The Brute® Deluxe 200-400 Series
Residential and Light Duty Commercial Boilers and Volume Water Heaters
The Bradford White Brute® Deluxe 200-400 Series offers an efficient, economical solution for residential and light commercial space heating and volume water heating applications. Available with inputs of 199,900, 300,000, and 399,000 BTU/Hr., and achieving efficiencies of 85%, these units are designed for high performance and reliability.
Highlights
- 199,900 - 399,900 BTU/Hr. input
- 85% Efficiency
- Installation Flexibility – New and Existing Systems
- Simple Wiring and Controls
- Fan Assisted Combustion
- Ease of Use & Maintenance
- Low NOx Emissions
Finned-Copper Heat Exchanger
The finned-copper heat exchanger provides a high-quality, cost-effective feature that quickly and reliably responds to the heating demands of a wide variety of applications.
Installation Flexibility
The design of the Brute® Deluxe 200-400 Series incorporates simple wiring and controls, along with fan-assisted combustion, to simplify installation in both new and existing heating systems. Units come standard with an indoor/outdoor cabinet and can be configured for Category I, Category III, or outdoor venting. These models comply with DOE 2012 minimum efficiency requirements for boilers and are factory-equipped with a user-friendly boiler reset control system.
Low NOx Emissions
The Brute® Deluxe 200-400 Series features low NOx emissions. NOx (Nitrogen Oxide) is a group of gases formed when fuel burns at high temperatures, which can react with volatile compounds (VOC) to create smog. Brute® Deluxe models exceed stringent air quality regulations, providing efficient heat while minimizing environmental impact.
Standard Features
- ASME 160 psi working pressure heat exchanger
- ASME "H" stamp
- Pump, mounted, and wired
- Flanged water connections
- Glass-lined headers
- External header gaskets
- 75 psi (517 kPa) ASME rated pressure relief valve (Boiler)
- 125 psi (861 kPa) ASME rated pressure relief valve (Water Heater)
- Low lead construction (Water Heater)
- Temperature pressure gauge
- Multiple operating gas valve/pressure regulators
- Manual "A" gas valve
- Intake air filter
- Removable burner tray(s)
- Stainless steel burners
- Built-in fan for Category I or III vent systems
- Air pressure switch
- Blocked vent switch
- Burner site glass
- PI controller
- Outdoor reset with ratios of 0.4 to 3.6 (Boiler)
- Warm weather shutdown (Boiler)
- Indicator lights for power, heat call, DHW call, and WWSD
- DHW operation
- Automatic boiler differential
- Pump pre-purge, post-purge, and exercise
- Blower pre-purge and post-purge
Factory-Mounted Options
- Glass-lined cast-iron headers, cupronickel tubes, bronze trim - HLW Stamp
- Glass-lined cast-iron headers, copper tubes, bronze trim - HLW Stamp
- Soft water pump
- Reversed heat exchanger
- Low water cutoff
Field Installed Accessories
- Inlet, outlet, outdoor, and supply sensors
- Codes for sensor errors
- 24V control system
- 115/24V transformer
- Flow switch
- Manual reset high limit
- Fusible link (size 200)
- On/Off firing
- Certified for indoor or outdoor use
- Hot surface ignition
- On/Off toggle switch
- Pump time delay
- CSD-1 compliant
- Less than 10 ppm NOx
- Side-wall vent terminal for indoor unit with horizontal venting
- Side-wall combustion air terminal for indoor unit with horizontal ducted air
- Air terminal for outdoor unit
- Vent terminal for outdoor unit
Specs at a Glance
Dimensional Data
Model Size (MBTU/Hr.) | A (in.) | A (cm) | B* Air Inlet Conn. (in.) | B* Air Inlet Conn. (cm) | C* Vent Conn. (in.) | C* Vent Conn. (cm) | Horiz. Vent Pipe (in.) | Horiz. Vent Pipe (cm) | Water Connections (in.) | Gas Connections (in.) |
---|---|---|---|---|---|---|---|---|---|---|
200 | 20 1/2 | 52 | 4 | 10 | 5 | 13 | 4 | 10 | 1 1/2 NPT | 3/4 NPT |
300 | 26 1/2 | 67 | 4 | 10 | 6 | 15 | 5 | 13 | 1 1/2 NPT | 3/4 NPT |
400 | 33 1/2 | 85 | 6 | 15 | 7 | 18 | 6 | 15 | 1 1/2 NPT | 3/4 NPT |
*Air and vent connections may be on top or back of the Brute® Deluxe and are field convertible.
