Installation Guide for Danfoss models including: VACON NXP Air Cooled, VACON, NXP Air Cooled, Air Cooled, Cooled

VACON NX Heat Exchanger Application Man

432.8 KB

VACON NXP Air Cooled | Danfoss


File Info : application/pdf, 55 Pages, 452.69KB

PDF preview unavailable. Download the PDF instead.

AB361177576753en-000201
vacon® nx
ac drives
liquid-cooled drives
heat exchanger
application manual

vacon · 1

INDEX

Document code: DPD01890A Date edited: 5.8.2016

1. General .............................................................................................................................. 2

2. Control I/O ......................................................................................................................... 3

3. Parameter lists .................................................................................................................. 4
3.1 Monitoring values (Control keypad: menu M1).......................................................................... 4 3.2 Basic parameters (Control keypad: Menu M2  G2.1) ............................................................. 8 3.3 Input signals (Control keypad: Menu M2  G2.2) ..................................................................... 9 3.4 Output signals (Control keypad: Menu M2  G2.3)................................................................. 10 3.5 Drive control parameters (Control keypad: Menu M2  G2.4)............................................... 14 3.6 Prohibit frequency parameters (Control keypad: Menu M2  G2.5)...................................... 14 3.7 Motor control parameters (Control keypad: Menu M2  G2.6).............................................. 15 3.8 Protections (Control keypad: Menu M2  G2.7)...................................................................... 16 3.9 Autorestart parameters (Control keypad: Menu M2  G2.8) ................................................. 17 3.10 PID control parameters (Control keypad: Menu M2  G2.9).................................................. 17 3.11 Flow control parameters (Control keypad: Menu M2  G2.10).............................................. 18 3.12 Fieldbus parameters (Control Keypad: Menu M2 G2.11)..................................................... 19
3.13 Keypad control (Control keypad: Menu M3)............................................................................. 20
3.14 System menu (Control keypad: M6) ......................................................................................... 20
3.15 Expander boards (Control keypad: Menu M7) ......................................................................... 20

4. Description of parameters ............................................................................................... 21 4.1 Keypad control parameters...................................................................................................... 52

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com

2 · vacon

General

heat exchanger application
1. GENERAL
This application is aimed to be used in the Vacon liquid-cooled AC drive inside the Heat exchanger unit.
The idea with the application is to maintain a constant flow of coolant through the heat exchanger and through the Vacon liquid-cooled drive.
The user sets a certain speed for the pump of the heat exchanger unit that produces a sufficient flow through the Vacon liquid-cooled drives to keep them cooled. This speed is NOT regulated but fixed by a parameter set value.
The Vacon AC drive also handles the temperature of the water in the heat exchanger unit by regulating the valve that handles the coolant intake to the heat exchanger element (from the customer's system). This regulation is based on the temperature of the water in the pipes between the outlet of the heat exchanger pump and the inlet of the cooling element of the Vacon liquid-cooled drive.
The actual value of the temperature for the regulation comes from a sensor called FSA11. This is a type of flow switch that measures both the temperature of the coolant and the flow in the pipes. If there is not enough flow in the pipe the sensor gives a signal that tells the drive to stop due to insufficient flow.
Vacon NX AC drives can be connected to the Profibus DP using a fieldbus board. The AC drive can then be controlled, monitored and programmed from the Host system. Profibus fieldbus board (OPT-C5) is normally included in the delivery of Vacon NX liquid-cooled drive Heat Exchanger Solution. The Profibus fieldbus board must be installed in slot E on the control board of the AC drive. For more information on the Profibus fieldbus board, see Vacon OPTC3/C5 Profibus Option Board User Manual.
The standard delivery also includes I/O boards OPT-A1 (placed in slot A), OPT-A2 (placed in slot B) and OPT-B5 (placed in slot C or D). The application, however, offers you more signals than the standard set of I/O boards allows you to connect. If you wish to use one additional analogue input signal and/or two additional analogue output signals, we recommend you to order Vacon I/O board OPT-B4 and place it in the last free board slot (C or D).

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
1

Control I/O

vacon · 3

2. CONTROL I/O

Reference potentiometer, 1...10 k

OPT-A1
Terminal 1 +10Vref 2 AI1+

2-wire

transmitter

Actual

value

I

­

(0)4...20 mA +

3 AI14 AI2+ 5 AI2-
6 +24V 7 GND 8 DIN1

9 DIN2

Signal Reference output Analogue input, voltage range 0--10V DC
I/O Ground Analogue input, current range 0--20mA
Control voltage output I/O ground Start/Stop Control place A (PID controller) Flow fault

Description Voltage for potentiometer, etc. Pressure, outlet (pump)
Ground for reference and controls Temperature
Voltage for switches, etc. max 0.1 A Ground for reference and controls Contact closed = start
NO/NC programmable

10 DIN3 External fault (programmable)
11 CMA Common for DIN 1--DIN 3

Contact open = External fault Connect to GND or +24V

12 +24V Control voltage output 13 GND I/O ground 14 DIN4 Pump 1
15 DIN5 Pump 2
16 DIN6 Sequence, 2-pump system

Voltage for switches (see #6) Ground for reference and controls Forced or single run Combined with DIN1 Forced or single run Combined with DIN1 Combined with DIN1

READY RUN

17 CMB Common for DIN4--DIN6

Connect to GND or +24V

mA

18 AO1+ Output frequency 19 AO1- Analogue output

20 DO1 Digital output

Programmable Range 0--20 mA/RL, max. 500 Programmable

READY

Open collector, I50mA, U48 VDC

OPT-A2

21 RO1

Relay output 1 Programmable

22 RO1

RUN

23 RO1

24 RO2

Relay output 2 Programmable

220

25 RO2

FAULT

VAC

26 RO2

OPT-B5

22 RO1

Relay output 1

23 RO1

COOLING OK

25 RO2

Relay output 2

26 RO2

PUMP 1

28 RO3

Relay output 3

29 RO3

PUMP 2

Table 1. Heat exchanger application I/O configuration example (with 2-wire

transmitter).

Jum per block X 3 : CAN grounding

Jum per block X 4 : CAN termina tion

Connected to shield N ot connected to shield

Terminated

= Factory default

N ot terminated

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
2

4 · vacon

Parameter lists

3. PARAMETER LISTS
On the next pages you will find the lists of parameters within the respective parameter groups. The parameter descriptions are given on pages 21 to 52.

Column explanations:

Code

= Location indication on the keypad; Shows the operator the present param. number

Parameter = Name of parameter

Min

= Minimum value of parameter

Max

= Maximum value of parameter

Unit

= Unit of parameter value; Given if available

Default = Value preset by factory

Cust

= Customer's own setting

ID

= ID number of the parameter

= In parameter row: Use TTF method to program these parameters.

= On parameter code: Parameter value can only be changed after the FC has been

stopped.

3.1 Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and measurements. Monitoring values cannot be edited. See the product's user manual for more information.

Code Parameter V1.1 Output frequency V1.2 Frequency reference V1.3 Motor speed V1.4 Motor current V1.5 Motor torque V1.6 Motor power V1.7 Motor voltage V1.8 DC link voltage V1.9 Unit temperature V1.10 Analogue input 1 V1.11 Analogue input 2 V1.12 Analogue input 3 V1.13 Analog Output1 V1.14 DIN1, DIN2, DIN3 V1.15 DIN4, DIN5, DIN6 V1.16 RO1, RO2, RO3 V1.17 RO4, RO5, RO6 V1.18 Temp reference V1.19 Actual temperature V1.20 Temp error value V1.21 PID output V1.22 Inlet pressure
Table 2. Monitoring values

Unit ID Hz 1 Hz 25 rpm 2 A3 %4 %5 V6 V7 °C 8 V 13 mA 14
1543 26 15 16 1516 1574 °C 1500 °C 1501 °C 1502 % 23 bar 1511

Description Output frequency to motor Frequency reference to motor control Motor speed in rpm
Calculated shaft torque Motor shaft power
Heatsink temperature AI1 AI2 AI3
Digital input statuses Digital input statuses Relay output statuses Relay output statuses
In % of the max. output value PT11

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
3

Parameter lists

vacon · 5

3.1.1 FB Monitor

Code

Parameter

Unit ID

V1.23.1 Motor Current

A 45

V1.23.2 Fault History

37

V1.23.3 Status Word

43

V1.23.4 Status Word 2

1800

V1.23.5 Fault Word 1

1172

V1.23.6 Fault Word 2

1173

V1.23.7 Warning Word 1

1174

V1.23.8 Fault Word 10

1202

V1.23.9 Warning Word 10

1269

Table 3. Monitoring values (G1.24 FB Monitor)

Description Motor current with one decimal Last active fault code Application status word Application status word 2 General fault word 1 General fault word General warning word Heat exchanger specific faults Heat exchanger specific warnings

3.1.1.1 Status Word, ID43

Description

b0

b1

Ready

b2

Run

b3

Fault

b4

b5

b6

Run enable

b7

Warning

b8

b9

b10

RO4 status

b11

RO5 status

b12

Run request

b13

Motor regulator active

b14

b15

Cooling OK

Table 4. Status Word

Comment

3.1.1.2 Status Word 2, ID1800 Give this status word to Vacon personnel in case of problems with running the application.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
3

