USER'S MANUAL

I. Summary

This instrument is a 6000 counts hand-held automatic range True RMS clamp digital meter. Its circuit design utilizes a large-scale integrated circuit (ADC) as the core and features a full-range overload protection circuit. It can measure AC and DC voltage, low-pass filter VFC voltage, low impedance Low Z voltage, AC and DC current, resistance, diode, continuity test, capacitance, frequency, duty cycle, temperature, and other parameters. It also includes data hold, relative value measurement, surge current measurement, torch function, NCV function, live wire judgment, under-voltage display, and automatic shutdown functions.

II. Open Packing for Checking

Open the box, take out the meter, and check the items below for missing or damaged parts:

Please contact your supplier if you find any problems.

III. Safety Notes

The meter's design complies with CE certification, IEC61010 related terms, double insulation, and Safety standard for overvoltage CAT III 600V. Failure to use the clamp meter according to the operating instructions may weaken or lose its protection.

  1. Check the clamp meter and test leads before use for any damage or abnormal phenomena. Do not use if test leads or housing insulation is obviously damaged, or if the LCD has no display.
  2. Do not use the clamp meter unless the back cover and battery cover are properly secured to avoid electric shock.
  3. Ensure fingers do not exceed the hand part of the test lead range when measuring. Avoid contact with exposed electrical wires, connectors, or unused inputs to prevent electric shock.
  4. Ensure the function switch is in the correct position before measurement. Do not change ranges during measurement to prevent damage.
  5. Do not apply more than DC1000V/AC750V between the meter terminals and ground to avoid electric shock and damage.
  6. Exercise caution when measuring voltages higher than 36V DC or 25V AC to avoid electric shock.
  7. Use the clamp meter according to the manual. Do not measure voltages or currents exceeding the allowable input value. Before measuring resistance, capacitance, diode, or circuit continuity, disconnect all power supplies and discharge capacitors.
  8. When the LCD displays the "?" symbol, replace the battery promptly for accurate measurements. Remove the battery if the meter will not be used for an extended period.
  9. Do not alter the internal wiring of the clamp meter to prevent damage or user injury.
  10. Do not store or use the clamp meter in environments with high temperature, high humidity, flammable materials, explosive substances, or strong electromagnetic fields.
  11. Clean the meter case with a soft cloth and neutral detergent. Avoid abrasive materials or solvents that could corrode or damage the instrument.

IV. Electric Symbols

V. General Specification

VI. Appearance Structure

VII. Display Screen

The display screen shows various indicators and measurements:

VIII. Button Function

Button Introduction: Short press (< 2 seconds), Long press (≥ 2 seconds)

  1. Data hold button (HOLD B/L): Press the HOLD B/L key to enter reading hold measurement mode. Press again to exit. Long press to turn the backlight on/off. The backlight turns off automatically after 15 seconds.
  2. Select button (SELECT/V.F.C): Short press: Switches between NCV and live wire judgment tests (NCV range). Switches AC/DC voltage/current (voltage/current range). Switches frequency/duty cycle (frequency range). Switches Celsius/Fahrenheit (temperature range). Switches resistance, capacitance, diode, on-off tests (resistance range). Long press (AC voltage range): Activates V.F.C. mode for low-pass filter voltage test.
  3. Relative value measurement (REL/): Short press: Enters relative value measurement for AC/DC voltage, capacitance, AC current, and temperature. Long press: Turns the torch light on/off.
  4. Surge current test (ZERO/INR): Short press (DC current range): Clears the open circuit base value. Long press (AC current range): Enters surge current test mode (displays "----" and "INR"). Long press again to exit. Surge current measurement captures True RMS of maximum current within 200ms.
  5. Automatic shutdown function: The meter has an APO function that automatically shuts down after 14 minutes of inactivity to save power. It beeps 3 times before shutdown. To disable APO, hold down SELECT/V.F.C while turning the range switch.

IX. Operate Instructions

1. AC Current and Surge Current Measurement

  1. Set the dial knob to the current range (defaults to AC current). Short press V.F.C. to switch to DC current.
  2. Press and hold the trigger to open the clamp head, grab the conductor, and slowly release the trigger until the clamp head is fully closed. Ensure the conductor is centered in the clamp head for accuracy. The meter measures only one conductor at a time.
  3. Read the True RMS of AC current from the display.
  4. Press REL to test relative value (REL character appears). Press again to exit.
  5. Long press ZERO/INR at AC current range for surge current test. The appliance's instantaneous maximum current can be measured. Long press again to exit. Surge current is True RMS of max current within 200ms.

Notes:

2. DC Current Measurement

  1. Turn knob to current range (defaults to AC). Short press V.F.C. to switch to DC.
  2. If open circuit display is not zero, short press ZERO/INR to clear. High current measurements may leave residual magnetism.
  3. Press and hold trigger, clamp conductor, slowly release until fully closed. Ensure conductor is centered for accuracy. Measures one conductor at a time.
  4. Read measured current from the display.

