NLII-RH+T-RS485 | Combined RH/temperature sensor with RS485
Room sensor NLII-RH is used to monitor the air quality inside buildings and control ventilation (HVAC) systems according to current levels of air pollution. The sensor measures the relative humidity (RH) and temperature (T). It is suitable for living rooms, bathrooms, warehouses, ateliers etc.
 measures RH and temperature  RS485 bus communication with Modbus
RTU protocol  maintenance during operation is not
required  long life and stability

Description
Measurement of the relative humidity is based on the principle of capacitive polymer sensor. The sensor provides two outputs over the RS485 bus one for the actual temperature and the other for the actual relative humidity. Sensor can efficiently manage ventilation and heat recovery units, based on current air quality. The current air quality can easily be determined by looking at the three LED indicators. The eco level means good indoor air quality that is needed to achieve a sense of well-being and at the same time optimal energy costs for heating or air conditioning. For information on the communication protocol, use the document NLII-Modbus-komunikace.
Explanation of abbreviations and technical terms can be found on our website in the Glossary section.

Technical data

Parameter
Supply voltage range
Average consumption RH measuring range RH accuracy 20 ­ 80 % RH accuracy 0 ­ 100 % T measuring range T accuracy Working temperature Working humidity non condensing Storage temperature Expected lifetime Ingress protection Dimensions RS485 bus A-B voltage difference A-B common input voltage A-B common output voltage

Value Unit 12 ­ 35 V DC 12 ­ 24 V AC
0,2 W 0 ­ 100 % RH
± 3 % RH ± 6 % RH 0 ­ 50 °C ± 0,4 °C 0 to +50 °C 0 ­ 90 % RH -20 to +60 °C min. 10 years IP20 90x80x31 mm
max 5 V -7 to 12 V
max 3 V

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-rh+t-rs485-en-v2-201027.docx

1/4

User manual

NLII-RH+T-RS485 | Combined RH/temperature sensor with RS485

Typical RH measurement accuracy at 25 °C

LED indication description

White LED lights: Less than 40 % RH or less than 18 °C. (according to the quantity selected for indication)
 low concentrations of RH. Too dry air feels cooler as compared to equally hot but more humid air ­ risk of drying of the mucous membranes - respiratory problems
 low temperature and its higher fluctuation is not economically profitable

Typical T measurement accuracy

Green LED lights: More than or equal to 40 % RH or 18 °C, less than or equal to 60 % RH or 22 °C.
(according to the quantity selected for indication)
 optimal relative humidity for humans
 optimal balance of air quality and energy efficiency of ventilation and air conditioning

CAUTION:

Yellow LED lights: More than 60 % RH or more than 22 °C. (according to the quantity selected for indication)  too high humidity, the risk of mold growth and associated health complications  higher temperature T - high temperature can cause fatigue, restlessness, headache and feeling hot

Warm-up: operational after 1 minute since power on. The declared accuracy is reached after 4 days of continuous power supply. It is necessary to avoid severe mechanical shock of the sensor.

Sensor start after power on
All three LEDs flash simultaneously until the first readings are available, but no longer than 10 seconds.
Sensor failure indication

All three LEDs are shining permanently.

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-rh+t-rs485-en-v2-201027.docx

2/4

User manual
NLII-RH+T-RS485 | Combined RH/temperature sensor with RS485
Electronic board controls and terminals

6 5 4 3 2 1

Terminals

1. ~ + 2. ~ GND 3. OUT1 4. GND 5. OUT2 6. GND

supply AC or DC (+) plus pole
supply AC or DC (-) minus pole, GND RS485 bus ­ signal line B
GND RS485 bus ­ signal line A
GND

Jumpers JP6 ­ LED indication settings

Jumpers on the electronics board Mark Description JP6 - 1 Enabling LED indication and selecting the JP6 - 3 quantity for indication
(factory setting is RH)

Settings

Meaning
LED indication disabled
LED indication enabled, indication by RH

LED indication enabled, indication by T

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-rh+t-rs485-en-v2-201027.docx

3/4

User manual

Sensor assembly

NLII-RH+T-RS485 | Combined RH/temperature sensor with RS485
Box color
Front: White - RAL9016 Base: gray - RAL7035
Way to use
The product is intended for indoor use only. You can read the recommendations for sensor placement on our web pages.
End of product life
Discard the product in according to the electronic waste law and the EU directives.

Dimensions

The producer reserves the right of technical changes in order to product improvements its properties and functions without previous notice.

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-rh+t-rs485-en-v2-201027.docx

4/4