6 · vacon

3.1.1.3 Fault Word 1, ID1172

Description

b0

Over current

b1

Over voltage

b2

Under voltage

b3

Motor stalled

b4

b5

Motor underload

b6

Unit over temperature

b7

Motor over temperature

b8

Input phase

b9

b10

b11

Keypad or PC communication

b12

Fieldbus communication

b13

b14

Slot communication

b15

4 mA

Table 5. Fault Word 1

Comment F1 F2 F9 F15 F17
F16 F10
F52 F53
F54 F50

3.1.1.4 Fault Word 2, ID1173

Description

b0

Output phase

b6

External fault

b9

IGBT

Table 6. Fault Word 2

Comment F11 F51
(fault or warning) F41

3.1.1.5 Warning Word 1, ID1174

Description

b0

Motor stalled

b1

Motor over temperature

b2

Motor underload

b3

Input phase

b4

Output phase

b8

Unit temperature

b9

4 mA

b15

Keypad communication

Table 7. Warning Word 1

Comment F15 F16,
F29 (fault or warn) F17 F10 F11
F50 F52

Parameter lists

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
3

Parameter lists

3.1.1.6 Fault Word 10, ID1202

Description

b0

b1

b2

b3

b4

b5

Over temperature

b6

b7

Inlet pressure low

b8

Flow

Table 8. Fault Word 10

Comment
F85 (warning) F88 F87

3.1.1.7 Warning Word 10, ID1269

Description

b0

b1

b2

b3

Inlet pressure low

b4

Over temperature

b5

Low temperature

b6

Table 9. Warning Word 10

Comment
F82 F83 F86

vacon · 7

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
3

8 · vacon

Parameter lists

3.2 Basic parameters (Control keypad: Menu M2  G2.1)

Code P2.1.1

Parameter Min Frequency

Min

Max

Unit Default

0.00 Par. 2.1.2 Hz

25.00

P2.1.2 Max Frequency Par. 2.1.1 320.00

Hz

50.00

P2.1.3 Acceleration time 1 0.1

3000.0

s

1.0

P2.1.4 Deceleration time 1 0.1

3000.0

s

P2.1.5

Current limit

0

2 x IH

A

P2.1.6

Nominal voltage of the motor

180

690

V

P2.1.7

Nominal frequency of the motor

30.00

320.00

Hz

P2.1.8

Nominal speed of the motor

300

20 000 rpm

P2.1.9

Nominal current of the motor

0.4 x IH

2 x IH

A

P2.1.10

Motor cos

0.30

1.00

P2.1.11 Start function

0

1

1.0
IL 400V 50.00
1440
IH 0.85
0

P2.1.12 Stop function

0

3

0

P2.1.13 U/f optimization

0

1

P2.1.14 I/O reference P2.1.15 Preset speed1 P2.1.16 Automatic restart

0

1

0.00 Par. 2.1.2 Hz

0

1

P2.1.17 Parameter conceal

0

1

Table 10. Basic parameters G2.1

0
0 10.00
0
1

Cust

ID

Note

101

NOTE: If fmax > than the

102

motor synchronous speed, check suitability for motor

and drive system

NOTE: If PID-controller is

103

used, Acceleration time 2 (par. 2.4.3) is automatically

applied

NOTE: If PID-controller is

104

used, Deceleration time 2 (par. 2.4.4) is automatically

applied

107

110

111

Check the rating plate of the motor

The default applies for a 4-

112 pole motor and a nominal

size AC drive.

113

Check the rating plate of the motor.

120

Check the rating plate of the motor

505

0=Ramp 1=Flying start

0=Coasting

506

1=Ramp 2=Ramp+Run enable coast

3=Coast+Run enable ramp

109

0=Not used 1=Automatic torque boost

117

0=Keypad reference 1=Fieldbus reference

105

731

0=Not used 1=Automatic restart

115

0=All parameters visible 1=Basic group (G2.1) visible

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
3

Parameter lists

vacon · 9

3.3 Input signals (Control keypad: Menu M2  G2.2)

Code

Parameter

Min

P2.2.1

DIN2 input

0

P2.2.2

DIN3 function

0

P2.2.3

DIN6 Function

0

P2.2.4 AI1 signal range

0

P2.2.5

AI1 supervision

0

P2.2.6

AI1 custom minimum setting

0.00

P2.2.7

AI1 custom maximum setting

0.00

Max 1
10
1 3 1 P2.2.6 100.00

Unit Default Cust ID

Note

1

1590

0=Normally open 1=Normally closed

0=Motor pot. UP(cc)

1=Reverse

2=External fault CC

3=External fault OC

4=Fault reset

3

301

5=Run enable 6=Preset speed 1

7=DC brake cmnd

8=PID disable

9=PID disable, go to preset

speed

10=PID keypad ref 2

0

1572

0=Preset Speed 1 1=Fault Reset

0=Signal range 0-20mA

1

379

1=Signal range 4-20mA 2=0-10V

3=2-10V

0

1544

%

0.00

380

%

100.00

381

P2.2.8

AI1 inversion

0

1

0

P2.2.9

AI1 filter time

0.00

10.00

s

1.00

P2.2.10 AI2 signal range

0

1

1

P2.2.11 AI2 supervision

0

1

1

P2.2.12

AI2 custom minimum setting

0.00

P2.2.6

%

0.00

P2.2.13

AI2 custom maximum setting

0.00

100.00

%

100.00

P2.2.14

AI2 inversion

0

1

0

P2.2.15

AI2 filter time

0.00

10.00

s

1.00

P2.2.16 AI3 signal selection 0

59

P2.2.17 AI3 signal range

0

1

1

P2.2.18 AI3 supervision

0

1

0

P2.2.19

AI3 custom minimum setting

0.00

P2.2.18

%

0.00

P2.2.20

AI3 custom maximum setting

P2.2.17

100.00

%

100.00

P2.2.21

AI3 inversion

0

1

0

P2.2.22

AI3 filter time

0.00

10.00

s

1.00

P2.2.23

Keypad control reference

0

1

0

P2.2.24

Fieldbus control reference

0

1

1

387 378 390 1545 391

0=Not inverted 1=Inverted 0=No filtering 0=Signal range 0-20mA 1=Signal range 4-20mA

392
398 389 1558 1520 1546 1517

0=Not inverted 1=Inverted 0=No filtering TTF programming method 0=Signal range 0-20mA 1=Signal range 4-20mA

1518 1529 1526 121
122

0=Not inverted 1=Inverted
0=No filtering
Keypad freq ref selection: 0=Reference from Keypad 1=FB reference
Fieldbus frequency reference selection: 0=Reference from Keypad 1=FB reference

Table 11. Input signals, G2.2

*Remember to place jumpers of block X2 accordingly. See the product's user manual.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
3

10 · vacon

Parameter lists

3.4 Output signals (Control keypad: Menu M2  G2.3) 3.4.1 Analogue output 1

Code

Parameter

Min

Max

P2.3.1.1

Analogue output 1 function

0

13

P2.3.1.2

Analogue output 1 filter time

0.00

10.00

P2.3.1.3

Analogue output 1 inversion

0

1

P2.3.1.4

Analogue output 1 minimum

0

1

P2.3.1.5

Analogue output 1 scale

10

1000

Table 12. Analogue output 1 signals

Unit Default Cust ID

Note

0=Not used

1=Output freq. (0--fmax) 2=Freq. reference (0--fmax) 3=Motor speed (0--Motor

nominal speed)

4=Motor current (0--InMotor)

5=Motor torque (0--TnMotor)

6=Motor power (0--PnMotor)

13

307 7=Motor voltage (0-UnMotor)

8=DC-link volt (0--1000V)

9=PI controller temp ref

10=PI contr. act. temp.

11=PI contr. temperature

error value

12=PI controller output

13=Pressure from PT11,

pump inlet

s

1.00

308 0=No filtering

0

309

0=Not inverted 1=Inverted

1

310

0=0 mA 1=4 mA

%

100

311

3.4.2 Analogue output 2

Code

Parameter

Min

Max

P2.3.2.1

Analogue output 2 function

0

13

P2.3.2.2

Analogue output 2 filter time

0.00

P2.3.2.3

Analogue output 2 inversion

0

P2.3.2.4

Analogue output 2 minimum

0

P2.3.2.5

Analogue output 2 scale

10

10.00 1 1
1000

Table 13. Analogue output 2 signals

Unit Default Cust ID

Note

0=Not used

1=Output freq. (0--fmax) 2=Freq. reference (0--fmax) 3=Motor speed (0--Motor

nominal speed)

4=Motor current (0--InMotor)

5=Motor torque (0--TnMotor)

6=Motor power (0--PnMotor)

10

1530 7=Motor voltage (0-UnMotor)

8=DC-link volt (0--1000V)

9=PID controller ref. value

10=PI contr. act. temp

11=PI contr. temperature

error value

12=PI controller output

13=Pressure from PT11,

pump inlet

s

1.00

1531 0=No filtering

0

1532

0=Not inverted 1=Inverted

0

1533

0=0 mA 1=4 mA

%

100

1534

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
3

Parameter lists

vacon · 11

3.4.3 Analogue output 3

Code

Parameter

Min

Max

P2.3.3.1

Analogue output 3 function

0

13

P2.3.3.2

Analogue output 3 filter time

0.00

P2.3.3.3

Analogue output 3 inversion

0

P2.3.3.4

Analogue output 3 minimum

0

P2.3.3.5

Analogue output 3 scale

10

10.00 1 1
1000

Table 14. Analogue output 3 signals

3.4.4 Relay output 1

Code

Parameter

Min

Max

P2.3.4.1

Relay output 1 signal selection

P2.3.4.2

Relay output 1 function

0

18

P2.3.4.3

Relay output 1 inversion

0

1

Table 15. Relay output 1 signals

Unit Default 4

s

1.00

0

0

%

100

Unit Default B.1

2

0

Cust

ID
1535
1536 1537 1538 1539

Note 0=Not used 1=Output freq. (0--fmax) 2=Freq. reference (0--fmax) 3=Motor speed (0--Motor
nominal speed) 4=Motor current (0--InMotor) 5=Motor torque (0--TnMotor) 6=Motor power (0--PnMotor) 7=Motor voltage (0-UnMotor) 8=DC-link volt (0--1000V) 9=PID controller ref. value 10=PI contr. act. temp 11=PI contr. temperature
error value 12=PID controller output 13=Pressure from PT11,
pump inlet
0=No filtering
0=Not inverted 1=Inverted 0=0 mA 1=4 mA