Notes:

3. AC Voltage Measurement (V~) and Low-Pass Filter Voltage (V.F.C.)

  1. Insert red test lead into VΩ•LIVE•°C•°F jack, black into COM.
  2. Turn knob to voltage range. Short press V.F.C. to switch to AC voltage. Connect leads in parallel to power supply/load.
  3. Read True RMS of AC voltage from display.
  4. Long press V.F.C. at AC voltage range to toggle low-pass filter for inverter/variable frequency motor signals.

Notes:

4. LowZ Low Impedance AC Voltage Measurement

  1. Insert red test lead into VΩ•LIVE•°C•°F jack, black into COM.
  2. Turn knob to low impedance AC voltage range. Connect leads in parallel to power supply/load.
  3. Read True RMS of AC voltage from display.

Notes:

5. DC Voltage Measurement

  1. Insert red test lead into VΩ•LIVE•°C•°F jack, black into COM.
  2. Turn knob to voltage range (defaults to DC). Connect leads in parallel to power supply/load.
  3. Read measured voltage from display.

Notes:

6. Resistance Measurement

  1. Turn knob to resistance range.
  2. Insert red test lead into VΩ•LIVE•°C•°F jack, black into COM.
  3. Connect test leads to the measured resistance and read the value on the LCD.

Notes:

7. Diode and Continuity Test

  1. Insert red test lead into VΩ•LIVE•°C•°F jack, black into COM.
  2. Turn knob to resistance range, short press V.F.C. to select diode or continuity mode.
  3. Continuity test: Buzzer sounds if resistance <500Ω.
  4. Diode test: Connect leads to diode's positive/negative poles. LCD displays forward voltage drop.

Notes:

8. Capacitance Measurement

  1. Insert red test lead into VΩ•LIVE•°C•°F jack, black into COM.
  2. Turn knob to resistance range, short press V.F.C. to switch to capacitance measurement.
  3. Connect leads to capacitor, ensuring correct polarity.
  4. Read capacitance value from display. Use REL mode for <10nF for accuracy.

Notes:

9. Frequency Measurement

  1. Insert red test lead into VΩ•LIVE•°C•°F jack, black into COM.
  2. Turn knob to Hz. Connect leads in parallel to signal source.
  3. Short press SELECT/V.F.C. to switch between frequency and duty cycle.
  4. Read frequency or duty cycle from display.

Notes:

10. Temperature Measurement

  1. Turn knob to °C/°F. Display shows ambient temperature.
  2. Insert K-type thermocouple into corresponding hole.
  3. Measure object surface with probe. Read Celsius value from screen after seconds.
  4. Press SELECT/V.F.C. to switch between Fahrenheit and Celsius.

Notes:

11. Live Wire Recognition (Live)

  1. Turn knob to NCV range (defaults to NCV). Short press SELECT/V.F.C. to switch to Live function (displays "Live").
  2. Insert red test lead into VΩ•LIVE•°C•°F jack, touch measured position.
  3. Audible and visual alarm indicates a live wire. No change means not live.

Notes:

12. Non-Contact AC Voltage Induction Measurement (NCV)

  1. Turn knob to NCV range (displays "NCV").
  2. NCV induction voltage range: 48V~250V. Place clamp head near charged electric field (AC power line, socket).
  3. Sensing AC voltage: Meter displays "----" and emits "drop, drop" alarm sound. More "----" segments and higher buzzer frequency indicate stronger induction field.

X. Technical Characteristic

Accuracy calibration at ambient temperature 23°C ± 5°C, humidity less than 75%RH.

1. AC Current (ACA)

RangeAccuracyResolutionOverload protection
60A0.01A
600A±(4.0%+10)0.1A1000A
1000A1A

Frequency response: 50Hz~60Hz; Display: True RMS.

Accuracy is 5% to 100% of range. Open circuit allows ≤10 words of remaining readings.

Continuous test time for currents >500A: ≤60 seconds.

2. Direct Current (DCA)

RangeAccuracyResolutionOverload protection
60A0.01A
600A±(4.0%+10)0.1A1000A
1000A1A

Accuracy is 5% to 100% of range. Short press ZERO to clear base value before test.

Continuous test time for currents >500A: ≤60 seconds.

3. AC Voltage (V~)

RangeAccuracyResolutionOverload protection
6V±(0.5%+7)0.001V
60V±(1.0%+10)0.01V1000VDC/
750VAC
600V±(1.0%+10)0.1V
750V±(1.0%+12)1V

Input impedance: ≥10MΩ.

Frequency response: sine wave and triangle wave 40Hz~1kHz.

V.F.C. function: Activates low-pass filter. V.F.C. frequency response: 40Hz~200Hz. V.F.C. accuracy: ±(5.0%+10).

