Hager MJN506 Miniature Circuit Breaker Datasheet

Technical Characteristics

Placeholder image for MJN506 circuit breaker.

Design

CharacteristicValue
Neutral terminal positionRight
Number of protected poles1
Number of poles2 P
Pole type1P+N
Tripping characteristicC

Functions

CharacteristicValue
With switched neutral conductorYes

Execution

CharacteristicValue
Number of modules1

Connectivity

CharacteristicValue
Highest connection alignment for modular equipmentStaggered

Main Electrical Characteristics

CharacteristicValue
Rated breaking capacity4.5 kA
Rated voltage (AC)230/240 V
Type of supply voltageAC
Frequency50/60 Hz

Voltage

CharacteristicValue
Rated insulation voltage500 V
Maximum operating voltage253 V
Impulse withstand voltage4000 V

Current

CharacteristicValue
Rated current Inom6 A
Operating breaking capacity according to EN 608984.5 kA
Thermal protection setting1.13/1.45 In
Magnetic maximum setting5/10 In
Rated breaking capacity4.5 kA

Current / Temperature

TemperatureAssigned Current
Assigned current at -25°C7.6 A
Assigned current at -20°C7.5 A
Assigned current at -15°C7.3 A
Assigned current at -10°C7.2 A
Assigned current at -5°C7.1 A
Assigned current at 0°C6.9 A
Rated current at 30°C6 A
Rated current at 35°C5.9 A
Rated current at 40°C5.8 A
Rated current at 45°C5.6 A
Rated current at 50°C5.5 A
Rated current at 55°C5.4 A
Rated current at 60°C5.2 A
Rated current at 65°C5.1 A
Rated current at 70°C4.9 A

Current Conversion Factor

ConditionFactor
Conversion factor rated current for 2 circuit breakers placed next to each other1
Conversion factor rated current for 3 circuit breakers placed next to each other0.95
Conversion factor rated current for 4 and 5 circuit breakers placed next to each other0.9
Conversion factor rated current for 6 circuit breakers placed next to each other0.85
Conversion factor electromagnetic values at 100 Hz1.1
Conversion factor electromagnetic values at 200 Hz1.2
Conversion factor electromagnetic values at 400 Hz1.5
Conversion factor electromagnetic values at 16 2/3 to 60 Hz1

Dimensions

CharacteristicValue
Installed product depth70 mm
Installed product height84.7 mm
Installed product width17.5 mm

Frequency

CharacteristicValue
Frequency50 to 60 Hz

Power

CharacteristicValue
Power loss at rated current1.8 W
Power loss per pole1.7 W

Lifespan

CharacteristicValue
Electrical lifespan in number of cycles1000
Maximum number of mechanical operations20000

Mounting

CharacteristicValue
Top connection type for modular equipmentScrew terminal
Tightening torque1.9 Nm
Bottom rail clip type for modular equipmentPlastic
Bottom connection type for modular equipmentScrew terminal
Removable from top for modular equipmentNo
Removable from bottom for modular equipmentYes
Suitable for flush mountingYes

Connection

CharacteristicValue
Output connection cross-section with screw terminal for flexible conductors1/16 mm²
Output connection cross-section with screw terminal for rigid conductors1/25 mm²
Input connection cross-section with screw terminal for rigid conductors1/25 mm²
Input connection cross-section with screw terminal for flexible conductors1/16 mm²
Input/output connection cross-section with screw terminal for rigid conductors1/25 mm²
Input/output connection cross-section with screw terminal for flexible conductors1/16 mm²
Connection typeScrew technology

Standards

CharacteristicValue
StandardEN 60898-1
European WEEE directiveApplicable

Safety

CharacteristicValue
Protection degree (IP)IP20

Operating Conditions

CharacteristicValue
Operating temperature-25...70 °C
Degree of pollution IEC 6642
Current limiting class3
Altitude2000 m
Tropical resistanceFor all climates
Storage/transport temperature-25...80 °C

PDF preview unavailable. Download the PDF instead.

MJN506 wkhtmltopdf 0.12.4 Qt 4.8.7

Related Documents

Preview Hager MJN506 Installatieautomaat Productdatablad
Gedetailleerde technische specificaties voor de Hager MJN506 1P+N 6A C-karakteristiek installatieautomaat, inclusief stroom, spanning, afmetingen en aansluitgegevens.
Preview Hager ADC932R RCBO: Installation and Usage Guide
This guide provides essential information for installing and using the Hager ADC932R Residual Current Operated Circuit-Breaker (RCBO) with switched neutral. It covers electrical connection, mounting, testing, and specific application guidance, including EV charger installations.
Preview Hager RCBO Installation and Guidance Manual
Comprehensive guide for installing and using Hager Residual Current Operated Circuit-Breakers (RCBOs), including electrical connections, mounting, testing, and specific guidance for EVCS applications.
Preview Hager MJN506 Installatieautomaat: 1P+N 6A C-karakteristiek Datasheet
Gedetailleerde technische datasheet voor de Hager MJN506 installatieautomaat, een 1P+N 6A C-karakteristiek stroomonderbreker met 4,5 kA uitschakelvermogen. Bevat specificaties over ontwerp, elektrische eigenschappen, afmetingen, montage en veiligheidsnormen.
Preview Hager Safety Switch (RCCB) 25-100A: Installation and Usage Guide
Comprehensive guide to Hager's Safety Switches (RCCBs) from 25-100A, covering installation, electrical connections, safety instructions, and operational indicators. Includes technical specifications and usage notes for electricians.
Preview Hager RCBO Application Guidance: Ensuring Correct Installation
Guidance from Hager on RCBO application, covering issues with neutral switching and unidirectional RCBOs, with solutions for correct installation and product selection. Includes technical details for ADC920R and ADA920U models.
Preview Hager AFDD Troubleshooting Guide: What to Do When Your AFDD Trips
Comprehensive guide from Hager on troubleshooting AFDD (Arc Fault Detection Device) trips, covering diagnostics, LED status codes, and specific fault scenarios like arc faults, residual current faults, overloads, and overvoltages.
Preview Hager Residual Current Breakers Operated RCBO 6-50A Installation and Safety Guide
This document provides installation instructions and safety warnings for Hager Residual Current Breakers Operated RCBO 6-50A. It details warranty information, electrical diagrams, and operational procedures for qualified contractors.