Cust

ID 1549
313
1540

Note
0=Not used 1=Ready 2=Run 3=Fault 4=Fault inverted 5=FC overheat warning 6=Ext. fault or warning 7=Ref. fault or warning 8=Warning 9=Reversed 10=Preset speed 1 11=At speed 12=Mot. regulator active 13=OP freq. limit superv.1 14=Control place: IO 15=Thermistor fault/warn. 16=Actual value supervision 17=Cooling OK 18=Alarm latched 0=Not inverted 1=Inverted

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
3

12 · vacon

Parameter lists

3.4.5 Relay output 2

Code

Parameter

Min

Max

P2.3.5.1

Relay output 2 signal selection

P2.3.5.2

Relay output 2 function

0

18

P2.3.5.3

Relay output 2 inversion

0

1

Table 16. Relay output 2 signals

3.4.6 Relay output 3

Code

Parameter

Min

Max

P2.3.6.1

Relay output 3 signal selection

P2.3.6.2

Relay output 3 function

0

3

P2.3.6.3

Relay output 3 inversion

0

1

Table 17. Relay output 3 signals

3.4.7 Relay output 4

Code

Parameter

Min

Max

P2.3.7.1

Relay output 4 signal selection

P2.3.7.2

Relay output 4 function

0

3

P2.3.7.3

Relay output 4 inversion

0

1

Table 18. Relay output 4 signals

Unit Default Cust ID

Note

B.2

1550

0=Not used

1=Ready

2=Run

3=Fault

4=Fault inverted

5=FC overheat warning

6=Ext. fault or warning

7=Ref. fault or warning

8=Warning

3

1513 9=Reversed

10=Preset speed 1

11=At speed

12=Mot. regulator active

13=OP freq. limit superv.1

14=Control place: IO

15=Thermistor fault/warn.

16=Actual value supervision

17=Cooling OK

18=Alarm latched

0

1541

0=Not inverted 1=Inverted

Unit Default Cust ID

Note

D.1

1551

0=Not used

1

1515

1=Cooling OK 2=Pump 1

3=Pump 2

0

1542

0=Not inverted 1=Inverted

Unit Default Cust ID

Note

D.2

1552

0=Not used

2

1553

1=Cooling OK 2=Pump 1

3=Pump 2

0

1554

0=Not inverted 1=Inverted

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
3

Parameter lists

vacon · 13

3.4.8 Relay output 5

Code

Parameter

Min

Max

P2.3.8.1

Relay output 5 signal selection

P2.3.8.2

Relay output 5 function

0

3

P2.3.8.3

Relay output 5 inversion

0

1

Table 19. Relay output 5 signals

Unit Default Cust ID

Note

D.3

1555

0=Not used

3

1556

1=Cooling OK 2=Pump 1

3=Pump 2

0

1557

0=Not inverted 1=Inverted

3.4.9 Relay output 6

Code

Parameter

Min

Max

P2.3.9.1

Relay output 6 signal selection

P2.3.9.2

Relay output 6 function

0

18

P2.3.9.3

Relay output 6 inversion

0

1

Table 20. Relay output 6 signals

Unit Default Cust ID

Note

A.1

1573

0=Not used

1=Ready

2=Run

3=Fault

4=Fault inverted

5=FC overheat warning

6=Ext. fault or warning

7=Ref. fault or warning

8=Warning

3

1567 9=Reversed

10=Preset speed 1

11=At speed

12=Mot. regulator active

13=OP freq. limit superv.1

14=Control place: IO

15=Thermistor fault/warn.

16=Actual value supervision

17=Cooling OK

18=Alarm latched

0

1568

0=Not inverted 1=Inverted

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
3

14 · vacon

Parameter lists

3.5 Drive control parameters (Control keypad: Menu M2  G2.4)

Code

Parameter

Min

P2.4.1

Ramp 1 shape

0.0

Max

Unit Default Cust

10.0

s

0.0

P2.4.2

Brake chopper

0

3

0

P2.4.3 DC braking current 0.4 x IH

2 x IH

A

IH

P2.4.4

DC braking time at stop

0.00 600.00

s

0.00

Frequency to start

P2.4.5 DC braking during 0.10

10.00

Hz

1.50

ramp stop

P2.4.6

DC braking time at start

0.00 600.00

s

0.00

P2.4.7

Flux brake

0

1

0

P2.4.8 Flux braking current 0.4 x IH 2 x IH

A

IH

Table 21. Drive control parameters, G2.4

ID

Note

500

0=Linear >0=S-curve ramp time

0=Disabled

1=Used when running

504 2=External brake chopper

3=Used when stopped/

running

507

508 0=DC brake is off at stop

515

516 0=DC brake is off at start

520

0=Off 1=On

519

3.6 Prohibit frequency parameters (Control keypad: Menu M2  G2.5)

Code

Parameter

Min

Max

Unit

P2.5.1

Prohibit frequency range 1 low limit

0.00

Par. 2.5.2

Hz

P2.5.2

Prohibit frequency range 1 high limit

0.00

Par. 2.1.2

Hz

P2.5.3

Prohibit acc./dec. ramp

0.1

10.0 Times

P2.5.4

Output frequency limit 1 supervision

0

2

P2.5.5

Output frequency limit 1;
Supervised value

0.00 Par. 2.1.2 Hz

Table 22. Prohibit frequency parameters, G2.5

Default 0.00 0.00 1.0 0
0.00

Cust

ID

Note

509 0=Not used

510 0=Not used

518
0=No limit 315 1=Low limit supervision
2=High limit supervision

316

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
3

Parameter lists

vacon · 15

3.7 Motor control parameters (Control keypad: Menu M2  G2.6)

Code

Parameter

Min

Max

Unit Default Cust

P2.6.1 Motor control mode

0

1

0

P2.6.2

U/f ratio selection

0

3

0

P2.6.3 Field weakening point 8.00 320.00

Hz

50.00

P2.6.4

Voltage at field weakening point

10.00 200.00

%

100.00

P2.6.5

U/f curve midpoint frequency

0.00

par. P2.6.4

Hz

50.00

P2.6.6

U/f curve midpoint voltage

0.00

100.00

%

100.00

P2.6.7

Output voltage at zero frequency

0.00

40.00

%

Varies

P2.6.8 Switching frequency 1.0

Varies kHz Varies

P2.6.9 Overvoltage controller 0

1

1

P2.6.10

Undervoltage controller

0

1

1

Table 23. Motor control parameters, G2.6

ID

Note

600

0=Frequency control 1=Speed control

0=Linear

108

1=Squared 2=Programmable

3=Linear with flux optim.

602

603 n% x Unmot

604

n% x Unmot 605 Parameter max. value =
par. 2.6.5

606 n% x Unmot

601

See Table 31 for exact values

607

0=Not used 1=Used (no ramping)

608

0=Not used 1=Used

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
3

16 · vacon

Parameter lists

3.8 Protections (Control keypad: Menu M2  G2.7)

Code

Parameter

Min

Max

Unit Default

P2.7.1

Response to 4mA reference fault

0

3

1

P2.7.2

Response to external fault

0

3

P2.7.3

Input phase supervision

0

3

P2.7.4

Response to undervoltage fault

1

3

P2.7.5

Output phase supervision

0

3

P2.7.6

Earth fault protection

0

3

P2.7.7

Thermal protection of the motor

0

3

P2.7.8

Motor ambient temperature factor

­100.0

100.0

%

P2.7.9

Motor cooling factor at zero speed

0.0

150.0

%

P2.7.10

Motor thermal time constant

1

200

min

P2.7.11 Motor duty cycle

0

100

%

P2.7.12 Stall protection

0

3

P2.7.13 P2.7.14

Stall current Stall time limit

0.1

InMotor x 2

A

1.00

120.00

s

P2.7.15 Stall frequency limit 1.0 Par. 2.1.2 Hz

P2.7.16

Underload protection

0

3

P2.7.17

Field weakening area load

10

150

%

P2.7.18 Zero frequency load 5.0

150.0

%

P2.7.19

Underload protection time limit

2

600

s

P2.7.20

Response to thermistor fault

0

3

P2.7.21

Response to fieldbus fault

0

3

P2.7.22 Resp. to slot fault

0

3

1
0
2
2
2
2
0.0
40.0
Varies 100 1 IL 15.00 25.0 0
50 10.0 20
0
2 2

Actual value

P2.7.23

supervision

0

4

0

function

P2.7.24

Actual value supervision limit

0

P2.7.25

Actual value supervision delay

0

Table 24. Protections, G2.7

100.0

%

10.0

3600

s

5

Cust

ID

Note

0=No response

700

1=Warning 2=Fault,stop acc. to 2.1.12

3=Fault,stop by coasting

701 See par. ID700

730 See par. ID700
1=Warning 727 2=Fault,stop acc. to 2.1.12
3=Fault,stop by coasting
702 See par. ID700

703 See par. ID700

704 See par. ID700

705

706

707
708 709 See par. ID700 710 711 712
713 See par. ID700

714 715 716

732 See par. ID700

733 See par. ID700
734 See par. ID700 0=Not used 1=If below limit: Warning
735 2=If above limit: Warning 3=If below limit: Fault 4=If above limit: Fault
736

