Instruction Manual for WSD models including: WSD-170YT08W-AC Emergency LED Driver, WSD-170YT08W-AC, Emergency LED Driver, LED Driver, Driver

201.0484     WSD-170YT08W-AC spec 10.16

DATA/SPEC SHEET

8W Emergency Backup Battery Driver 100-347Vac WSD-170YT08W-AC · WSD LED INC Current: 100mA maxInput Power: 6W maxOutput Voltage: 170V DCEmergency Power: 8WRecharge Time: 24HrsDischarge Time: 90 minutesBattery: Li-ion  BatteryAmbient Temp: 5°C-50°C(41°F to 122°F)Download:

8W Emergency Backup Battery Driver 100-347Vac WSD-170YT08W-AC · WSD LED INC


File Info : application/pdf, 5 Pages, 10.06MB

PDF preview unavailable. Download the PDF instead.

201.0484 WSD-170YT08W-AC spec 10.16 ?v=1729043657
WSD-170YT08W-AC EMERGENCY LED DRIVER

New Design

CONSTANT POWER
EMERGENCY OUTPUT

FEATURES
Patent design ideal for Ultra-thin back-lit panel lights, easy to install and fix. Easy wiring,directly connect to AC INPUT of LED driver, suitable for CCT selectable lighting fixture. No need flex conduit and connector, high cost performance. Constant output power. Built-in Lithium Battery. Patent design with 12V auxiliary source Protections: Input over current projection,output over charge protection,output over discharge protection,output short circuit protection. UL listed for factory or field installation-UL924& CSA C22.2 NO.141. Compliance with NFPA 101 life Safety Code and CEC (CA Title 20).

NOTE: leading-out wires left or right are optional, please advise before order.

ELECTRICAL SPECIFICATIONS
Input Voltage:100~347Vac,50/60Hz Input Current: 100mA max Input Power: 6W max Output Voltage: 170V DC Emergency Power: 8W Recharge Time: 24Hrs Discharge Time: 90 minutes Battery: Li-ion Battery Ambient Temp: 5°C-50°C(41°F to 122°F)

DIMENSIONS
Driver-19.09''x1.3''x1.06''(485mmx33mmx27mm) Mounting center-18.23''(463mm)

12.076m"m

405mm 15.94"

33m1.m3"

425mm 16.73" 463mm 18.23" 485mm 19.09"

Web:WWW.WSDLEDINC.COM

leo.zhu@wisdom-ssl.com

Tel:1(469).857.5693

WSD-170YT08W-AC EMERGENCY LED DRIVER

INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
Risk of fire or electric shock.Luminaire wiring and electrical parts may be damaged when drilling for installation of LED Emergency Backup.Check for enclosed wiring and components. Risk of fire or electric shock.This LED Emergency Backup installation requires knowledge of luminaire electrical systems.If not qualified,do not attempt installation.Contact a qualified electrician. Before installing,make certain the AC power to the fixture is off. The electrical rating of this product is 100-347Vac.Installer must confirm that there is 100-347Vac to the fixture before installation. To prevent electrical shock only mate unit connector after installation is complete and before the AC power to the fixture is back on. Do not use in outdoor. This LED Emergency Backup unit requires an un-switched AC power source of 100-347Vac,50/60Hz The AC driver must be on the same branch circuit as the LED Emergency Backup unit. Do not let power supply cords touch hot surfaces. Do not mount near gas or electric heaters. Do not connect battery pack connector until all other wiring is complete and AC power is on. The emergency LED driver is for use with grounded,UL listed LED luminaires,shall be enclosed by the LED luminaire and bonded to the grounding of LED luminaire. Verify that all replacement lamp types marked on the installed luminaire are also identified as suitable for use with this emergency battery pack. The battery pack is fixed by screws and the indicator light is installed on the surface of luminaires. Equipment should be mounted in locations and at heights where it is not be subjected to tampering by unauthorized personnel. The use of accessory equipment is not recommended by the manufacturer and may cause an unsafe condition. Do not use this equipment for other than its intended use. Use with grounded, UL Listed, dry or damp location rated fixtures. IMPORTANT: Please charge the battery consistently for >24 hours for the first time usage so as to activate the whole battery cells of discharging/charging duration. IMPORTANT: Customers are advised to charge emergency LED drivers 24 hours every 6 months during storage,and which could be stocked for 1 year at most. If customers don't install and recharge for more than one year, the batteries may be damaged. This is not covered in the warranty, and we would charge for replacement. IMPORTANT: Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility test before using and final installation.

THIS PRODUCT CONTAINS A RECHARGEABLE LI-ION BATTERY.

S

THE BATTERY MUST BE RECYCLED OR DISPOSED OFF PROPERLY.

