241 ADL10-E(II) Installation and operation instruction V2.2
241
ADL10-E
ACREL Co,.Ltd

 Declare
  

The copyright is the property of Acrel. Any information in any paragraph or section cannot be extracted, copied or otherwise reproduced or propagated. Otherwise offenders shall take all consequences.
All rights are reserved.
 
Acrel reserves the right to modify the product specifications herein without notification. Please consult the local agent about the latest specifications before placing a purchase order.

 1  General.................................................................................................................................. 1 2  Functions.......................................................................................................................1 3  Technical parameter...................................................................................................... 1 4  Outline...........................................................................................................................2 5  Wiring and installing.................................................................................................3 6  Display description....................................................................................................... 3 7  Communication description..........................................................................................3

1  General
ADL10-E  LCD   IEC62053-21IEC62053-22  
ADL10-E single phase electric energy meter is a new generation energy meter designed by Acrel Co,.Ltd with many years' experience in designing electricity meters. Measurement, statistic, communication and LCD display functions are installed in the power meter. This power meter has advantages of high stability, low power consumption and data saving after blackout etc. All meters
meet the related technical requirements of electronic power meter in the IEC62053-21 IEC62053-22 standards.

2  Functions
 Function

 Function description

 Measurement of kWh
 Measurement of electrical parameters
LCD  LCD Display
 Communication

() Single-phase active kWh (positive and negative) UI PQSPFF  Voltage, Current, Active power, Reactive power, Apparent power, Power factor and Frequency 8  LCD  8 bits section LCD display RS485 MODBUS-RTU Communication interface: RS485, Communication protocol: MODBUS-RTU

(  means standard;  means optional)
3  Technical parameter

3.1  Electric performance 



Reference voltage 

Input voltage

Reference frequency





Power consumption 

Input current

Basic current

AC220V 50Hz <10VA 10A

 Function provide
 

C

 Measurement performance
 Communication

 Maximum current  Starting current  Consumption  Accuracy of measuring  Range of measuring  Interface  Connection mode  Protocol

60A
0.004Ib
<4VA () (Maximum current)
1 1 Class 000000.00~999999.99kWh
RS485(A+B-)
 Shielded twisted pair conductors MODBUS-RTUDL/T645-07

3.2  Mechanical performance

××

18mm×96 mm×70mm

Outline (Length × Width × Height)

3.3  Work environment





Range of temperature

Working temperature





Storing temperature

Relative humidity  Altitude

-25~55 -40~70 95%(No condensation) <2000m

4  Dimension drawings

 4.0N·m
5  Wiring and installing
5.1  Wiring diagram

5.2  Installing notices ADL10 

ADL10 single phase electric meter used the direct connecting method. Please pay attention to the direction of input and output while wiring and screw tightly (torque less than 12Nm) prevent the
meter from the abnormal work.
6  Display description
 The meter shows total energy first while turning on and then shows voltage, current and power, etc. in turn. The example shows as following:

 Current total energy 12.34kWh  Current voltage 220.0V

 Current current10.00A

 Current power 2.20kW

 Power factor 1.00

 Current even test, baud rate 9600

 Current address 001

 Current version V1.00

7  Communication description

7.1  Communication protocol  MODBUS-RTU  DL/T645-2007 


The meters adapt Modbus and DL/T645 protocol. Please refer to the relevant standards for

more information.

7.2 MODBUS  Communication address table

 





Address Variable

Length

R/W

0000H



4

R

0001H 0002H

Current total electricity 

...

Reserved

000AH 000BH 000CH

 Voltage  Current

2

R

2

R

000DH 

2

R

000EH

Active power 

2

R

000FH

Reactive power 

2

R

Apparent power

0010H



2

R

0011H

Power factor 

2

R

0012H

Frequency 

...

Reserved

0014H

0015H 



Address

1

R/W

0015H 



Communication baud rate

1

R/W

0016H ... 0047H
0048H
0049H ...

 Reserved
 Method of testing  Device ID

2

R/W

6

R/W

 Notes  unit: 0.01kWh
 unit0.1V  unit0.01A  unit 0.001kw  unit 0.001kvar  unit 0.001kVA  unit0.001
 unit 0.01Hz
1247
009600 014800 022400 03:1200
02: even 00: none

004BH

004CH 

4

004DH Forward reactive electric energy

004EH 

004FH Reversing reactive electric energy

4

0050H ... 0067H

 Reserved

0068H 0069H

 Forward active electric energy

4

006AH ... 0071H

 Reserved

0072H



4

0073H

Reversing active electric energy

R

 unit 0.01kWh

 unit

R

0.01kWh

R

0.01kWh

R

0.01kWh