1. Loosen the four cover screws and remove the cover. Do not damage the O-ring seal.
2. Select the knockout that you want to remove. 3. Place a screwdriver blade on the knockout near the
edge. 4. Apply a sharp blow to the screwdriver handle to
loosen the knockout. 5. Connect an approved watertight conduit fitting to
the conduit. 6. Connect the fitting to the A19QSC control
enclosure.
Note: For flexible conduits, you can reverse Step 5 and Step 6.
7. Insert the wire through the conduit opening. 8. Connect the wires to the screw terminals. For more
information, see Figure 2, Figure 3, and Figure 4. 9. Ensure that the enclosure O-ring is securely
seated in the groove so that it forms a correct seal between the cover and case. 10. Replace the cover and tighten the screws.

Wiring diagrams
Figure 2: Standard wiring for heating applications

Callout 1 2 3

Description Heating load Dial A19 temperature control

Note: In Figure 2, R to B opens on temperature rise. Figure 3: Standard wiring for cooling applications

Callout 1 2 3

Description Cooling load Dial A19 temperature control

Note: In Figure 3, R to Y closes on temperature rise.

A19QSC Series Temperature Controls with Type 4X Enclosures Installation Guide

3

Figure 4: Standard wiring for combination heating and cooling applications

Callout 1
2 3 4 5

Description User-supplied SPDT switch or switching thermostat Cooling load Heating load Dial A19 temperature control

Note: In Figure 4, R to B opens and R to Y closes on temperature rise.

Setup and adjustments
Turn the knob under the temperature control cover to adjust the setpoint. Before you finish the installation, observe at least three complete operating cycles of the controlled equipment to ensure that all components function correctly. To check for correct A19QSC temperature control operation, see Operation for more information.
Heating applications
The following procedure describes how to adjust the temperature for heating applications. · Turn the dial clockwise to a setpoint greater than the
sensed temperature. The heating system cycles on. · Turn the dial counterclockwise to a setpoint less than
the sensed temperature. The heating system cycles off. If the temperature does not operate in this manner, check the wiring and the tightness of the wiring connections.
Cooling or ventilating applications
The following procedure describes how to adjust the temperature for heating applications. · Turn the dial clockwise to a setpoint greater than the
sensed temperature. The ventilating or cooling system cycles off. · Turn the dial counterclockwise to a setpoint less than the sensed temperature. The ventilating or cooling system cycles on. If the temperature does not operate in this manner, check the wiring and the tightness of the wiring connections.
Operation
When the temperature at the sensing element rises to the setpoint or the dial setting, the switch between R and Y closes and the switch between R and B opens on singlepole, double-throw (SPDT) models. The opposite happens when the temperature at the sensing element falls below the following value: the setpoint or dial setting minus the differential. For more information, see Figure 2, Figure 3, and Figure 4.
Repair information
If the A19QSC type electromechanical temperature control fails to operate within its specifications, replace the unit. For a replacement A19QSC control, contact the nearest PENN by Johnson Controls® representative.

4

A19QSC Series Temperature Controls with Type 4X Enclosures Installation Guide

Technical specifications

Table 1: A19QSC Series Temperature Controls with Type 4X Raintight Enclosures

Specifications Switch contact ratings
Ambient operating conditions Ambient storage conditions Shipping weight Compliance

Applied VAC

24 VAC

Motor, full load amperes -

Motor, locked rotor

-

amperes

Non-inductive, single-

-

pole, single-throw (SPST)

amperes

Non-inductive, SPDT

-

amperes

Pilot duty volt-amperes

125 A

-26°F to 140°F (-32°C to 60°C)

120 VAC 16 A 96 A

208 VAC 9.2 A 55.2 A

240 VAC 8 A 48 A

277 VAC -

600 VAC -

22 A

22 A

22 A

22 A

-

16 A 125 A

16 A 125 A

16 A 125 A

16 A 125 A

125 A

-40°F to 140°F (-40°C to 60°C)

1.2 lb (0.54 kg)
UL Listed; File E6688, CCN XAPX (US) and XAPX7 (Canada) UL Listed as Type 4X

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult Johnson Controls Application Engineering at (800) 275-5676. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.

Product warranty
This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/ buildingswarranty.
Single point of contact

APAC

EU

UK

NA/SA

JOHNSON CONTROLS JOHNSON

JOHNSON

JOHNSON

C/O CONTROLS

CONTROLS

CONTROLS

CONTROLS

PRODUCT MANAGEMENT VOLTAWEG 20

TYCO PARK

5757 N GREEN BAY

NO. 32 CHANGJIANG RD 6101 XK ECHT

GRIMSHAW LANE AVE.

NEW DISTRICT

THE NETHERLANDS MANCHESTER

GLENDALE, WI

WUXI JIANGSU PROVINCE

M40 2WL

53209

214028

UNITED KINGDOM USA

CHINA

Contact information