SIEMENS Outdoor Load Center
Catalog Number: SNW2040L1125
Enclosure Type: Type 3R
Feature: Plug-On Neutral Ready
Ratings
125A MAXIMUM
BACK-FED MAIN BREAKER REQUIRES HOLD-DOWN MEANS AND LINE TERMINAL BARRIER. SEE ACCESSORY CHART FOR REQUIRED KIT(S).
120/240 V~, 60 HZ, 1Ø 3W
208Y/120 V~, 60 HZ, 1Ø 3W
FOR INSTALLATION BY A QUALIFIED PERSON IN ACCORDANCE WITH ALL LOCAL ELECTRICAL CODES AND/OR THE NATIONAL ELECTRICAL CODE ®.
Usage as Service Equipment
SUITABLE FOR USE AS SERVICE EQUIPMENT WHEN MAIN BREAKER IS INSTALLED. WHEN USED AS SERVICE EQUIPMENT, APPLY "SERVICE DISCONNECT" LABEL TO FRONT NEXT TO MAIN BREAKER HANDLE.
WHEN USED AS SERVICE EQUIPMENT, UNUSED NEUTRAL BAR TERMINALS MAY BE USED TO TERMINATE EQUIPMENT GROUNDING WIRES IN THE COMBINATIONS INDICATED FOR EQUIPMENT GROUND BAR TERMINALS.
SUM OF QT BREAKER RATING IS NOT TO EXCEED 110 AMPS PER BRANCH CIRCUIT BUS STAB.
TO RESET BREAKERS WITH TRIPPED HANDLE POSITION BETWEEN "ON" AND "OFF", MOVE HANDLE TO "OFF" THEN TO "ON".
REMOVE TWISTOUTS FROM TRIM ONLY WHERE BREAKERS WILL BE INSTALLED. ALL OPENINGS MUST BE FILLED WITH BREAKERS OR FILLER PLATES.
Wire and Torque Requirements
USE COPPER OR ALUMINUM 60°/75°C WIRE. SEE BREAKER MARKINGS FOR WIRE SIZE AND TORQUE REQUIREMENTS.
TERMINALS | WIRE | TORQUE |
---|---|---|
NEUTRAL/GROUND BARS (USE TYPE EC2GB or EC3GB GND BAR KIT ACCESSORY) GROUND CONDUCTORS ONLY | 10-14 CU/10-12 AL 8 AWG 6-4 AWG (2)or(3) 14 AWG (2) 12-10 AWG | 20 LB-INS 25 LB-INS 35 LB-INS 20 LB-INS 20 LB-INS |
A, B, G, N1 | 2/0 - 4 AWG | 110 LB-INS |
N2 ECLK2N NEUTRAL LUG | 2/0 - 4 AWG | 110 LB-INS |
ECLK1-2 NEUTRAL LUG KIT | 2/0 - 4 AWG | 45 LB-INS |
ECLK2 NEUTRAL LUG KIT | 2/0 - 4 AWG | 135 LB-INS |
MAIN LUG TO BUS CONNECTION (1/4-20 NUT) | 45 LB-INS | |
BONDING SCREW | 45 LB-INS |
Accessories
DESCRIPTION | CAT. NO. |
---|---|
FILLER PLATE, 1" | QF3 |
BREAKER HOLD-DOWN/BARRIER | ECMBR2 |
SUBFEED LUG KIT | ECLK2125 |
100-125 AMP MAIN LUG KIT | ECMLK125 |
STANDBY PWR INTERLOCK KIT | ECSBPK01 ECSBPK02 |
Conduit Hubs
TRADE SIZE | CAT. NO. |
---|---|
1 INCH | ECHS100 |
1-1/4 INCH | ECHS125 |
1-1/2 INCH | ECHS150 |
2 INCH | ECHS200 |
2-1/2 INCH | ECHS250 |
Short Circuit Current Rating (SCCR)
THIS PANELBOARD HAS A MAXIMUM SHORT CIRCUIT CURRENT RATING OF 100,000 AMPS RMS SYMMETRICAL, 120/240V~. THE ACTUAL RATING IS DEPENDENT ON THE BRANCH BREAKERS INSTALLED IN THIS PANELBOARD AND THE MAIN/FEEDER BREAKER, IF ANY, INSTALLED AHEAD OF THIS PANELBOARD. THE CORRECT MAIN BREAKER/FEEDER/MAIN BREAKER/BRANCH BREAKER SERIES COMBINATIONS TO BE USED ARE LISTED IN THE TABULATION BELOW. ANY CIRCUIT BREAKER INSTALLED, REPLACED, OR ADDED IN THIS PANELBOARD MUST BE MANUFACTURED BY SIEMENS AND MUST BE OF THE CORRECT TYPE AS INDICATED IN THE TABULATION BELOW. USE OF OTHER CIRCUIT BREAKERS IN THIS EQUIPMENT MAY VOID THE WARRANTY.