737

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
3

Parameter lists

vacon · 17

3.9 Autorestart parameters (Control keypad: Menu M2  G2.8)

Code P2.8.1 P2.8.2

Parameter Wait time Trial time

Min

Max

Unit Default Cust

0.10

10.00

s

0.50

0.00

60.00

s

30.00

P2.8.3

Start function

0

2

0

Table 25. Autorestart parameters, G2.8

ID

Note

717

718

0=Ramp

719 1=Flying start

2=According to par. 2.1.11

3.10 PID control parameters (Control keypad: Menu M2  G2.9)

Code

Parameter

Min

Max

P2.9.1

PID activation

0

1

P2.9.2

PID reference

0

2

P2.9.3

Actual value 1 selection

0

2

P2.9.4 P2.9.5 P2.9.6 P2.9.7 P2.9.8

PID controller gain PID controller Itime PID controller Dtime Actual value 1 minimum scale Actual value 1 maximum scale

0.0 0.00 0.00 ­1000.0 ­1000.0

1000.0 320.00 10.00 1000.0 1000.0

P2.9.9 Error value inversion 0

1

P2.9.10

Dead band

0

P2.9.11 Dead band delay

0

10.00 100.00

Table 26. PID control parameters, G2.9

Unit Default Cust ID

Note

1

163

0=Not used 1=PID control activated

0=PID ref from Keypad

control page, par. 3.4

0

332

1=PID ref from Keypad control page, par 3.5

2=PID ref from fieldbus

(ProcessDataIN 1)

0=AI1 signal (c-board)

1

334 1=AI2 signal (c-board)

2=Fieldbus ProcessDataIN2

%

100.0

118 0=No part P used

s

5.00

119 320.00=No part I used

s

0.00

132 0=No part D used

%

0.0

336 0=No minimum scaling

%

100.0

0

°C

0.0

s

10.0

337 100=No maximum scaling

340
1575 1576

0=No inversion 1=Inversion 0=Not Used

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
3

18 · vacon

Parameter lists

3.11 Flow control parameters (Control keypad: Menu M2  G2.10)

Code

Parameter

Min

Max Unit

P2.10.1

Constant speed

Par. 2.1.1 Par. 2.1.1 Hz

P2.10.2

Coolant inlet pressure, minimum

0.00

Par. 2.10.3

bar

P2.10.3

Coolant inlet pressure, maximum

Par. 2.10.2

30.00 bar

P2.10.4

Coolant inlet pressure, alarm limit

0.00

100.00 bar

P2.10.5

Coolant inlet pressure, fault limit

0.00

100.00 bar

P2.10.6

Coolant inlet pressure, supervision

0

1

P2.10.7

Temperature sensor, minimum value

0.00 Par. 2.10.7 °C

P2.10.8

Temperature sensor, maximum value

Par. 2.10.6

100.00 °C

Coolant outlet

P2.10.9 temperature alarm,

0.00

100.00 °C

lower limit

Coolant outlet

P2.10.10 temperature alarm,

0.00

100.00 °C

higher limit

Coolant outlet

P2.10.11 temperature fault,

0.00

100.00 °C

higher limit

P2.10.12 Autochange interval

0

169

h

P2.10.13

Delayed fault

1

30

s

Table 27. Flow control parameters, G2.10

Default 50.00 0.00 10.00 1.00 2.00 0 0.00 100.00
22.00
30.00
40.00
169 2

Cust

ID 1514
1504

Note

1505

1570

1571

1569

0=Off (No sensor) 1=On (Sensor installed)

1509

1510

1591

1594

1595

1599 1503

0=Test mode 169=Single motor, no change

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
3

Parameter lists

vacon · 19

3.12 Fieldbus parameters (Control Keypad: Menu M2 G2.11)

Code

Parameter

Min

P2.11.1

Fieldbus data out 1 selection

0

Max 10000

P2.11.2

Fieldbus data out 2 selection

0

10000

P2.11.3

Fieldbus data out 3 selection

0

10000

P2.11.4

Fieldbus data out 4 selection

0

10000

P2.11.5

Fieldbus data out 5 selection

0

P2.11.6

Fieldbus data out 6 selection

0

P2.11.7

Fieldbus data out 7 selection

0

P2.11.8

Fieldbus data out 8 selection

0

10000 10000 10000 10000

Table 28. Fieldbus parameters, G2.11

Unit Default Cust 1501 2 45 1511 1 4 5 37

ID

Note

852

Choose monitoring data with parameter ID

853

Choose monitoring data with parameter ID

854

Choose monitoring data with parameter ID

855

Choose monitoring data with parameter ID

856

Choose monitoring data with parameter ID

857

Choose monitoring data with parameter ID

858

Choose monitoring data with parameter ID

859

Choose controlled data with parameter ID

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
3

20 · vacon

Parameter lists

3.13 Keypad control (Control keypad: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed below. See the Keypad control menu in the product's User Manual.

Code

Parameter

Min

Max

Unit

P3.1

Control place

1

3

R3.2 Keypad reference Par. 2.1.1 Par. 2.1.2 Hz

P3.3

Direction (on keypad)

0

1

R3.6

Stop button

0

1

R3.4

PID reference Par. 2.10.6 Par. 2.10.7 °C

R3.5 PID reference 2 Par. 2.10.6 Par. 2.10.7 °C

Table 29. Keypad control parameters, M3

Default 1
0
1 25.00 0.00

Cust

ID

Note

1=I/O terminal

125 2=Keypad

3=Fieldbus

123

0=Forward 1=Reverse

0=Limited function of

114

Stop button 1=Stop button always

enabled

3.14 System menu (Control keypad: M6)
For parameters and functions related to the general use of the AC drive, such as application and language selection, customised parameter sets or information about the hardware and software, see the product's User manual.

3.15 Expander boards (Control keypad: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and boardrelated information. For more information, see the product's User Manual.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
3

Description of parameters

vacon · 21

4. DESCRIPTION OF PARAMETERS
On the following pages you will find the parameter descriptions arranged according to the individual ID number of the parameter. A shaded parameter ID number (e.g. 418 Motor potentiometer UP) indicates that the TTF programming method is applied to this parameter (see All-in-One Application Manual). Some parameter names are followed by a number code indicating the "All in One" applications in which the parameter is included. If no code is shown the parameter is available in all applications. See below. The parameter numbers under which the parameter appears in different applications are also given.

101

Minimum frequency

102

Maximum frequency

(2.1.1) (2.1.2)

Defines the frequency limits of the AC drive. The maximum value for these parameters is 320 Hz. The software will automatically check the values of parameters ID105, ID106 and ID728.

103

Acceleration time 1

104

Deceleration time 1

(2.1.3) (2.1.4)

These limits correspond to the time required for the output frequency to accelerate from the zero frequency to the set maximum frequency (par. ID102).

105

Preset speed 1

(2.1.15)

Parameter values are automatically limited between the minimum and maximum frequencies (par. ID101, ID102).

107

Current limit

(2.1.5)

This parameter determines the maximum motor current from the AC drive. The parameter value range differs from size to size. When this parameter is changed the stall current limit (ID710) is internally calculated to 90% of current limit.

108

U/f ratio selection

(2.6.2)

Linear: 0
Squared: 1

The voltage of the motor changes linearly with the frequency in the constant flux area from 0 Hz to the field weakening point where the nominal voltage is supplied to the motor. Linear U/f ration should be used in constant torque applications. Use this default setting if there is no special need for another setting. The voltage of the motor changes following a squared curve form with the frequency in the area from 0 Hz to the field weakening point where the nominal voltage is also supplied to the motor. The motor runs undermagnetised below the field weakening point and produces less torque and electromechanical noise. Squared U/f ratio can be used in applications where torque demand of the load is proportional to the square of the speed, e.g. in centrifugal fans and pumps.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

22 · vacon

U[V]

Un

ID603

Default: Nominal voltage of the motor

Description of parameters
Field weakening point

Linear

Squared

Default: Nominal

frequency of the

motor

f[Hz]

NX12K07
Figure 1. Linear and squared change of motor voltage

Programmable U/f curve:

2

The U/f curve can be programmed with three different points. Programmable

U/f curve can be used if the other settings do not satisfy the needs of the

application.

Un ID603

U[V] Default: Nominal voltage of the motor

Field weakening point

ID605 (Def. 10%)
ID606 (Def. 1.3%)

Default: Nominal frequency of the motor
f[Hz]

ID604 (Def. 5 Hz)

ID602

NX12K08

Figure 2. Programmable U/f curve

Linear with flux optimisation:

3

The AC drive starts to search for the minimum motor current in order to save

energy, lower the disturbance level and the noise. This function can be used

in applications with constant motor load, such as fans, pumps etc.

109

U/f optimisation

(2.1.13)

Automatic torque boost

The voltage to the motor changes automatically which makes the motor produce sufficient torque to start and run at low frequencies. The voltage increase depends on the motor type and power. Automatic torque boost can be used in applications where starting torque due to starting friction is high, e.g. in conveyors.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 23

EXAMPLE:

What changes are required to start with load from 0 Hz?



First set the motor nominal values (Parameter group 2.1).

Option 1: Activate the Automatic torque boost.

Option 2: Programmable U/f curve To get torque you need to set the zero point voltage and midpoint voltage/frequency (in parameter group 2.6) so that the motor takes enough current at low frequencies. First set par. ID108 to Programmable U/f curve (value 2). Increase zero point voltage (ID606) to get enough current at zero speed. Set then the midpoint voltage (ID605) to 1.4142*ID606 and midpoint frequency (ID604) to value ID606/100%*ID111.

NOTE!

In high torque ­ low speed applications ­ it is likely that the motor will overheat. If the motor has to run a prolonged time under these conditions, special attention must be paid to cooling the motor. Use external cooling for the motor if the temperature tends to rise too high.

110

Nominal voltage of motor (2.1.6)

Find this value Un on the rating plate of the motor. This parameter sets the voltage at the field weakening point (ID603) to 100% * UnMotor. Note also used connection Delta/Star.