Accuracy is 5% to 100% of range. Short-circuit allows ≤5 words of remaining readings.

4. DC Voltage

RangeAccuracyResolutionOverload protection
600mV0.1mV
6V±(0.5%+7)0.001V1000VDC/
750VAC
60V±(1.0%+10)0.01V
600V±(1.0%+10)0.1V
1000V±(1.0%+10)1V

Input impedance: ≥10MΩ.

Accuracy is 5% to 100% of range. Short-circuit allows ≤5 words of remaining readings.

5. Low Impedance AC Voltage (LowZ V~)

RangeAccuracyResolutionOverload protection
6V±(1.0%+10)0.001V300V DC/AC
60V±(1.0%+10)0.01V
300V±(1.0%+12)0.1V

Display: AC voltage True RMS. Input impedance: <3kΩ. Frequency response: sine wave and triangle wave 40Hz~1kHz. Accuracy is 5% to 100% of range. Short-circuit allows ≤5 words of remaining readings.

6. Resistance

RangeAccuracyResolutionOverload protection
600Ω0.1Ω250V DC/AC
6kΩ±(1.0%+5)0.001kΩ
60kΩ0.01kΩ
600kΩ0.1kΩ
6MΩ0.001MΩ
20MΩ±(1.5%+15)0.01MΩ
60MΩ±(2.5%+20)0.01MΩ

Open circuit voltage: about 1V. Accuracy is 5% to 100% of range.

7. Continuity Test

RangeAccuracyResolutionOverload protection
600ΩResistance value >50Ω: buzzer off; ≤50Ω: buzzer on.0.001Ω250V AC/DC

Open circuit voltage: about 2V.

8. Diode Test

RangeAccuracyResolutionOverload protection
3.3VOpen circuit voltage ~3.9V. Measures PN junction forward voltage drop ≤3.9V.0.001V250V AC/DC

Normal silicon PN junction voltage: 0.5~0.8V.

9. Capacitance

RangeAccuracyResolutionOverload protection
1nF±(5.0%+40)0.001nF250V AC/DC
10nF0.01nF
100nF±(5.0%+10)0.1nF
1μF0.001μF
10μF0.01μF
100μF0.1μF
1mF0.001mF
10mF0.01mF

Measured value = measured display value - test lead open circuit value.

For ≤1μF, use REL mode to measure and deduct open circuit readings. Accuracy is 5% to 100% of range.

Large capacitance response time: ≥1mF about 8s. Error excludes lead distributed capacitance.

10. Frequency (Hz) / Duty Cycle (%)

RangeAccuracyResolutionOverload protection
10Hz-10MHz±(0.3%+3)0.01Hz-1kHz Hz250V DC/AC
10.0%-90.0%0.1%

Frequency input amplitude requirements: 10Hz-100kHz: 1Vrms≤input amplitude≤20Vrms. 100kHz-10MHz: 3Vrms≤input amplitude≤20Vrms.

Duty cycle: 10%-90% range suitable for 10Hz-1kHz square wave; 30%-70% range suitable for 1kHz-10kHz square wave. Input amplitude: 3Vpp≤input amplitude≤20Vpp.

11. Temperature Test (°C/°F)

RangeDisplay rangeResolution
(-20~1000)°C<400°C ±(2.0%+5)
≥400°C ±(1.5%+15)
1°C
(-4~1832)°F<752°F ±(2.0%+5)
≥752°F ±(1.5%+15)
1°F

Overload protection: 250V DC/AC RMS. Accessory: Type K thermocouple. Accuracy may be affected by ambient temperature difference (±5°C requires 1 hour stabilization).

XI. Instrument Maintenance

1. Power Supply

Uses 2 AAA batteries. Replace batteries when:

2. General Maintenance

Maintenance and service should be performed by qualified personnel or designated service departments.

Remove batteries if the instrument is not used for a long time to prevent leakage corrosion.

Protect from water, dust, and falls.

Model: 601C-610B-000A

Models: 610B True RMS Clamp Digital Meter, 610B, True RMS Clamp Digital Meter, RMS Clamp Digital Meter, Clamp Digital Meter, Digital Meter

File Info : application/pdf, 5 Pages, 318.14KB

PDF preview unavailable. Download the PDF instead.

2a049520eb Acrobat Distiller 15.0 (Windows)

Related Documents

Preview 1000A AC Clamp Meter: Operating Instructions and Specifications
Comprehensive operating instructions and technical specifications for the 1000A AC Clamp Meter. Learn about safety features, measurement functions including AC/DC voltage, current, resistance, capacitance, frequency, duty cycle, and temperature, along with detailed meter descriptions and input limits.
Preview AC/DC Clamp Meter Operator's Instruction Manual
This manual provides detailed operating instructions, safety precautions, and specifications for the AC/DC Clamp Meter. Learn how to measure DC/AC voltage, AC/DC current, resistance, frequency, and perform diode and continuity tests.