Owner's Manual for MEAN WELL models including: HDR-30-24 AC-DC Power Supply, HDR-30-24, AC-DC Power Supply, Power Supply, Supply

HDR-30-24 Mean Well From 477.4 UAH - РАДИОМАГ РКС КОМПОНЕНТЫ Manufacturer: Mean-Well USA, Inc. AC/DC Power Supply Single-OUT 24V 1.5A 36W 4-Pin

HDR-30-24 MeanWell від 477.4 грн - РАДИОМАГ РКС КОМПОНЕНТЫ


File Info : application/pdf, 4 Pages, 206.54KB

PDF preview unavailable. Download the PDF instead.

hdr-30-spec
30W Ultra Slim Step Shape DIN Rail

HDR-30 series
User's Manual



UL508

UL62368-1

Features

Bauar t gepruft Sicherheit
egel ma ge od o s be wac g
www. tuv.com ID 2000000000
BS EN/EN61558

R33100 RoHS

TPTC004 AS/NZS60950-1 IEC62368-1

Ultra slim design with 35mm(2SU) width

Universal input 85~264VAC(277VAC operational)

No load power consumption<0.3W

Isolation class 

Pass LPS (Limited power source)

DC output voltage adjustable

Protections : Short circuit / Overload / Over voltage

Cooling by free air convection (working temperature:-30~+70°C)

DIN rail TS-35/7.5 or 15 mountable

LED indicator for power on

3 years warranty

 Applications
Household control system Building automation Industrial control system Factory automation Electro-mechanical apparatus
 GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

 Description
HDR-30 is one economical ultra slim 30W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 35mm(2SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-30 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 90%, the entire series can operate at the ambient temperature between -30 and 70 under air convection. The complete protection functions and relevant certificates for home automations and industrial control apparatus (IEC62368-1, UL508,UL62368-1, BS EN/EN61558-2-16) make HDR-30 a very competitive power supply solution for household and industrial applications.
 Model Encoding HDR - 30 - 12

Downloaded from Arrow.com.

Output voltage Rated wattage Series name

File Name:HDR-30-SPEC 2022-12-02

30W Ultra Slim Step Shape DIN Rail

HDR-30 series

SPECIFICATION

MODEL

HDR-30-5

HDR-30-12

HDR-30-15

HDR-30-24

HDR-30-48

OUTPUT

DC VOLTAGE

5V

12V

15V

RATED CURRENT

3A

2A

2A

CURRENT RANGE

0 ~ 3A

0 ~ 2A

0 ~ 2A

RATED POWER

15W

24W

30W

RIPPLE & NOISE (max.) Note.2 80mVp-p

120mVp-p

120mVp-p

VOLTAGE ADJ. RANGE

4.5 ~ 5.5V

10.8 ~ 13.8V

13.5 ~ 18V

VOLTAGE TOLERANCE Note.3 ±2.0%

±1.0%

±1.0%

LINE REGULATION

±1.0%

±1.0%

±1.0%

LOAD REGULATION

±1.0%

±1.0%

±1.0%

SETUP, RISE TIME

500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load

HOLD UP TIME (Typ.)

30ms/230VAC 12ms/115VAC at full load

24V 1.5A 0 ~ 1.5A 36W 150mVp-p 21.6 ~ 29V ±1.0% ±1.0% ±1.0%

48V 0.75A 0 ~ 0.75A 36W 240mVp-p 43.2 ~ 55.2V ±1.0% ±1.0% ±1.0%

VOLTAGE RANGE

85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational )

FREQUENCY RANGE

47 ~ 63Hz

INPUT EFFICIENCY (Typ.)

82%

88%

89%

89%

90%

AC CURRENT (Typ.)