111

Nominal frequency of motor (2.1.7)

Find this value fn on the rating plate of the motor. This parameter sets the field weakening point (ID602) to the same value.

112

Nominal speed of motor

(2.1.8)

Find this value nn on the rating plate of the motor.

113

Nominal current of motor (2.1.9)

Find this value In on the rating plate of the motor.

115

Parameter conceal

With this parameter you can hide all other parameter groups except the basic parameter group (P2.1).

Note! The factory default of this parameter is 1, i.e. all parameter groups except P2.1 are hidden. The other parameter groups cannot be browsed or edited before the value of this parameter is set to 0.

0 = Disabled (all parameter groups can be browsed with the keypad) 1 = Enabled (only the basic parameters, P2.1, can be browsed with the keypad)

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

24 · vacon

Description of parameters

117

I/O frequency reference selection

(2.1.14)

Defines which frequency reference source is selected when controlled from the I/O control place.

0 = Keypad reference (Menu M3) 1 = Fieldbus reference

118

PID controller gain

(2.9.4)

This parameter defines the gain of the PID controller. If the value of the parameter is set to 100% a change of 10% in the error value causes the controller output to change by 10%. If the parameter value is set to 0 the PID controller operates as ID-controller. See examples at parameter ID132 below.

119

PID controller I-time

(2.9.5)

The parameter ID119 defines the integration time of the PID controller. If this parameter is set to 1.00 second a change of 10% in the error value causes the controller output to change by 10.00%/s. If the parameter value is set to 0.00 s the PID controller will operate as PD controller. See examples at parameter ID132 below.

120

Motor cos phi

(2.1.10)

Find this value "cos phi" on the rating plate of the motor.

121

Keypad frequency reference selection

(2.2.22)

Defines which frequency reference source is selected when controlled from the keypad.

0 Reference from keypad (Freq Ref) 1 Reference from fieldbus

122

Fieldbus frequency reference selection

(2.2.23)

Defines which frequency reference source is selected when controlled from the fieldbus.

0 Reference from keypad (Freq Ref) 1 Reference from fieldbus

132

PID controller D-time

(2.9.6)

The parameter ID132 defines the derivation time of the PID controller. If this parameter is set to 1.00 second a change of 10% in the error value during 1.00 s causes the controller output to change by 10.00%. If the parameter value is set to 0.00 s the PID controller will operate as PI controller. See examples below.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 25

Example 1: In order to reduce the error value to zero, with the given values, the AC drive output behaves as follows:

Given values: Par. 2.1.12, P = 0% Par. 2.1.13, I-time = 1.00 s Par. 2.1.14, D-time = 0.00 s Error value (setpoint ­ process value) = 10.00%

Min freq. = 0 Hz Max freq. = 50 Hz

In this example, the PID controller operates practically as I-controller only. According to the given value of parameter 2.1.13 (I-time), the PID output increases by 5 Hz (10% of the difference between the maximum and minimum frequency) every second until the error value is 0.

Hz
PID output Error value

10% I-Part=5 Hz/s

10% I-Part=5 Hz/s

10%

I-Part=5 Hz/s

10%

I-Part=5 Hz/s

Error=10%

I-Part=5 Hz/s

1s

t

NX12k70

Figure 3. PID controller function as I-controller.

Example 2: Given values:

Par. 2.1.12, P = 100% Par. 2.1.13, I-time = 1.00 s Par. 2.1.14, D-time = 1.00 s Error value (setpoint ­ process value) = ±10%

Min freq. = 0 Hz Max freq. = 50 Hz

As the power is switched on, the system detects the difference between the setpoint and the actual process value and starts to either raise or decrease (in case the error value is negative) the PID output according to the I-time. Once the difference between the setpoint and the process value has been reduced to 0 the output is reduced by the amount corresponding to the value of parameter 2.1.13. In case the error value is negative, the AC drive reacts reducing the output correspondingly. See Figure 4.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

26 · vacon
Hz

Description of parameters

D-part

D-part

D-part

PID output Error value

P-part=5 Hz

Error=10%

Error= -10% P-part= -5 Hz

t

NX12k69
Figure 4. PID output curve with the values of Example 2.

Example 3: Given values:

Par. 2.1.12, P = 100% Par. 2.1.13, I-time = 0.00 s Par. 2.1.14, D-time = 1.00 s Error value (setpoint ­ process value) = ±10%/s

Min freq. = 0 Hz Max freq. = 50 Hz

As the error value increases, also the PID output increases according to the set values (D-time = 1.00s)

Hz PID output Error value

D-part=10%=5,00 Hz

D-part= -10%= -5,00 Hz

P-part=100% *PID error = 5,00Hz/s 10%

1,00 s

NX12k72

t

Figure 5. PID output with the values of Example 3.

163

PID activation

(2.9.1)

Activate the PID control by setting value 1 for this parameter.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 27

301

DIN3 function

(2.2.2)

This parameter has 10 selections. The default value is 3.

0 Motor potentiometer UP Contact closed: Reference increases until the contact is opened.
1 Enable PID reference 2 Contact open: PID controller reference selected with parameter R3.4. Contact closed: PID controller keypad reference 2 selected with parameter R3.5.
2 External fault Contact closed: Fault is displayed and motor stopped when the input is active
3 External fault Contact open: Fault is displayed and motor stopped when the input is not active
4 Fault reset Contact closed: All faults reset
5 Run enable Contact open: Start of motor disabled Contact closed: Start of motor enabled
6 Preset speed 7 DC-braking command
Contact closed: In Stop mode, the DC braking operates until the contact is opened

Output frequency

ID515

t

t

DIN3

DIN3

RUN STOP

NX12K83

RUN STOP

NX12K83

a) DIN3 as DC-brake command input and stop-mode = Ramp

b) DIN3 as DC-brake command input and stop-mode = Coasting

Figure 6. DIN3 as DC-brake command input: a) Stop mode = Ramp, b) Stop mode = coasting

8 PID disable 9 PID disabled; go to Preset speed 10 PID keypad reference 2

307

Analogue output 1 function

(2.3.1.1)

This parameter selects the desired function for the analogue output 1 signal. 0 Not used 1 Output frequency (0--fmax) 2 Frequency reference (0--fmax) 3 Motor speed (0--Motor nominal speed) 4 Motor current (0--Motor nominal current) 5 Motor torque (0--Motor nominal torque) 6 Motor power (0--Motor nominal power) 7 Motor voltage (0--Motor nominal voltage) 8 DC-link voltage (0--Motor nominal voltage)

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

28 · vacon

Description of parameters

9 PI controller temperature reference 10 PI controller actual temperature (from FSA11) 11 PI controller error value of the temperature 12 PI controller output 13 Pressure from PT11, pump inlet

308

Analogue output 1 filter time

(2.3.1.2)

Defines the filtering time of the analogue output signal. Setting this parameter value 0 will deactivate filtering.

309

Analogue output 1 inversion

Inverts the analogue output signal:

(2.3.1.3)

Maximum output signal = Minimum set value Minimum output signal = Maximum set value

See parameter ID311 below.

310

Analogue output 1 minimum

(2.3.1.4)

Defines the signal minimum to either 0 mA or 4 mA (living zero). Note the difference in analogue output scaling in parameter ID311 (Figure 7).

0 Set minimum value to 0 mA 1 Set minimum value to 4 mA

311

Analogue output 1 scale

Scaling factor for analogue output.

(2.3.1.5)

Analogue output current
20 mA

ID311 = 200%

ID311 = 100%

12 mA 10 mA

ID311 = 50%

ID310 = 1 4 mA

Max. value of signal

ID310 = 0

selected by ID307

0 mA

0

0.5

1.0

NX12K18

Figure 7. Analogue output scaling

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 29

313

Relay output 1 function

(2.3.4.2)

Setting value 0 = Not used

Signal content Out of operation

1 = Ready

The AC drive is ready to operate

2 = Run

The AC drive operates (motor is running)

3 = Fault

A fault trip has occurred

4 = Fault inverted

A fault trip has not occurred

5 = FC overheat warning

The heat-sink temperature exceeds +70°C

6 = External fault or warning 7 = Reference fault or warning 8 = Warning

Fault or warning depending on par. ID701
Fault or warning depending on par. ID700
- if analogue reference is 4--20 mA and signal is <4mA
Always if warning exists

9 = Reversed

The reverse command has been selected

10 = Preset speed 1

The preset speed has been selected with digital input

11 = At speed

The output frequency has reached the set reference

12 = Motor regulator activated
13 = Output frequency limit supervision 14 = Control from I/O terminals 15 = Thermistor fault or warning (Appl.2)
16 = Actual value supervision 17 = Cooling OK

Overvoltage or overcurrent regulator was activated
The output frequency goes outside the set supervision low limit/high limit (see parameter ID's 315 and 316 below) I/O control mode selected (in menu M3) The thermistor input of option board indicates overtemperature. Fault or warning depending on par. ID732. Actual value supervision is active

Table 30. Output signals via relay outputs RO1 and RO2.

315

Output frequency limit supervision function

0 No supervision 1 Low limit supervision 2 High limit supervision

(2.5.4)

If the output frequency goes under/over the set limit (ID316) this function generates a warning message via the relay output RO1 or RO2 depending on the settings of parameters ID313 and ID1513.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

30 · vacon

Description of parameters

316

Output frequency limit supervision value

(2.5.5)

Selects the frequency value supervised by parameter ID315. See Figure 8.

f[Hz] ID316

ID315 = 2

t

Example: 21 RO1 22 RO1 23 RO1

21 RO1 22 RO1 23 RO1

21 RO1 22 RO1 23 RO1

Figure 8. Output frequency supervision

NX12K19

332

PID controller reference signal

(2.9.2)

Defines which frequency reference place is selected for the PID controller.

