SIEMENS Outdoor Load Center

Catalog Number: SNW2040L1125

Enclosure Type: Type 3R

Feature: Plug-On Neutral Ready

Ratings

125A MAXIMUM

BACK-FED MAIN BREAKER REQUIRES HOLD-DOWN MEANS AND LINE TERMINAL BARRIER. SEE ACCESSORY CHART FOR REQUIRED KIT(S).

120/240 V~, 60 HZ, 1Ø 3W

208Y/120 V~, 60 HZ, 1Ø 3W

FOR INSTALLATION BY A QUALIFIED PERSON IN ACCORDANCE WITH ALL LOCAL ELECTRICAL CODES AND/OR THE NATIONAL ELECTRICAL CODE ®.

Usage as Service Equipment

SUITABLE FOR USE AS SERVICE EQUIPMENT WHEN MAIN BREAKER IS INSTALLED. WHEN USED AS SERVICE EQUIPMENT, APPLY "SERVICE DISCONNECT" LABEL TO FRONT NEXT TO MAIN BREAKER HANDLE.

WHEN USED AS SERVICE EQUIPMENT, UNUSED NEUTRAL BAR TERMINALS MAY BE USED TO TERMINATE EQUIPMENT GROUNDING WIRES IN THE COMBINATIONS INDICATED FOR EQUIPMENT GROUND BAR TERMINALS.

SUM OF QT BREAKER RATING IS NOT TO EXCEED 110 AMPS PER BRANCH CIRCUIT BUS STAB.

TO RESET BREAKERS WITH TRIPPED HANDLE POSITION BETWEEN "ON" AND "OFF", MOVE HANDLE TO "OFF" THEN TO "ON".

REMOVE TWISTOUTS FROM TRIM ONLY WHERE BREAKERS WILL BE INSTALLED. ALL OPENINGS MUST BE FILLED WITH BREAKERS OR FILLER PLATES.

Wire and Torque Requirements

USE COPPER OR ALUMINUM 60°/75°C WIRE. SEE BREAKER MARKINGS FOR WIRE SIZE AND TORQUE REQUIREMENTS.

TERMINALS WIRE TORQUE
NEUTRAL/GROUND BARS
(USE TYPE EC2GB or EC3GB
GND BAR KIT ACCESSORY)
GROUND CONDUCTORS ONLY
10-14 CU/10-12 AL
8 AWG
6-4 AWG
(2)or(3) 14 AWG
(2) 12-10 AWG
20 LB-INS
25 LB-INS
35 LB-INS
20 LB-INS
20 LB-INS
A, B, G, N12/0 - 4 AWG110 LB-INS
N2 ECLK2N NEUTRAL LUG2/0 - 4 AWG110 LB-INS
ECLK1-2 NEUTRAL LUG KIT2/0 - 4 AWG45 LB-INS
ECLK2 NEUTRAL LUG KIT2/0 - 4 AWG135 LB-INS
MAIN LUG TO BUS CONNECTION (1/4-20 NUT)45 LB-INS
BONDING SCREW45 LB-INS

Accessories

DESCRIPTION CAT. NO.
FILLER PLATE, 1"QF3
BREAKER HOLD-DOWN/BARRIERECMBR2
SUBFEED LUG KITECLK2125
100-125 AMP MAIN LUG KITECMLK125
STANDBY PWR INTERLOCK KITECSBPK01
ECSBPK02

Conduit Hubs

TRADE SIZE CAT. NO.
1 INCHECHS100
1-1/4 INCHECHS125
1-1/2 INCHECHS150
2 INCHECHS200
2-1/2 INCHECHS250

Short Circuit Current Rating (SCCR)

