Instruction Manual for Intesis models including: INMBSHIS000O000, Home Automation Gateway

INMBSHIS---O000 Installation Manual

Hisense, Intesis, HMS, BMS, SCADA, PLC, VRF, Modbus, Master, Installation, Manual

HMS Networks S.L.U.

Owner’s Record INMBSHIS***O000 The serial number is ...

Follow instructions of the user's manual for more details. Owner’s Record The serial number is located at the rear of the gateway. Record this information in the space provided below. Refer to it whenever you contact upon your gateway dealer or support team regarding this product.

INMBSHIS---O000 Installation Manual

Serial No. Safety instructions. Installation. ... Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and...

INMBSHIS---O000 Installation Manual - Intesis

WARNING. Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health.


File Info : application/pdf, 2 Pages, 316.06KB

PDF preview unavailable. Download the PDF instead.

installation-sheet-inmbshisxxxo000
INMBSHIS***O000
Hisense to Modbus Slave or to Home Automation gateway
Order Code: INMBSHIS***O000
** stands for the Intesis gateway capacity and varies depending on the specific gateway acquired
Installation Sheet rev.1.1
HMS Industrial Networks S.L.U. ©

Owner's Record
The serial number is located at the rear of the gateway. Record this information in the space provided below. Refer to it whenever you contact upon your gateway dealer or support team regarding this product.
Serial No.

SAFETY INSTRUCTIONS

INSTALLATION

! WARNING
Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the Intesis gateway and/or any other equipment connected to it.
The Intesis gateway must be installed by accredited electrician or similar technical personnel, following all the safety instructions given here and in accordance always with the country legislation for installation of electric equipment.
The Intesis gateway cannot be installed outdoors or exposed to direct solar radiation, water, high relative humidity or dust.
The Intesis device must only be installed in a restricted access location.
In case of wall mount, fix firmly the Intesis gateway on a not vibrating surface following the instructions next.
In case of DIN rail mount fix the Intesis device properly to the DIN rail following the instructions below.
Mounting on DIN rail inside a metallic cabinet properly connected to earth is recommended.
Disconnect always power of any wires before manipulating and connecting them to the Intesis gateway.
A power supply with an NEC Class 2 or Limited Power Source (LPS) and SELV rated is to be used.
Respect always the expected polarity of power and communication cables when connecting them to the Intesis gateway.
Supply always a correct voltage to power the Intesis device, see details of voltage range admitted by the device in the technical characteristics below.
CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type. Dispose of Used Batteries according to the instructions. Battery replacement shall be done by an authorized installer.
CAUTION: The device is to be connected only to networks without routing to the outside plant, all communication ports are considered for indoor only and can be connected SELV circuits only.
This device was designed for installation in an enclosure. To avoid electrostatic discharge to the unit in environments with static levels above 4 kV, precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure (ex. making adjustments, setting switches etc.) typical anti-static precautions should be observed before touching the unit.
Safety instructions in other languages can be found at: https://intesis.com/docs/manuals/v6-safety
CONFIGURATION Use the Configuration Tool to configure the gateway.
See instructions to download and install the latest version at: https://intesis.com/docs/software/intesis-maps-installer
Use the Ethernet connection or the Console Port (mini USB type B connector included) to get communication between the gateway and the configuration tool.
Follow instructions of the user's manual for more details.
Rev.1.0 © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice

Follow instructions next to properly install the gateway.
Disconnect from mains the power supply before connecting it to the Intesis device.
Disconnect power of any bus or communication cable before connecting it to the Intesis device.
Mount the Intesis gateway on the wall or DIN rail following the instruction given below, respecting the safety instructions given above.
Connect a NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply to the Intesis gateway, respect the polarity if DC power or Line and Neutral if AC power. Apply always a voltage within the range admitted by the Intesis gateway and of enough power (see technical characteristics).
Circuit-breaker must be used before the power supply. Rating 250V6A.
Connect the communication cables to the Intesis gateway, see details on the user's manual.
Power the Intesis device and the rest of devices connected to it.
NOTE: The device cannot be installed in air-handling space.
Wall Mount
1. Separate the fixing clips in the bottom of the box, pushing them to the outside until hear the "click" which indicates that now the clips are in position for wall mount, see in the figure below.
2. Use the holes of the to fix the box in the wall using screws. Use the template below for the wall wholes.

Press

Press

Press

Clips in their original position Clips in position for wall mount (for DIN rail mount)
DIN Rail Mount
With the clips of the box in their original position, insert first the box in the upper edge of the DIN rail and later insert the box in the down part of the rail, using a small screwdriver and following the steps in the figure below.