0 Reference from keypad (PID reference 1, Menu M3, par. R3.4) 1 Reference from keypad (PID reference 2, Menu M3, par. R3.5) 2 Fieldbus reference (FBProcessDataIN1)

334

Actual value selection

(2.9.3)

0 AI1 (control board) 1 AI2 (control board) 2 Fieldbus (FBProcessDataIN2)

336

Actual value 1 minimum scale

(2.9.7)

Sets the minimum scaling point for Actual value.

Scaled input signal [%]

See

100

ID336 = 30% ID337 = 80%

Figure 9.

NX12 k34.fh1 1

337

Actual value 1 maximum scale

(2.9.8)

Sets the maximum scaling point for Actual value. See

30 0

0

3,0

0

6,0

4

8,8

Figure 9.

Analogue 80 100 input [%] 8,0 10,0 V 16,0 20,0 mA 16,8 20,0 mA

Figure 9. Example of actual value signal scaling
Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 31

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

32 · vacon

Description of parameters

340

PID error value inversion

(2.9.9)

This parameter allows you to invert the error value of the PID controller (and thus the operation of the PID controller).

0 No inversion 1 Inverted

378

AI1 signal filter time

(2.2.8)

When this parameter is given a value greater

than 0 the function that filters out disturbances

%

from the incoming analogue signal is activated.

100%
Long filtering time makes the regulation
response slower. See Figure 10.

63%

Unfiltered signal
Filtered signal

ID378
Figure 10. AI1 signal filtering

t [s]
NX12K74

379

AI1 signal range

0 Signal range 0...20 mA 1 Signal range 4...20 mA 2 Signal range 0...10 V 3 Signal range 2...10 V

(2.2.3)

380

AI1 custom setting minimum

381

AI1 custom setting maximum

(2.2.5) (2.2.6)

These parameters set the analogue input signal for any input signal span between 0.00...100.00%. However, the max value of par. ID380 cannot be greater than the value set for parameter ID381, and the min value of par. ID381 cannot be smaller than the max value of par. ID380.
Note: Parameter ID379 AI1 signal range is inactivated if ID380  0% or ID381  100%.
See also Figure 11.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

387

AI1 signal inversion

(2.2.7)

If this parameter = 0, no inversion of analogue signal takes place.

AO signal

vacon · 33

Max ID379 = 0 AI1 = 0--20mA

Min

0

ID380

ID381

AI1
100%
NX12K71

Figure 11. AI1 no signal inversion

If this parameter = 1 inversion of analogue signal takes place.

AO signal

389

AI2 signal filter time

See parameter ID378.

390

AI2 signal range

0 Signal range 0...20 mA 1 Signal range 4...20 mA

Max

ID320 = 0 AI1 = 0--20mA

Min

AI1

0

ID380

ID381

100%
NX12K73

Figure 12. AI1 signal inversion

(2.2.14)

(2.2.9)

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

34 · vacon

Description of parameters

391

AI2 custom setting minimum

392

AI2 custom setting maximum

See parameters ID380 and ID381.

(2.2.11) (2.2.12)

398

AI2 signal inversion

See parameter ID387.

(2.2.13)

500

Acceleration/Deceleration ramp 1 shape (2.4.1)

The start and end of acceleration and deceleration ramps can be smoothed with these parameters. Setting value 0 gives a linear ramp shape which causes acceleration and deceleration to act immediately to the changes in the reference signal. Setting a value 0.1...10 seconds for this parameter produces an S-shaped acceleration/ deceleration. The acceleration time is determined with parameters ID103/ID104.

[Hz]

ID103, ID104

ID500

ID500

[t]

NX12K20

Figure 13. Acceleration/Deceleration (S-shaped)

504

Brake chopper

(2.4.2)

0 = No brake chopper used 1 = Brake chopper in use and tested when running. Can be tested also in READY state 2 = External brake chopper (no testing) 3 = Used and tested in READY state and when running

When the AC drive is decelerating the motor, the inertia of the motor and the load are fed into an external brake resistor. This enables the AC drive to decelerate the load with a torque equal to that of acceleration (provided that the correct brake resistor has been selected). See separate Brake resistor installation manual.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 35

505

Start function

(2.1.11)

Ramp: 0

The AC drive starts from 0 Hz and accelerates to the set reference frequency within the set acceleration time. (Load inertia or starting friction may cause prolonged acceleration times).

Flying start:

1

The AC drive is able to start into a running motor by applying a small torque to

motor and searching for the frequency corresponding to the speed the motor

is running at. Searching starts from the maximum frequency towards the

actual frequency until the correct value is detected. Thereafter, the output

frequency will be increased/decreased to the set reference value according to

the set acceleration/deceleration parameters.

Use this mode if the motor is coasting when the start command is given. With the flying start it is possible to ride through short mains voltage interruptions.

506

Stop function

(2.1.12)

Coasting:

0

The motor coasts to a halt without any control from the AC drive, after the Stop

command.

Ramp: 1

After the Stop command, the speed of the motor is decelerated according to the set deceleration parameters. If the regenerated energy is high it may be necessary to use an external braking resistor for faster deceleration.

Normal stop: Ramp/ Run Enable stop: coasting

2

After the Stop command, the speed of the motor is decelerated according to

the set deceleration parameters. However, when Run Enable is selected, the

motor coasts to a halt without any control from the AC drive.

Normal stop: Coasting/ Run Enable stop: ramping

3

The motor coasts to a halt without any control from the AC drive. However,

when Run Enable signal is selected, the speed of the motor is decelerated

according to the set deceleration parameters. If the regenerated energy is

high it may be necessary to use an external braking resistor for faster

deceleration.

507

DC-braking current

(2.4.3)

Defines the current injected into the motor during DC-braking.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

36 · vacon

Description of parameters

508

DC-braking time at stop

(2.4.4)

Determines if braking is ON or OFF and the braking time of the DC-brake when the motor is stopping. The function of the DC-brake depends on the stop function, parameter ID506.

0

DC-brake is not used

>0

DC-brake is in use and its function depends on the Stop function,

(param. ID506). The DC-braking time is determined with this parameter.

Par. ID506 = 0; Stop function = Coasting:

After the stop command, the motor coasts to a stop without control of the AC drive.

With DC-injection, the motor can be electrically stopped in the shortest possible time, without using an optional external braking resistor.

The braking time is scaled according to the frequency when the DC-braking starts. If the frequency is  the nominal frequency of the motor, the set value of parameter ID508 determines the braking time. When the frequency is 10% of the nominal, the braking time is 10% of the set value of parameter ID508.

fout

fout

fn

fn

Output frequency

Motor speed

Output frequency

DC-braking ON

0,1 x fn

Motor speed

DC-braking ON

t

t

t = 1 x Par. ID508

t = 0,1 x Par. ID508

RUN STOP

RUN STOP

Figure 14. DC-braking time when Stop mode = Coasting.

NX12K21

Par. ID506 = 1; Stop function = Ramp:
After the Stop command, the speed of the motor is reduced according to the set deceleration parameters, as fast as possible, to the speed defined with parameter ID515, where the DC-braking starts.
The braking time is defined with parameter ID508. If high inertia exists, it is recommended to use an external braking resistor for faster deceleration. See Figure 15.

fout
par. ID515
RUN STOP

Motor speed Output frequency
DC-braking
t t = Par. ID508
NX12K23

Figure 15. DC-braking time when Stop mode = Ramp

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

509

Prohibit frequency area 1; Low limit

510

Prohibit frequency area 1; High limit

(2.5.1) (2.5.2)

In some systems it may be necessary to avoid certain frequencies because of mechanical resonance problems. With these parameters it is possible to set limits for the "skip frequency" region. See Figure 16.

Output frequency [Hz]

vacon · 37

ID509 ID510

Reference [Hz]
NX12K33
Figure 16. Example of prohibit frequency area setting.

515 516
518 limits

DC-braking frequency at stop

(2.4.5)

The output frequency at which the DC-braking is applied. See Figure 16.

DC-braking time at start

(2.4.6)

DC-brake is activated when the start command is given. This parameter defines the time before the brake is released. After the brake is released, the output frequency increases according to the set start function by parameter ID505.

Acceleration/deceleration ramp speed scaling ratio between prohibit frequency 23457 (2.5.3, 2.5.7)
Defines the acceleration/deceleration time when the output frequency is between the selected prohibit frequency range limits (parameters ID509 and ID510). The ramping speed (selected acceleration/ deceleration time 1 or 2) is multiplied with this factor. E.g. value 0.1 makes the acceleration time 10 times shorter than outside the prohibit frequency range limits.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

38 · vacon

Description of parameters

fout [Hz]

Par. ID510 Par. ID509

Par. ID518 = 0,2 Par. ID518 = 1,2

Time [s]
NX12k81
Figure 17. Ramp speed scaling between prohibit frequencies

519

Flux braking current

(2.4.8)

Defines the flux braking current value. The value setting range depends on the used application.

520

Flux brake

(2.4.7)

Instead of DC braking, flux braking is a useful way to raise the braking capacity in cases where additional brake resistors are not needed. When braking is needed, the frequency is reduced and the flux in the motor is increased, which in turn increases the motor's capability to brake. Unlike DC braking, the motor speed remains controlled during braking.

The flux braking can be set ON or OFF.

0 = Flux braking OFF 1 = Flux braking ON

Note: Flux braking converts the energy into heat at the motor, and should be used intermittently to avoid motor damage.

600

Motor control mode

(2.6.1)

0 Frequency control:

The I/O terminal and keypad references are frequency references and the AC drive controls the output frequency (output frequency resolution = 0.01 Hz)

1 Speed control:

The I/O terminal and keypad references are speed references and the AC drive controls the motor speed compensating the motor slip (accuracy ± 0.5%).