0.88A/115VAC 0.48A/230VAC

INRUSH CURRENT (Typ.) COLD START 25A/115VAC 45A/230VAC

OVERLOAD PROTECTION

105 ~ 160% rated output power Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed

ENVIRONMENT

OVER VOLTAGE
WORKING TEMP. WORKING HUMIDITY STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION

5.75 ~ 7.5V

15 ~ 18V

18.8 ~ 22.5V

30 ~ 36V

57.6~ 67.2V

Protection type : Shut down o/p voltage, re-power on to recover

-30 ~ +70 (Refer to "Derating Curve")

20 ~ 90% RH non-condensing

-40 ~ +85, 10 ~ 95% RH non-condensing

±0.03%/ (0 ~ 50) RH non-condensing

10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6

OPERATING ALTITUDE 2000 meters

OVER VOLTAGE CATEGORY
SAFETY STANDARDS WITHSTAND VOLTAGE

; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters
UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1,IEC62368-1, EAC TP TC 004, BSMI CNS14336-1 approved; Design refer to TUV BS EN/EN62368-1 I/P-O/P:4KVAC

ISOLATION RESISTANCE I/P-O/P:100M Ohms / 500VDC / 25/ 70% RH

Parameter

Standard

Test Level / Note

Conducted

BS EN/EN55032(CISPR32), CNS13438 Class B

EMC EMISSION

Radiated

BS EN/EN55032(CISPR32), CNS13438 Class B

Harmonic Current

BS EN/EN61000-3-2

Class A

SAFETY &
EMC
(Note 4)

Voltage Flicker

BS EN/EN61000-3-3

BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3

Parameter

Standard

ESD

BS EN/EN61000-4-2

-------
Test Level /Note Level 3, 8KV air; Level 2, 4KV contact, criteria A

Radiated Susceptibility

BS EN/EN61000-4-3

Level 3, criteria A

EMC IMMUNITY

EFT/Burest Surge

BS EN/EN61000-4-4 BS EN/EN61000-4-5

Level 3, criteria A Level 4,2KV/L-N, criteria A

Conducted

BS EN/EN61000-4-6

Level 3, criteria A

MTBF

Magnetic Field

BS EN/EN61000-4-8

Voltage Dips and interruptions BS EN/EN61000-4-11

3670.4K hrs min. Telcordia SR-332 (Bellcore) ; 968.1K hrs min.

Level 4, criteria A 95% dip 0.5 periods, 30% dip 25 periods, 95% interruptions 250 periods
MIL-HDBK-217F (25)

OTHERS DIMENSION

35*90*54.5mm (W*H*D)

PACKING

0.12Kg;96pcs/12.5Kg/1.1CUFT

NOTE

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1f & 47f parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC

directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.

(as available on http://www.meanwell.com)

5. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft).

 Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

File Name:HDR-30-SPEC 2022-12-02

Downloaded from Arrow.com.

30W Ultra Slim Step Shape DIN Rail
Block Diagram

HDR-30 series

I/P

EMI FILTER

RECTIFIERS &
FILTER

POWER SWITCHING

RECTIFIERS &
FILTER

+V -V

O.L.P.

CONTROL

DETECTION CIRCUIT
O.V.P.

Derating Curve

Output Derating VS Input Voltage

100
80
60 50 40
20
-30 0 10 20 30 40 50 60 70 (VERTICAL)
AMBIENT TEMPERATURE ()

100 90 80 70 60 50 40
85 95 100 115 120 140 160 180 200 220 240 264 277 (operational)
INPUT VOLTAGE (VAC) 60Hz

LOAD (%) LOAD (%)

Downloaded from Arrow.com.

File Name:HDR-30-SPEC 2022-12-02

30W Ultra Slim Step Shape DIN Rail
Mechanical Specification (Unit: mm , tolerance ± 0.5mm)
35
21

HDR-30 series
58.4 54.5

90 63.65 45.15

43

ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15

Terminal Pin No. Assignment

Pin No. Assignment

1

+V

2

-V

Pin No. Assignment

3

AC/L

4

AC/N

Installation Manual Please refer to : http://www.meanwell.com/manual.html

Downloaded from Arrow.com.

35

File Name:HDR-30-SPEC 2022-12-02



References

iText 5.5.6 ©2000-2015 iText Group NV (AGPL-version) (AGPL-version)