THIS PANELBOARD HAS A MAXIMUM SHORT CIRCUIT CURRENT RATING OF 100,000 AMPS RMS SYMMETRICAL, 120/240V~. THE ACTUAL RATING IS DEPENDENT ON THE BRANCH BREAKERS INSTALLED IN THIS PANELBOARD AND THE MAIN/FEEDER BREAKER, IF ANY, INSTALLED AHEAD OF THIS PANELBOARD. THE CORRECT MAIN BREAKER/FEEDER/MAIN BREAKER/BRANCH BREAKER SERIES COMBINATIONS TO BE USED ARE LISTED IN THE TABULATION BELOW. ANY CIRCUIT BREAKER INSTALLED, REPLACED, OR ADDED IN THIS PANELBOARD MUST BE MANUFACTURED BY SIEMENS AND MUST BE OF THE CORRECT TYPE AS INDICATED IN THE TABULATION BELOW. USE OF OTHER CIRCUIT BREAKERS IN THIS EQUIPMENT MAY VOID THE WARRANTY.

MAIN BREAKER (SIEMENS TYPE) MAIN/FEEDER BREAKER PANELBOARD MAIN BRANCH BREAKER RATING AMPS
NONE USEDNONE USEDNONE USED or QPQP, QG, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QFGA2, QFGA2N, QPF, QPF2, QPF2N, QE, QE210,000
NONE USEDNONE USEDNONE USEDQPH*, QAFH, QAFH2, QFGAH2, QPHF, QPHF2, QEH, QEH222,000
NONE USEDEQ9677, QPH*NONE USED or QP, QPH*QP, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QFGA2, QFGA2N, QPF, QPF2, QPF2N, QE, QE242,000
JXD2(-A), JD6(-A), JXD6(-A), LD6(-A), MXD6, ND6, SND6-B, NXD6, NJJA, NJGA, NLGB, NMG, NNG, NPG, PD6, SPD6-B, PXD6, RD6, RXD6NONE USEDHQP*HQP*, HQAF2, HQFGA2, HQPF242,000
FD6, FXD6NONE USEDQPH, BLHQP, QPH*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, QFGA2, QFGA2N, QFGAH2, QPF, QPF2, QPF2N, QPHF, QPHF2, QE, QE2, QEH, QEH265,000
ND6, SND6-B, NXD6, Class J, T, R, or L FusesNONE USED or QP BL, QSQPH, BLHQP, QPH*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, QFGA2, QFGA2N, QFGAH2, QPF, QPF2, QPF2N, QPHF, QPHF2, QE, QE2, QEH, QEH2
JXD2(-A), JD6(-A), JXD6(-A), LD6(-A), LXD6(-A), MD6, MXD6, ND6, SND6-B, NXD6, PD6, SPD6-B, PXD6, RD6, RXD6, NDGA, NFGA, NJJA, NJGA, NLGB, NMG, NNG, NPGNONE USEDQPH*, HQP*QP, QPH*, HQP*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, HQAF2, QFGA2, QFGA2N, QFGAH2, HQFGA2, QPF, QPF2, QPF2N, QPHF, QPHF2, HQPF2, QE, QE2, QEH2100,000
NONE USEDHQSH, HQPH, HED4, HED6, NGBNONE USED or QP, QPH*, HQP*QP, QPH*, HQP*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, HQAF2, QFGA2, QFGA2N, QFGAH2, HQFGA2, QPF, QPF2, QPF2N, QPHF, QPHF2, HQPF2, QE, QE2, QEH2
HFD6, HFXD6, HFGA, HJD6(-A), HJXD6(-A), HJGA, HLD6(-A), HLXD6(-A), HLGB, HMD6, HMXD6, HMG, HND6, SHND6-B, HNXD6, HNG, HPD6, SHPD6-B, HPXD6, HPG, HRD6, HRXD6, or Class J, T, R, or L FusesED4, ED6, QSNONE USED or QP, QPH*, HQP*QP, QPH*, HQP*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, HQAF2, QFGA2, QFGA2N, QFGAH2, HQFGA2, QPF, QPF2, QPF2N, QPHF, QPHF2, HQPF2, QE, QE2, QEH2
HFD6, HFXD6, or 300V Class T Fuses – 200A MaxNONE USEDQPH*, HQP*QPH*, HQP*
HDGA, HFGA, or 300V Class T Fuses – 600A MaxNONE USED or QPH*, HQP*QPH*, HQP*QPH*, HQP*

*Type QPH and HQP breakers installed in this panel are limited to 100 amps max. when installed on a circuit capable of delivering fault current greater than 10,000 amps.