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 39

601

Switching frequency

(2.6.8)

Motor noise can be minimised using a high switching frequency. Increasing the switching frequency reduces the capacity of the AC drive unit. The range of this parameter depends on the size of the AC drive:

Type 0016--0061 NX_5 0072--2300 NX_5 0170--1500 NX_6

Min. [kHz] 1.0 1.0 1.0

Max. [kHz] 10,0 10.0 6.0

Table 31. Size-dependent switching frequencies

Default [kHz] 10.0 3.6 1.5

Note! The actual switching frequency might be reduced down to 1.5kHz by thermal management functions. This has to be considered when using sine wave filters or other output filters with a low resonance frequency.

602

Field weakening point

(2.6.3)

The field weakening point is the output frequency at which the output voltage reaches the set (ID603) maximum value.

603

Voltage at field weakening point

(2.6.4)

Above the frequency at the field weakening point, the output voltage remains at the set maximum value. Below the frequency at the field weakening point, the output voltage depends on the setting of the U/f curve parameters. See parameters ID109, ID108, ID604 and ID605. When the parameters ID110 and ID111 (nominal voltage and nominal frequency of the motor) are set, the parameters ID602 and ID603 are automatically given the corresponding values. If you need different values for the field weakening point and the maximum output voltage, change these parameters after setting the parameters ID110 and ID111.

604

U/f curve, middle point frequency (2.6.5)

If the programmable U/f curve has been selected with parameter ID108 this parameter defines the middle point frequency of the curve. See Figure 2.

605

U/f curve, middle point voltage

(2.6.6)

If the programmable U/f curve has been selected with the parameter ID108 this parameter defines the middle point voltage of the curve. See Figure 2.

606

Output voltage at zero frequency (2.6.7)

If the programmable U/f curve has been selected with the parameter ID108 this parameter defines the zero frequency voltage of the curve. NOTE: If the value of parameter ID108 is changed this parameter is set to zero. See Figure 2.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

40 · vacon

Description of parameters

607

Overvoltage controller

(2.6.9)

These parameters allow the under-/overvoltage controllers to be switched out of operation. This may be useful, for example, if the mains supply voltage varies more than ­15% to +10% and the application will not tolerate this over-/undervoltage. In this case, the regulator controls the output frequency taking the supply fluctuations into account.

0 Controller switched off 1 Controller switched on = Minor adjustments of OP frequency are made

608

Undervoltage controller

(2.6.10)

See par. ID607. Note: Over-/undervoltage trips may occur when controllers are switched out of operation.

0 Controller switched off 1 Controller switched on = Minor adjustments of OP frequency are made

700

Response to the 4mA reference fault

(2.7.1)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

A warning or a fault action and message is generated if the 4...20 mA reference signal is used and the signal falls below 3.5 mA for 5 seconds or below 0.5 mA for 0.5 seconds. The information can also be programmed into relay outputs RO1 or RO2.

701

Response to external fault

(2.7.2)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

A warning or a fault action and message is generated from the external fault signal in the programmable digital input DIN3. The information can also be programmed into relay outputs RO1 or RO2.

702

Output phase supervision

(2.7.5)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

Output phase supervision of the motor ensures that the motor phases have an approximately equal current.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 41

703

Earth fault protection

(2.7.6)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

Earth fault protection ensures that the sum of the motor phase currents is zero. The overcurrent protection is always working and protects the AC drive from earth faults with high currents.

704

Motor thermal protection

(2.7.7)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

If tripping is selected the drive will stop and activate the fault stage. Deactivating the protection, i.e. setting parameter to 0, will reset the thermal stage of the motor to 0%.

705

Motor thermal protection: Motor ambient temp. factor

The factor can be set between -100.0%...100.0%.

(2.7.8)

706

Motor thermal protection: Motor cooling factor at zero speed (2.7.9)

The current can be set between 0--150.0% x InMotor. This parameter sets the value for thermal current at zero frequency. See Figure 18.

The default value is set assuming that there is no external fan cooling the motor. If an external fan is used this parameter can be set to 90% (or even higher).

Note: The value is set as a percentage of the motor name plate data, par. ID113 (Nominal current of motor), not the drive's nominal output current. The motor's nominal current is the current that the motor can withstand in direct on-line use without being overheated.

Pcooling
100%

Overload area IT

If you change the parameter Nominal current of motor, this parameter is automatically restored to the default value.

Par. ID706=40%

Setting this parameter does not affect the

maximum output current of the drive which

is determined by parameter ID107 alone.

0

fn

f

NX12k62

Figure 18. Motor thermal current IT curve

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

42 · vacon

Description of parameters

707

Motor thermal protection: Time constant

(2.7.10)

This time can be set between 1 and 200 minutes.

This is the thermal time constant of the motor. The bigger the motor, the bigger the time constant. The time constant is the time within which the calculated thermal stage has reached 63% of its final value.

The motor thermal time is specific to the motor design and it varies between different motor manufacturers.

If the motor's t6­time (t6 is the time in seconds the motor can safely operate at six times the rated current) is known (given by the motor manufacturer) the time constant parameter can be set basing on it. As a rule of thumb, the motor thermal time constant in minutes equals to 2xt6. If the drive is in stop stage the time constant is internally increased to three times the set parameter value. The cooling in the stop stage is based on convection and the time constant is increased. See also Figure 19.

708

Motor thermal protection: Motor duty cycle

(2.7.11)

Defines how much of the nominal motor load is applied. The value can be set to 0%...100%.

Motor temperature

105%
Motor current
I/IT

Trip area

Fault/warning par. ID704

Time constant T*)
Motor temperature  = (I/IT)2 x (1-e-t/T)
*) Changes by motor size and
adjusted with parameter ID707
Figure 19. Motor temperature calculation

Time
NX12k82

709

Stall protection

(2.7.12)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

Setting the parameter to 0 will deactivate the protection and reset the stall time counter.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

710

Stall current limit

(2.7.13)

The current can be set to 0.0...2*IH. For a stall stage to occur, the current must have exceeded this limit. See Figure 20. The software does not allow entering a greater value than 2*IH. If parameter ID107 Nominal current limit of motor is changed, this parameter is automatically calculated to 90% of the current limit.

vacon · 43
I
Stall area Par. ID710

f Par. ID712 NX12k63

Figure 20. Stall characteristics settings

711

Stall time

(2.7.14)

This time can be set between 1.0 and 120.0s. This is the maximum time allowed for a stall stage. The stall time is counted by an internal up/down counter. If the stall time counter value goes above this limit the protection will cause a trip (see ID709).

Stall time counter

Par. ID711

Trip area

Trip/warning par. ID709

Stall No stall

Time
NX12k64

Figure 21. Stall time count

712

Stall frequency limit

(2.7.15)

The frequency can be set between 1-fmax (ID102). For a stall state to occur, the output frequency must have remained below this limit.

713

Underload protection

(2.7.16)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

If tripping is set active the drive will stop and activate the fault stage. Deactivating the protection by setting the parameter to 0 will reset the underload time counter to zero.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

44 · vacon

Description of parameters

714

Underload protection, field weakening area load

(2.7.17)

The torque limit can be set between 10.0--150.0 % x TnMotor. This parameter gives the value for the minimum torque allowed when the output frequency is above the field weakening point. See Figure 22.

Par. ID714

Torque

If you change parameter ID113 (Motor nominal current) this parameter is automatically restored to the default value.

Par. ID715

5 Hz

Underload area
Fieldweakening point par. ID602

f
NX12k65

Figure 22. Setting of minimum load

715

Underload protection, zero frequency load

(2.7.18)

The torque limit can be set between 5.0--150.0 % x TnMotor. This parameter gives value for the minimum torque allowed with zero frequency. See Figure 22.

If you change the value of parameter ID113 (Motor nominal current) this parameter is automatically restored to the default value.

716

Underload time

(2.7.19)

This time can be set between 2.0 and 600.0 s. This is the maximum time allowed for an underload state to exist. An internal up/down counter counts the accumulated underload time. If the underload counter value goes above this limit the protection will cause a trip according to parameter ID713). If the drive is stopped the underload counter is reset to zero. See Figure 23.

Underload time counter

Par. ID716

Trip area

Trip/warning par. ID713

Time Underload No underl.
NX12k66
Figure 23. Underload time counter function
Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 45

717

Automatic restart: Wait time

(2.8.1)

Defines the time before the AC drive tries to automatically restart the motor after the fault state has disappeared.

718

Automatic restart: Trial time

(2.8.2)

The Automatic restart function restarts the AC drive when the fault state has disappeared and the waiting time has elapsed.

The trial time count starts from the first autorestart. If the number of faults occurring during the trial time exceeds 3, the fault state becomes active. Otherwise the fault is cleared after the trial time has elapsed and the next fault starts the trial time count again.

If a single fault remains during the trial time, a fault state is true.

719

Automatic restart: Start function

(2.8.3)

The Start function for Automatic restart is selected with this parameter. The parameter defines the start mode:

0 = Start with ramp 1 = Flying start 2 = Start according to ID505

727

Response to undervoltage fault

(2.7.4)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

For the undervoltage limits, see the product's user manual.

730

Input phase supervision

(2.7.3)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

The input phase supervision ensures that the input phases of the AC drive have an approximately equal current.

731

Automatic restart

(2.1.16)

The Automatic restart is taken into use with this parameter.

0 = Disabled 1 = Enabled

The function resets the following faults (max. three times) (see the product's user manual:

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

46 · vacon

Description of parameters

· Overcurrent (F1) · Overvoltage (F2) · Undervoltage (F9) · AC drive overtemperature (F14) · Motor overtemperature (F16) · Reference fault (F50)

732

Response to thermistor fault

(2.7.20)

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to ID506 3 = Fault, stop mode after fault always by coasting

Setting the parameter to 0 will deactivate the protection.