URL

https://www.intesis.com

1 / 2

CONNECTIONS

Power Supply

Hisense H-Link TB2

Ethernet

Power Supply Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply.

Modbus TCP

If using DC power supply:

Home Automation Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted

(check table below). The power supply can be connected to earth but only through the negative terminal,

never through the positive terminal.

If using AC power supply: Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the AC power supply to earth, and make sure the same power supply is not supplying any other device.

Ethernet / Modbus TCP (TCP) / Home Automation (WMP) / Console (UDP & TCP) Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of the building, contact the network administrator and make sure traffic on the port used is allowed through all the LAN path (check the gateway user manual for more information). Default IP is 192.168.100.246.
PortA / H-Link Hisense Connect the H-Link terminals (TB2) of Hisense Outdoor Unit to the connectors A3 and A4 of gateway's PortA. There is no polarity to be respected.

Console Port

PortB / Modbus RTU Connect the EIA485 bus to connectors B1 (B+), B2 (A-) and B3 (SNGD) of gateway's PortB. Respect the polarity. Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, maximum 32 devices connected to the bus, and in each end of the bus it must be a termination resistor of 120 . Bus biasing and termination resistor for EIA485 can be enabled for PortB by means of a dedicated DIP switch ­ see table below.
Connect the serial cable EIA232 coming from the external serial device to the EIA232 connector of gateway's PortB. This is a DB9 male (DTE) connector in which only the lines TX, RX and GND are used. Details of the pinout can be seen in the user's manual. Respect the maximum distance of 15 meters.

USB storage

Modbus RTU EIA232

Modbus RTU EIA485

Console Port Connect a mini-type B USB cable from your computer to the gateway to allow communication between the Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user manual for more information.
USB Connect a USB storage device (not a HDD) if required. Check the user manual for more information.

ELECTRICAL & MECHANICAL FEATURES

Enclosure
Mounting
Terminal Wiring
(for power supply and low-voltage signals)

Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): 90x88x56 mm Recommended space for installation (dxwxh): 130x100x100mm Color: Light Grey. RAL 7035
Wall. DIN rail EN60715 TH35.
Per terminal: solid wires or stranded wires (twisted or with ferrule)
1 core: 0.5mm2... 2.5mm2 2 cores: 0.5mm2... 1.5mm2 3 cores: not permitted If cables are more than 3.05 meters long, Class 2 cable is required.

Power

1 x Plug-in screw terminal block (3 poles)
9 to 36VDC +/-10%, Max.: 140mA. 24VAC +/-10% 50-60Hz, Max.: 127mA Recommended: 24VDC

Ethernet Port A

1 x Ethernet 10/100 Mbps RJ45 2 x Ethernet LED: port link and activity
1 x H-Link Plug-in screw terminal block orange (2 poles)
1500VDC isolation from other ports
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use

Switch A
(SWA)

1 x DIP-Switch for PORTA configuration:
Reserved for future use (leave OFF, default)

Battery
Console Port
USB port
Push Button Operation Temperature Operational Humidity Protection
LED Indicators

Size: Coin 20mm x 3.2mm Capacity: 3V / 225mAh Type: Manganese Dioxide Lithium
Mini Type-B USB 2.0 compliant 1500VDC isolation Type-A USB 2.0 compliant Only for USB flash storage device (USB pen drive) Power consumption limited to 150mA (HDD connection not allowed) Button A: Not used Button B: Not used
0°C to +60°C
5 to 95%, no condensation
IP20 (IEC60529) 10 x Onboard LED indicators
2 x Run (Power)/Error 2 x Ethernet Link/Speed 2 x Port A TX/RX 2 x Port B TX/RX 1 x Button A indicator 1 x Button B indicator

PORT B
Switch B
(SWB)

1 x Serial EIA232 (SUB-D9 male connector)
Pinout from a DTE device 1500VDC isolation from other ports (except PORT B: EIA485)
1 x Serial EIA485 Plug-in screw terminal block (3 poles)
A, B, SGND (Reference ground or shield) 1500VDC isolation from other ports (except PORT B: EIA232)
1 x DIP-Switch for serial EIA485 configuration: Position 1:
ON: 120  termination active Off: 120  termination inactive (default)
Position 2-3:
ON: Polarization active Off: Polarization inactive (default)

100 mm (h) 100 mm (w)

130 mm (d)

This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic parts and they must be properly disposed of by following the instructions at https://intesis.com/weee-regulation
Rev.1.0 © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice

URL

https://www.intesis.com

2 / 2

