Installation Instructions

Freeze Sensor Connection Kit

For Select Watts and FEBCO Valve Assemblies or Standalone Operation

Important Safety Information

WARNING: Read this Manual BEFORE using this equipment. Failure to read and follow all safety and use information can result in death, serious personal injury, property damage, or damage to the equipment. Keep this Manual for future reference.
WARNING: You are required to consult the local building and plumbing codes prior to installation. If the information in this manual is not consistent with local building or plumbing codes, the local codes should be followed. Inquire with governing authorities for additional local requirements.
WARNING: Freeze sensor solely provides alerts about a possible freeze event and cannot prevent a freeze event from occurring. User action is required to prevent freeze conditions from causing product and/or property damage.
NOTICE: Use of the freeze sensor does not replace the need to comply with all required instructions, codes, and regulations related to installation, operation, and maintenance of this product, including the need to provide protection against a freeze event. Watts is not responsible for the failure of alerts due to connectivity issues, power outages, or improper installation.

Product Overview

Utilizes smart and connected sensor technology with valve installations to monitor temperature and alert facility personnel when freeze conditions can cause damage to equipment. The Freeze Sensor Connection Kit includes two temperature sensors, allowing the user to choose which is more suitable for installation. One sensor can be mounted to a valve assembly; the other can be installed outdoors as a standalone unit.

When the kit is installed with either sensor, the sensor is activated and wired to a monitoring system. As temperature nears and reaches the freezing point, the monitoring system relays a signal to a connected building or irrigation management system, allowing freeze alerts to be distributed according to the BMS or IMS application. When the monitoring system is Wi-Fi enabled, notifications can be issued through the Smart Freeze Alert cloud service.

Kit Components

Requirements

Installation and Setup

Setting Up the Valve

The freeze sensor is shown installed on a FEBCO 765 PVB. The installation steps are the same for any Watts or FEBCO valve that has a freeze sensor.

  1. For retrofit installation only. Snap the mounting clip with the freeze sensor over one of the valve's test cocks.
  2. Remove the insulation from the freeze sensor leads.
  3. Use the wire stripper to cut ½" insulation off both ends of the 2-conductor cable connecting the sensor to the activation module.
  4. Connect the freeze sensor leads to one end of the cable using the provided weather-proof wire nuts.
  5. Use the tie to strap the first segment of the cable to the valve.

Using the Standalone Outdoor Sensor

The standalone outdoor sensor can be installed instead of the valve-mounted sensor. For more information on installation, refer to tekmar Outdoor Sensor 070 at watts.com.

Wiring the Activation Module

The following steps apply to both the valve-mounted sensor and the standalone outdoor sensor.

  1. Grasp the finger recesses on the top and bottom of the activation module and pull off the cover.
  2. Connect the positive wire of the power adapter (black with white stripes) to terminal 1 and the ground wire to terminal 2.
  3. Connect one wire of the sensor cable to terminal 3 and the other wire to terminal 4.
  4. Use the wire stripper to cut ½" insulation off both ends of the system cable connecting the activation module to the building or irrigation management system.
  5. Connect one wire of the system cable to COM terminal 6 and the other wire to either NO terminal 5 or NC terminal 7.
  6. Follow the manufacturer's instructions to connect the other end of the cable to the building or irrigation management system.
  7. Replace the module cover and plug the power adapter into a 120 V AC, 60 Hz, GFI-protected electrical outlet or connect it to a DC 24 V power source.
  8. Mount the module in an unobstructed location for the best Wi-Fi signal.

Terminal Connections:

Setting Up the Alert System on a Wi-Fi Network

Hardware installation must be completed before product registration and Wi-Fi setup. Ensure that electrical power and Wi-Fi are available. The activation module does not need to be Wi-Fi enabled to work with a building or irrigation management system. Enable Wi-Fi to send email alerts independently of a third-party controller.

Initiating the Process
  1. After plugging in the activation module, wait until the Wi-Fi blue LED starts to blink.
  2. Use a mobile phone or computer to scan for new Wi-Fi networks, then:
    • Choose FreezeMonitorSetup-xxxxx. (The variable is a unique alphanumeric string for the device.)
    • Enter the password freezemonitor.
  3. If the Watts webpage does not open automatically, launch a web browser and enter http://10.10.0.1, or scan the QR code.
  4. Review the privacy policy by scrolling to the end, then tap Agree and Continue.
  5. Review the terms of use by scrolling to the end, then tap Agree and Continue.
  6. When the setup menu appears, tap Begin to complete the 4-step process.
Completing the Setup

Step 1 Product Registration: Complete the required fields (marked with *) to register the product, then tap Next.