Diagram Description

The diagram illustrates the internal connections for the load center, showing the main line, neutral, and equipment ground bus bars.

Key indicators in the diagram:

  1. NEUTRAL BUS FOR PLUG-ON NEUTRAL CIRCUIT BREAKERS
  2. BOND WHEN REQ'D
  3. BACK-FED BRKR WHEN USED

Safety Warnings

⚠️ DANGER

Hazardous Voltage. Will cause death, serious injury or substantial property damage. Turn off power supplying this equipment before working inside.

⚠️ PELIGRO

Voltaje peligroso. Causará la muerte, lesiones graves o daño substancial a la propiedad. Desconecte el suministro de energía a este equipo antes de trabajar en su interior.

Models: SNW2040L1125 Outdoor Load Center, SNW2040L1125, Outdoor Load Center

PDF preview unavailable. Download the PDF instead.

sie-wd-lc-snw2040l1125 Corel PDF Engine Version 21.3.0.755

Related Documents

Preview Siemens US2:PNW3048L1200C Load Center Datasheet
Datasheet for the Siemens US2:PNW3048L1200C, a low voltage plug-on neutral ready pro series assembled load center with 30 spaces, 48 circuits, 1-phase, 3-wire system, rated 120/240V (200A), 100KAIC, featuring copper bus, grey trim, and NEMA Type 3R outdoor enclosure.
Preview Siemens SN1224L1125 Indoor Load Center: Safety and Installation Guide
Essential safety warnings, installation guidelines, and technical specifications for the Siemens SN1224L1125 Indoor Load Center, a Plug-On Neutral Ready Type 1 electrical panel.
Preview Siemens MC2442B1200EFV Meter Load Center Combination - 200A, Flush Mount
Technical specifications and features for the Siemens MC2442B1200EFV Meter Load Center Combination. This 200A, 24-space, 42-circuit unit is designed for overhead or underground service entry and flush mounting, suitable for solar applications.
Preview Siemens US2:PNW1224B1100C Data Sheet - Low Voltage Plug-On Neutral Ready Load Center
Technical data sheet for the Siemens US2:PNW1224B1100C Load Center. Features include 100A ampacity, 120/240V, 22KAIC, copper bus, NEMA Type 3R enclosure for outdoor use, and UL certification.
Preview Siemens US2:SN4264L1225 Load Center - 225A, 42 Spaces, 120/240V
Data sheet for the Siemens US2:SN4264L1225 assembled load center. Features include 42 1-inch spaces, 225A ampacity, 120/240V rating, aluminum bus, grey trim, and NEMA Type 1 enclosure for residential and light commercial use.
Preview Siemens Plug-On Neutral Load Centers and Electronic Breakers
Siemens offers durable, innovative, and safe plug-on neutral load centers with electronic breakers for secure connections and confident installations. Features include quicker breaker installation, easier wiring, small breaker footprint, and ample wire bending space.
Preview Siemens Circuit Breaker Installation Guide
Comprehensive installation instructions for Siemens and Murray circuit breakers, covering safety warnings, breaker types, and step-by-step installation procedures. Includes guidance for plug-in and bolt-on models.
Preview Siemens Meter Centers: SOLAR Ready, 1-Phase, 3-Wire 120/240V AC Combinations
Detailed specifications and product catalog for Siemens Meter Centers, including EUSERC compliant and non-EURSERC models, designed for solar readiness and 1-phase, 3-wire 120/240V AC applications.