Recovery Data
Model Size (MBTU/Hr.) | 40°F (22°C) | 50°F (28°C) | 60°F (33°C) | 70°F (39°C) | 80°F (44°C) | 90°F (50°C) | 100°F (56°C) | 120°F (67°C) | 140°F (78°C) |
---|---|---|---|---|---|---|---|---|---|
200 | GPH: 510 LPH: 1,928 | GPH: 408 LPH: 1,542 | GPH: 340 LPH: 1,285 | GPH: 291 LPH: 1,100 | GPH: 255 LPH: 964 | GPH: 227 LPH: 858 | GPH: 204 LPH: 771 | GPH: 170 LPH: 643 | GPH: 146 LPH: 552 |
300 | GPH: 765 LPH: 2,892 | GPH: 612 LPH: 2,313 | GPH: 510 LPH: 1,928 | GPH: 437 LPH: 1,652 | GPH: 383 LPH: 1,448 | GPH: 340 LPH: 1,285 | GPH: 306 LPH: 1,157 | GPH: 255 LPH: 964 | GPH: 219 LPH: 828 |
400 | GPH: 1,020 LPH: 3,856 | GPH: 816 LPH: 3,084 | GPH: 680 LPH: 2,570 | GPH: 583 LPH: 2,204 | GPH: 510 LPH: 1,928 | GPH: 453 LPH: 1,712 | GPH: 408 LPH: 1,542 | GPH: 340 LPH: 1,285 | GPH: 291 LPH: 1,100 |
Electrical Data
Model Size (MBTU/Hr.) | Boiler / Heater Circuit Size (Volts, Phase, Amps) | Pump Circuit Size (Volts, Phase, Amps) | Blower Circuit Connection |
---|---|---|---|
200 - 400 | 120 Single 15 | Included in Heater | Included in Heater Circuit |
Sizing Data
Model Number | Input (BTU/Hr.) | Input (kW) | Output (BTU/Hr.) | Output (kW) | Shipping Weight (lbs.) | Shipping Weight (kg.) |
---|---|---|---|---|---|---|
BMT2H0200 | 200,000 | 58.6 | 170,000 | 50.4 | 290 | 132 |
BMT2H0300 | 299,000 | 87.6 | 255,000 | 74.7 | 320 | 145 |
BMT2H0400 | 399,000 | 116.9 | 340,000 | 99.6 | 350 | 159 |
BMT2V0200 | 199,900 | 58.6 | 169,915 | 49.8 | 290 | 132 |
BMT2V0300 | 300,000 | 87.9 | 255,000 | 74.7 | 320 | 145 |
BMT2V0400 | 399,900 | 117.2 | 339,915 | 99.6 | 350 | 159 |
Note: Input and output must be derated 4% per 1,000 feet above sea level when installed above 2,000 feet altitude.
Pump Data
Model Number | HP | Amps |
---|---|---|
BMT2H0200 | 1/8 | 1.8 |
BMT2H0300 | 1/8 | 2.0 |
BMT2H0400 | 1/8 | 2.0 |
Model Number | Soft Water (HP, Amps) | Normal Water (HP, Amps) | ||
---|---|---|---|---|
BMT2V0200 | 1/10 | 1.5 | 1/6 | 2.0 |
BMT2V0300 | 1/10 | 1.5 | 1/6 | 2.0 |
BMT2V0400 | 1/10 | 1.5 | 1/6 | 2.0 |
Clearance Data
Appliance Surface | Required Clearance from Combustible Material (in.) | Suggested Service Access Clearance (in.) | ||
---|---|---|---|---|
in. | cm | in. | cm | |
Left Side | 1 | 2.5 | 24 | 61.0 |
Right Side | 1 | 2.5 | 24 | 61.0 |
Top | 1 | 2.5 | 12 | 30.5 |
Back* | 1 | 2.5 | 12 | 30.5 |
Front | 1 | 2.5 | 36 | 91.4 |
Vertical Vent** (Category 1) | 6 (15.2) | |||
Horizontal Vent (Category 3) | Per UL 1738 venting system supplier's instructions |
* When vent and/or combustion air connects to the back, recommended clearance is 36" (91cm). ** 1" when b-vent is used.
Water Flow Data
Model Number | 20°F (11°C) | 25°F (14°C) | 30°F (17°C) | 35°F (19°C) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Flow (GPM) | Flow (LPM) | Flow (GPM) | Flow (LPM) | Flow (GPM) | Flow (LPM) | Flow (GPM) | Flow (LPM) | |||||||||
BMT2H0200 | 17 | 64 | 14 | 53 | 11 | 42 | 10 | 38 | ||||||||
BMT2H0300 | 26 | 97 | 20 | 76 | 17 | 64 | 15 | 57 | ||||||||
BMT2H0400 | 34 | 129 | 27 | 102 | 23 | 87 | 19 | 72 |
Model Number | Hard Water (GPM Rise °F) | Normal Water (GPM Rise °F) | Soft Water (GPM Rise °F) | |||
---|---|---|---|---|---|---|
Flow | Rise °F | Flow | Rise °F | Flow | Rise °F | |
BMT2V0200 | 45 | 8 | 35 | 10 | 23 | 15 |
BMT2V0300 | 45 | 11 | 35 | 15 | 23 | 22 |
BMT2V0400 | 45 | 15 | 35 | 19 | 23 | 30 |
Model Number | Hard Water (LPM Rise °C) | Normal Water (LPM Rise °C) | Soft Water (LPM Rise °C) | |||
---|---|---|---|---|---|---|
Flow | Rise °C | Flow | Rise °C | Flow | Rise °C | |
BMT2V0200 | 170 | 4 | 133 | 6 | 87 | 8 |
BMT2V0300 | 170 | 6 | 133 | 8 | 87 | 12 |
BMT2V0400 | 170 | 8 | 133 | 11 | 87 | 17 |
Note: Soft water: 1 to 7.5 grains per gallon. Normal water: 7.6 to 17 grains per gallon. Hard water: More than 17 grains per gallon.