Step 2 Setup: Complete the required fields to configure the valve assembly, then tap Next.

Step 3 Notifications: Enter contact information for real-time notifications, then tap Next.

Step 4 Connect: Connect to the desired Wi-Fi network, then tap Next.

NOTE: If your desired network is not visible, or if you are having difficulty connecting, contact your network administrator. High-security networks may require additional permissions.

Testing the Connection

Press the multifunction button on the module for at least 15 seconds to send the message. The Low Temperature alert serves as the test message.

How the Alert System Works

The freeze sensor measures temperature when energized by the freeze sensor activation module. The relay activates at 37°F (2.7°C) and remains active below 32°F (0°C).

The activation module can connect to a building management system, irrigation management system, or a Wi-Fi network. When connected to Wi-Fi, the system can be configured to send alerts via email and text message.

Press the multifunction button for the minimum number of seconds indicated to activate a function. Call customer service for technical assistance.

FUNCTIONPRESS (IN SECONDS)NOTE
Messages OFF (Muted)1Silences messaging. This function is not toggled. A change in conditions (e.g., temperature drop) or Wi-Fi status change resets this function to Messages ON.
Wi-Fi ON/OFF3Activates or deactivates the Wi-Fi function.
Reset10Clears all temporary data.
Test15Sends the Low Temperature alert during testing.

Messaging

Messaging is aligned with measured temperature. To silence messaging, press the multifunction button for 1 to 3 seconds. The Messaging ON function is restored by a change in condition (such as a temperature increase or decrease) or Wi-Fi status, as well as a reset or power cycle.

Temperature Alert Levels:

Messaging Table:

MESSAGENOTE
Device Registered (Wi-Fi enabled activation module)Indicates the Wi-Fi enabled activation module is successfully registered and connected to the cloud service. Alerts are sent to the contact entries provided during setup (email address required, mobile phone number optional).
Sensor ErrorIndicates the freeze sensor may be faulty, measuring temperature out of range, or improperly wired to the activation module. An alert is sent once every 24 hours. This error message is also sent if there are issues with initial and subsequent hardware installation.
Low Temperature AlertIndicates the current temperature is near the freezing point. An alert is sent after 2 hours when the temperature is measured between 32°F and 37°F. A reminder is issued every 12 hours if the temperature remains in this range. Normal operation resumes after 4 hours when the temperature exceeds 37°F. No alerts are issued. This alert also serves as a test message.
Low Temperature ReminderIndicates the current temperature is near the freezing point. This alert is sent every 12 hours when the temperature is measured between 32°F and 37°F. Normal operation resumes after 4 hours when the temperature exceeds 37°F. No alerts are issued.
Freezing Temperature AlertIndicates the current temperature is below the freezing point. An alert is sent after 2 hours when the temperature is measured below 32°F. A reminder is issued every 12 hours if the temperature remains in this range. When the temperature rises above 32°F, the Low Temperature reminder is sent every 12 hours when the temperature is measured between 32°F and 37°F.
Freezing Temperature ReminderIndicates the current temperature is below the freezing point. This reminder is sent every 12 hours when the temperature is measured below 32°F. When the temperature rises above 32°F, the Low Temperature alert is sent after 2 hours when the temperature is measured between 32°F and 37°F.
Device Lost Connectivity to Cloud ServiceIndicates no connection between the Wi-Fi enabled module and the cloud service. Alerts are sent accordingly. After 1 hour, the disconnected device can reestablish connectivity and resume alerts. After 24 hours, it can reestablish connectivity and resume alerts. If connection is not made by the specified date, the device is unregistered. After 5 days, the device can reestablish connectivity and resume alerts. If connection is not made by the specified date, the device is unregistered. After 30 days, the device is unregistered, and alerts are no longer issued.
Device Reestablished Connectivity to Cloud ServiceIndicates the Wi-Fi enabled module has reconnected to the cloud service.
Device UnregisteredIndicates no connection between the Wi-Fi enabled module and the cloud service. Alerts are no longer issued. The module must be reset and reregistered to send alerts. If re-registered and reconnected, no notifications regarding connection/disconnection are sent for 24 hours from reconnection.