Li-ion

Web:WWW.WSDLEDINC.COM

leo.zhu@wisdom-ssl.com

Tel:1(469).857.5693

WSD-170YT08W-AC EMERGENCY LED DRIVER

OPTIONAL ACCESSORY

BLD-JT-R-TZ-053

Dimensions: 3.3''x1.69''x1.05''(83.7mmx43mmx26.7mm)

216.0.75m" m

3.2mm

10mm

83.7mm 3.3"

43mm 1.69"

40m20mmm1.507.7"9"

BLD-JT-R-TZ-064

Dimensions: 3.3''x1.69''x1.05''(83.7mmx43mmx26.7mm)

14.639m"m

833.3.7"mm

40m20mmm1.507.7"9"

26.7mm 1.05"
3.2mm

BLD-JT-R-TZ-063

Dimensions: 3.3''x3.3''x1.05''(83.9mmx83.9mmx26.7mm)

48303.m.329"m0mmm1m.570".79"

38.33."9mm

216.0.75m" m 24000mm.7mm9" 1.57"

Web:WWW.WSDLEDINC.COM

leo.zhu@wisdom-ssl.com

Tel:1(469).857.5693

WSD-170YT08W-AC EMERGENCY LED DRIVER
TEST SWITCH
Skinny Film Test Switch

42.4±0.2mm 1.67"
Red Green Charging Emergency TEST

7mm 0.28"

9.6mm 0.38"

200±2mm 7.87"

13.9±0.1mm 0.55"

OPERATION
AC Operation: AC power is present, The LED load from the LED driver is normal power supply, AC LED driver output current can not exceed 150W or 4A, the emergency driver is charging in a standby mode. The GREEN LED light flashes indicates that it is charging. The GREEN LED light on indicates that it is full charged.
Emergency Operation: When AC power fails, the emergency driver automatically switches to emergency mode,the indicator will be solid red, operating the LEDs for a minimum of 90 minutes. When AC power is restored, the emergency driver automatically returns to the charging mode.
This unit contains a control circuit that automatically performs a 30-second discharge test once a month and a full 90-minute discharge test once a year. During routine testing, the emergency driver simulates an AC power failure causing the unit to automatically switch to emergency mode. The unit will monitor the operation of the LED load, battery voltage, LED load connections and emergency duration. At the end of this test, if the emergency system functions properly, the unit will return to normal operation. Should the unit detect any problems, the indicator light will be yellow.

AC Power ON

Charging

Full-charged

Indicator Light Introduction

T

1 Green/Flashing: Charging

Green

2 Green/ON: Full-charged

flashing

3 Red/ON: Discharging(EM mode)

Charging 1

4 Red/Flashing: Low battery

Red flashing

5 Yellow: Error

Low battery 4

Green ON
Full-charged 2
Yellow ON

Error

5

Red ON
Discharging 3

AC Power OFF

Discharging

Test Switch Introduction

Emergency Mode

Press the test swith to confirm whether emergency function is normal

Press the test switch Green turns to Red Emergency function is normal

Web:WWW.WSDLEDINC.COM

leo.zhu@wisdom-ssl.com

Tel:1(469).857.5693

WSD-170YT08W-AC EMERGENCY LED DRIVER

WIRING DIAGRAM
1. For luminaire with 0-10V LED driver and using 0-10V dimmer (* LED DRIVER INPUT POWER NOT GREATER THAN 60W) Emergency Inverter Dim+ (Blue) , Driver Dim- (Yellow) has to connect with LED driver DIM+ and DIM-.

AC-N AC-L

Connect to Ground Connect to AC-N Connect to AC-L Switch AC-L out Connect to Wall Switch

BLUE

0-10V Dimmer

DIM+ DIM-

Connect to Sensor DIM+ Connect to Sensor Aux 12V Connect to Sensor DIM-
Connect to DIM+(Dimmer) Connect to DIM-(Dimmer) Connect to DIM+(Driver)

ORANGE RED
BLACK
PURPLE PINK BLUE

DIM+

Connect toDIM-(Driver)
DIMAC-N
LED Driver AC-L

Connect to Driver N
Connect to Driver L

PurpleBROYEWLNLOW

YELLOWWH/GITREEBELNACK

Testing Button

WSD-170YT08W-AC

Red Green Charging Emergency TEST
Red Green Charging Emergency TEST

2. For luminaire with 0-10V LED driver, without using 0-10V dimmer (* LED DRIVER INPUT POWER NOT GREATER THAN 60W)Emergency Inverter Dim+ (Blue) , Driver Dim- (Yellow) has to connect with LED driver
DIM+ and DIM-.

AC-N AC-L

Switch

AC-L out

Connect to Ground Connect to AC-N
Connect to AC-L Connect to Wall Switch

BLUE

DC12V Sensor
(optional)

DIM+ Aux 12V DIM-

Connect to Sensor DIM+

ORANGE

Connect to Sensor Aux 12V

RED

Connect to Sensor DIM-

BLACK

Connect to DIM+(Dimmer) Connect to DIM-(Dimmer) Connect to DIM+(Driver)

PURPLE PINK BLUE

BROWYNELLOW

Connect toDIM-(Driver)

Purple

DIM+

DIM-
LED Driver

Connect to
DRIVER N Driver N

DRIVER L

Connect to Driver L

YELLOWWH/GITREEBELNACK

Testing Button

WSD-170YT08W-AC

Web:WWW.WSDLEDINC.COM

leo.zhu@wisdom-ssl.com

Tel:1(469).857.5693



References

Adobe Illustrator 25.0 (Windows) Adobe PDF library 10.01