MAIN BREAKER (SIEMENS TYPE) | MAIN/FEEDER BREAKER | PANELBOARD MAIN | BRANCH BREAKER | RATING AMPS |
---|---|---|---|---|
NONE USED | NONE USED | NONE USED or QP | QP, QG, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QFGA2, QFGA2N, QPF, QPF2, QPF2N, QE, QE2 | 10,000 |
NONE USED | NONE USED | NONE USED | QPH*, QAFH, QAFH2, QFGAH2, QPHF, QPHF2, QEH, QEH2 | 22,000 |
NONE USED | EQ9677, QPH* | NONE USED or QP, QPH* | QP, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QFGA2, QFGA2N, QPF, QPF2, QPF2N, QE, QE2 | 42,000 |
JXD2(-A), JD6(-A), JXD6(-A), LD6(-A), MXD6, ND6, SND6-B, NXD6, NJJA, NJGA, NLGB, NMG, NNG, NPG, PD6, SPD6-B, PXD6, RD6, RXD6 | NONE USED | HQP* | HQP*, HQAF2, HQFGA2, HQPF2 | 42,000 |
FD6, FXD6 | NONE USED | QPH, BLH | QP, QPH*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, QFGA2, QFGA2N, QFGAH2, QPF, QPF2, QPF2N, QPHF, QPHF2, QE, QE2, QEH, QEH2 | 65,000 |
ND6, SND6-B, NXD6, Class J, T, R, or L Fuses | NONE USED or QP BL, QS | QPH, BLH | QP, QPH*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, QFGA2, QFGA2N, QFGAH2, QPF, QPF2, QPF2N, QPHF, QPHF2, QE, QE2, QEH, QEH2 | |
JXD2(-A), JD6(-A), JXD6(-A), LD6(-A), LXD6(-A), MD6, MXD6, ND6, SND6-B, NXD6, PD6, SPD6-B, PXD6, RD6, RXD6, NDGA, NFGA, NJJA, NJGA, NLGB, NMG, NNG, NPG | NONE USED | QPH*, HQP* | QP, QPH*, HQP*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, HQAF2, QFGA2, QFGA2N, QFGAH2, HQFGA2, QPF, QPF2, QPF2N, QPHF, QPHF2, HQPF2, QE, QE2, QEH2 | 100,000 |
NONE USED | HQSH, HQPH, HED4, HED6, NGB | NONE USED or QP, QPH*, HQP* | QP, QPH*, HQP*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, HQAF2, QFGA2, QFGA2N, QFGAH2, HQFGA2, QPF, QPF2, QPF2N, QPHF, QPHF2, HQPF2, QE, QE2, QEH2 | |
HFD6, HFXD6, HFGA, HJD6(-A), HJXD6(-A), HJGA, HLD6(-A), HLXD6(-A), HLGB, HMD6, HMXD6, HMG, HND6, SHND6-B, HNXD6, HNG, HPD6, SHPD6-B, HPXD6, HPG, HRD6, HRXD6, or Class J, T, R, or L Fuses | ED4, ED6, QS | NONE USED or QP, QPH*, HQP* | QP, QPH*, HQP*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, HQAF2, QFGA2, QFGA2N, QFGAH2, HQFGA2, QPF, QPF2, QPF2N, QPHF, QPHF2, HQPF2, QE, QE2, QEH2 | |
HFD6, HFXD6, or 300V Class T Fuses – 200A Max | NONE USED | QPH*, HQP* | QPH*, HQP* | |
HDGA, HFGA, or 300V Class T Fuses – 600A Max | NONE USED or QPH*, HQP* | QPH*, HQP* | QPH*, HQP* |
*Type QPH and HQP breakers installed in this panel are limited to 100 amps max. when installed on a circuit capable of delivering fault current greater than 10,000 amps.
Diagram Description
The diagram illustrates the internal connections for the load center, showing the main line, neutral, and equipment ground bus bars.
- LINE: Two connection points labeled A and B are shown for the incoming line.
- NEUTRAL: Two neutral bus bars are present, labeled N1 and N2. The text indicates that the installed neutrals limit the panelboard to 30 circuits requiring neutral connections, with ECNBX kits available for up to 40 circuits.
- EQPT GND: Equipment Ground connections are depicted.
Key indicators in the diagram:
- NEUTRAL BUS FOR PLUG-ON NEUTRAL CIRCUIT BREAKERS
- BOND WHEN REQ'D
- BACK-FED BRKR WHEN USED
Safety Warnings
⚠️ DANGER
Hazardous Voltage. Will cause death, serious injury or substantial property damage. Turn off power supplying this equipment before working inside.
⚠️ PELIGRO
Voltaje peligroso. Causará la muerte, lesiones graves o daño substancial a la propiedad. Desconecte el suministro de energía a este equipo antes de trabajar en su interior.