LED Reference

LED STATUSGREENBLUERED
Power OFFOFFOFFOFF
LED function verificationON 1 sON 1 sON 1 s
Power ONONONOFF
Access Point modeBlink 4 Hz
Client connected (Access Point mode)Blink 2 Hz
Client disconnected (Access Point mode)Blink 4 Hz
Wi-Fi disconnected (Station mode)Blink 2 Hz
Wi-Fi connected (Station mode)Blink 1 Hz
IoT Hub disconnected (Station mode)Blink 1 Hz
IoT Hub connected (Station mode)Solid ON if IoT Hub connected
Wi-Fi disabledOFFOFF
Low temperatureBlink 1 Hz
Freezing temperatureBlink 2 Hz
Temperature sensor errorBlink 4 Hz
After pressing the multifunction button for more than 1 s but less than 3 s (Disable repeat alert)Blink 8 Hz
After pressing the multifunction button for more than 3 s but less than 10 s (Wi-Fi ON/OFF toggle)Blink 8 Hz
After pressing the multifunction button for more than 10 s but less than 15 s (Factory reset)Blink 8 Hz
After pressing the multifunction button for more than 15 s (Installer Test mode)Blink 2 HzBlink 2 HzBlink 2 Hz
Credential missing (Factory calibration required)Blink 2 HzBlink 2 HzBlink 6 Hz
Communication error with sensor controller
Factory Calibration modeONONON
End Factory Calibration mode (PASS)ONOFFON

Radio Frequency Safety

FCC Compliance Statement

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur during a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:Changes or modifications to this equipment not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

ISED Compliance Statement

This device complies with the Industry Canada license-exempt Radio Standards Specification. Operation is subject to the following two conditions.

Limited Warranty

Watts Regulator Co. (the "Company") warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.

Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.

Models: IS-FZ Freeze Sensor Connection Kit, IS-FZ, Freeze Sensor Connection Kit, Sensor Connection Kit, Connection Kit, Kit

File Info : application/pdf, 24 Pages, 3.03MB

PDF preview unavailable. Download the PDF instead.

IS-FZSensorConnectionKit+2409

References

Adobe PDF Library 17.0

Related Documents

Preview Watts IS-FS-BMS Flood Sensor Connection Kit Installation Guide
Comprehensive installation guide for the Watts BMS Flood Sensor Connection Kit (Model IS-FS-BMS). Learn step-by-step instructions for setup, wiring, and requirements for integrating flood detection into your building management system.
Preview Watts Backflow Preventer Flood Detection System
Watts offers advanced flood detection for RPZ/RPDA backflow preventers, providing 24/7 monitoring, real-time alerts via phone/text/email, and protection against water damage. Learn how to add flood detection to new or existing installations.
Preview Watts Series 800M4, LF800M4 Pressure Vacuum Breaker Assemblies: Installation, Maintenance, and Repair Manual
Comprehensive guide for installing, maintaining, and repairing Watts Series 800M4 and LF800M4 Pressure Vacuum Breaker Assemblies. Covers safety, installation procedures, servicing, freeze protection, and warranty.
Preview Watts LFF113FP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology
Detailed information on the Watts LFF113FP Wireless Smart Flood Protection Shut Down Valve, including its features, materials, operation, specifications, and flow data. This valve is designed to automatically shut off water flow in case of continuous discharge from an RPZ Backflow Preventer.
Preview Watts IntelliFlow A2C-SC/A2C-SC-WB Installation Instructions
Installation guide for Watts IntelliFlow A2C-SC and A2C-SC-WB smart water shutoff and leak detection system for washing machines. Covers setup, operation, specifications, and troubleshooting to prevent water damage.
Preview BT-CT03 RF Central Unit WIFI: Installation and Operational Manual
Comprehensive guide to installing and operating the Watts BT-CT03 RF Central Unit WIFI, a smart home controller for heating and cooling systems with multi-zone management and Wi-Fi connectivity.
Preview Watts Home Mobile App: Installation, Operation, and Maintenance Guide
A comprehensive guide to installing, operating, and maintaining the Watts Home Mobile App. Learn how to manage Watts, tekmar, and SunTouch smart home devices, including thermostats and snow melting controls, through the app's features like location management, device integration, and user settings.
Preview SunStat ConnectPlus Installation and Operation Manual
This manual provides detailed instructions for the installation and operation of the SunStat ConnectPlus Wi-Fi thermostat, including features, specifications, wiring diagrams, troubleshooting, and warranty information.