733

Response to fieldbus fault

(2.7.21)

Set here the response mode for the fieldbus fault if a fieldbus board is used. For more information, see the respective Fieldbus Board Manual.

See parameter ID732.

734

Response to slot fault

(2.7.22)

Set here the response mode for a board slot fault due to missing or broken board.

See parameter ID732.

735

Actual value supervision function (2.7.22)

0 = Not used 1 = Warning, if actual value falls below the limit set with par. ID736 2 = Warning, if actual value exceeds the limit set with par. ID736 3 = Fault, if actual value falls below the limit set with par. ID736 4 = Fault, if actual value exceeds the limit set with par. ID736

736

Actual value supervision limit

(2.7.24)

With this parameter you can set the limit (in percent) of actual value supervised by par. ID735.

737

Actual value supervision delay

(2.7.25)

Set here the delay for the actual value supervision function (par. ID735) If this parameter is in use, the function of par. ID735 will be active only when the actual value stays outside the defined limit for the time determined by this parameter.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 47

852 to 859
1503 1504 1505 1509 1510 1513 1514

Fieldbus data out selections 1 to 8

6

(2.11.1 to 2.11.8)

Using these parameters, you can monitor any monitoring or parameter value from the fieldbus. Enter the ID number of the item you wish to monitor for the value of these parameters.

Some typical values:

1 Output frequency 2 Motor speed 3 Motor current 4 Motor torque 5 Motor power 6 Motor voltage 7 DC link voltage 8 Unit temperature 9 Motor temperature 13 AI1 14 AI2
Table 4-32.

15 Digital inputs 1,2,3 statuses

16 Digital inputs 4,5,6 statuses

17 Digital and relay output statuses

25 Frequency reference

26 Analogue output current

27 AI3

28 AI4

31 AO1 (expander board)

32 AO2 (expander board)

37 Active fault 1

45

Motor current (drive independent) given with one decimal point

Delayed fault

(2.10.12)

If the sensor signals of too low a coolant flow in the system and the duration of this state exceeds the time set with this parameter, a fault is activated. Additionally, the Cooling OK signal is removed and the AC drive stops.

Coolant inlet pressure, minimum Coolant inlet pressure, maximum

(2.10.2.) (2.10.3.)

With these parameters, you can define the value for the minimum and maximum coolant inflow pressures of the pressure range in bar.

Temperature sensor, minimum value Temperature sensor, maximum value

(2.10.6) (2.10.7)

Relay output 2 function See Table 30 at parameter ID313.

(2.3.5.2)

Constant speed

(2.10.1)

The constant speed reference can be set with this parameter when the PID control is enabled.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

48 · vacon

Description of parameters

1515
1517 1518
1520
1526
1529
1530 1531 1532 1533 1534
1535 1536 1537 1538 1539
1540 1541 1542
1544 1545 1546

Relay output 3 function

(2.3.6.2)

Setting value 0 = Not used

Signal content Out of operation

1 = Cooling OK

2 = Pump 1

3 = Pump 2

Table 33. Output signals via relay outputs RO3 and RO4.

AI3 custom setting minimum AI3 custom setting maximum
See parameters ID380 and ID381.

(2.2.18) (2.2.19)

AI3 signal range
0 Signal range 0...20 mA 1 Signal range 4...20 mA

(2.2.16)

AI3 signal filter time See parameter ID378.

(2.2.21)

AI3 signal inversion See parameter ID387.

(2.2.20)

Analogue output 2 function Analogue output 2 filter time Analogue output 2 inversion Analogue output 2 minimum Analogue output 2 scale

(2.3.2.1) (2.3.2.2) (2.3.2.3) (2.3.2.4) (2.3.2.5)

See respective parameters 307 to 311 at Analogue output 1.

Analogue output 3 function Analogue output 3 filter time Analogue output 3 inversion Analogue output 3 minimum Analogue output 3 scale

(2.3.3.1) (2.3.3.2) (2.3.3.3) (2.3.3.4) (2.3.3.5)

See respective parameters 307 to 311 at Analogue output 1.

Relay output 1 inversion Relay output 2 inversion Relay output 3 inversion

(2.3.4.3) (2.3.5.3) (2.3.6.3)

If the values of these parameters = 0, no inversion of the respective relay output signal takes place.

Analogue input 1 supervision Analogue input 2 supervision Analogue input 3 supervision

(2.2.4) (2.2.10) (2.2.17)

The signal level of the respective analogue input is supervised if value 1 is given to this parameter.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 49

1549 1550 1551 1552
1553 1554 1555 1556 1557 1558
1567 1568 1569
1570
1572

Relay output 1, signal selection Relay output 2, signal selection Relay output 3, signal selection Relay output 4, signal selection

(2.3.4.1) (2.3.5.1) (2.3.6.1) (2.3.7.1)

Connect the RO signal to the relay output of your choice with this parameter using the TTF programming method. More information on the TTF method in Vacon All in One Application manual. You will find the relay output signal contents on page 29.

Relay output 4 function See Table 33.

(2.3.7.2)

Relay output 4 inversion See par. ID1540.

(2.3.7.3)

Relay output 5, signal selection See par. ID1549.

(2.3.8.1)

Relay output 5 function See Table 33.

(2.3.8.2)

Relay output 5 inversion See par. ID1540.

(2.3.8.3)

AI3 signal selection

(2.2.15)

Connect the AI3 signal to the analogue input of your choice with this parameter using the TTF programming method. More information on the TTF method in Vacon All in One Application manual.

Relay output 6 function See Table 33.

(2.3.9.2)

Relay output 6 inversion See par. ID1540.

(2.3.9.3)

Coolant inlet pressure supervision

(2.10.5)

If the system is equipped with a pressure sensor set value 1 for this parameter and 0 if no sensor is installed.

Coolant inlet pressure alarm limit

(2.10.4)

When the inlet pressure drops below the limit set with this parameter, a warning is triggered. A pressure sensor must be installed in the system.

DIN6 function

(2.2.3)

This parameter has 2 selections. The default value is 0.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

50 · vacon
0 Preset Speed 1 1 Fault reset
Contact closed: All faults reset

Description of parameters

1573

Relay output 6, signal selection See par. ID1549.

(2.3.9.1)

1590
1591 1594 1595 1599

DIN2 input

(2.2.1)

This parameter changes the default status of the digital input.

0 = Digital input 'normally open' 1 = Digital input 'normally closed'

Coolant outlet temperature alarm, lower limit Coolant outlet temperature alarm, upper limit

(2.10.8) (2.10.9)

Set here the temperature minimum and maximum limits for the coolant. If the temperature goes below or exceeds the set limits a warning is triggered.

Coolant outlet temperature fault, upper limit

(2.10.10)

Set here the temperature maximum limit for the coolant. If the temperature exceeds the set limits, a temperature fault is triggered.

Autochange interval

(2.10.11)

After the expiry of the time defined with this parameter, the autochange function takes place. The available time range for the autochange varies from 1 to 168 hours.

0

Test mode; Autochange after 30 seconds

1 to 168 Time range for autochange in hours

169

Single motor used; no autochange

· The time count is activated only if the Start/Stop request is active. · The time count is reset after the autochange has taken place.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

Description of parameters

vacon · 51

1575 1576

PID output, dead band PID output, dead band delay

(2.9.10) (2.9.11)

This function is designed to prevent wear and unwanted movements of the actuators, for example valves.

Use Dead band parameter to define dead band area around the PID setpoint value (temperature setpoint). The output of the PID controller will be locked, if the actual temperature (measured temperature) stays in the dead band area for the set time.

Use Dead band delay parameter to set the time that the actual temperature must stay in the dead band area, before the output of the PID controller is locked.

The output of the PID controller will be released, if the actual temperature goes outside of the dead band area.

Note! This function is disabled when Dead Band = 0.

24-hour support: +358 (0)201 212 575 · Email: vacon@vacon.com
4

52 · vacon

Description of parameters

4.1 Keypad control parameters
Unlike the parameters listed above, these parameters are located in the M3 menu of the control keypad. The reference parameters do not have an ID number.

114

Stop button activated

(3.4)

If you wish to make the Stop button a "hotspot" which always stops the drive regardless of the selected control place, give this parameter the value 1. See also parameter ID125.

125

Control place

(3.1)

The active control place can be changed with this parameter. For more information, see the product's user manual. Pushing the Start button for 3 seconds selects the control keypad as the active control place and copies the Run status information (Run/Stop, direction and reference).

123

Keypad direction

(3.3)

0

Forward: The rotation of the motor is forward, when the keypad is the active

control place.

1

Reverse: The rotation of the motor is reversed, when the keypad is the active

control place.

For more information, see the product's user manual.

R3.2

Keypad Reference

(3.2)

The frequency reference can be adjusted from the keypad with this parameter. The output frequency can be copied as the keypad reference by pushing the Stop button for 3 seconds when you are on any of the pages of menu M3. For more information, see the product's user manual.

R3.4

PID reference 1

(3.4)

With this parameter, you can set the desired temperature for the coolant circulating in the system.

R3.5

PID reference 2

(3.5)

With this parameter, you can set another, optional temperature for the coolant circulating in the system. The value is activated by setting the value 10 for parameter ID301. See page 27.

Tel. +358 (0)201 2121 · Fax: +358 (0)201 2121 205
4

www.danfoss.com

Vacon Ltd
Member of the Danfoss Group
Runsorintie 7 65380 Vaasa Finland

Document ID:
DPD01890A Rev. A



References

Danfoss A/S GPL Ghostscript 9.55.0