User Guide for HK INSTRUMENTS models including: AVT Air Velocity Transmitter, AVT, Air Velocity Transmitter, Velocity Transmitter, Transmitter
AVT User Guide 8.2 231114 » HK Instruments - User-friendly measuring devices
Published: 14.11.2023 3 (25) 1 Introduction Thank you for choosing an AVT air velocity transmier. It is an air velocity and temperature transmier.
File Info : application/pdf, 25 Pages, 1.49MB
DocumentDocumentAVT air velocity transmitter USER GUIDE Published: 14.11.2023 2 (25) Contents 1 Introducon............................................................................................................................... 3 1.1 About this user guide............................................................................................................................................................. 3 1.2 Intended use............................................................................................................................................................................. 3 2 Descripon of the product....................................................................................................4 2.1 Overview of the main parts..................................................................................................................................................4 2.2 Technical specificaons.......................................................................................................................................................... 5 2.3 Dimensions................................................................................................................................................................................ 6 3 Safety precauons................................................................................................................... 7 4 Commissioning.......................................................................................................................... 8 4.1 Warm-up mode........................................................................................................................................................................ 8 4.2 Mounng the product............................................................................................................................................................ 8 4.3 Wiring..........................................................................................................................................................................................9 4.3.1 Modbus models (-MOD)......................................................................................................................................10 4.4 Selecng the measurement range.....................................................................................................................................11 4.5 Selecng the output mode................................................................................................................................................. 11 4.6 Configuring sengs via device menu.............................................................................................................................. 12 4.6.1 Available sengs for velocity and temperature............................................................................................14 4.6.2 Relay sengs......................................................................................................................................................... 16 4.6.3 Exit menu view...................................................................................................................................................... 17 4.7 Available sengs for Modbus........................................................................................................................................... 17 4.7.1 Baud rate menu..................................................................................................................................................... 17 4.7.2 Address menu.........................................................................................................................................................18 4.7.3 Parity bit menu...................................................................................................................................................... 18 4.7.4 Vel. unit menu........................................................................................................................................................18 4.7.5 Temp. unit menu....................................................................................................................................................18 4.7.6 Exit menu view...................................................................................................................................................... 18 4.8 Locking the cover.................................................................................................................................................................. 18 5 Modbus.....................................................................................................................................19 5.1 Terminang Modbus............................................................................................................................................................. 19 5.2 Modbus properes................................................................................................................................................................19 5.3 Modbus funcon codes....................................................................................................................................................... 19 5.4 Modbus registers................................................................................................................................................................... 20 5.4.1 Input registers........................................................................................................................................................ 20 5.4.2 Holding registers....................................................................................................................................................21 6 Maintenance............................................................................................................................23 6.1 Cleaning the probe and the sensor element.................................................................................................................. 23 7 Disposal.................................................................................................................................... 24 8 Warranty policy......................................................................................................................25 Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 3 (25) 1 Introduction Thank you for choosing an AVT air velocity transmier. It is an air velocity and temperature transmier. The -MOD models have Modbus communicaon instead of analogue outputs. Other models have one analogue air velocity output and one analogue temperature output. You can select the measurement range and the output mode for the analogue outputs on the field during commissioning. The oponal display shows air velocity and temperature measurement values. The -MOD models have an RS-485 connecon for Modbus RTU communicaon. The -R model includes a relay and a relay connector. You can configure the device sengs using: · the device menu (-D models) · Modbus communicaon (-MOD models) 1.1 About this user guide This user guide contains important informaon about the installaon, wiring, configuraon and use of the product. Read this guide carefully before you install the product, connect the wires, or operate the product. Make sure that you fully understand all instrucons before you start work. If you are not sure what the instrucons mean, contact the seller or the manufacturer. Follow all instrucons in this user guide carefully. Always obey the applicable local rules and regulaons. The original instrucons were wrien in English. If there are differences between the English instrucons and the translaons, refer to the English instrucons. If you find a mistake in the English instrucons or in the translaons, please send the details to the manufacturer. 1.2 Intended use The AVT air velocity transmiers are intended to be used in commercial environments for measuring air velocity and temperature in venlaon ducts. They are compable with dry air. The AVT air velocity transmiers are not intended to be used with flammable or corrosive gases. These transmiers are intended to be connected to building automaon systems in the HVAC/R industry. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 2 Description of the product This secon introduces the main parts of the product and contains the technical specificaons. 2.1 Overview of the main parts I J A H B G F C E K D A Display (-D models) C Cable gland E Cover locking screw (-R models) G Probe I Bolt and nut for locking the probe in posion K Holes for fixing screws B Cover D Strain relief F Duct flange H Sensor element J Housing 4 (25) L Tout/B M Vout/A 24V NC COM GND NO N O P Q Tout/B Vout/A R 24V GND S L Menu buons (-D models) M Jumper for temperature output signal selecon (excluding -MOD models) N Jumper for air velocity output signal selecon (excluding O Terminal block -MOD models) P Relay (-R models) Q Measurement range selecon jumpers (excluding -D models) R Modbus terminaon jumper (-MOD models) S Relay connector (-R models) Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug 2.2 Technical specifications Property Supply Current consumpon Relay (-R models) Air velocity measurement Measurement range Accuracy (typ. at 25 °C) Temperature measurement Measurement range Accuracy (25 °C) Warm-up me Outputs Output signal 1 (T out [C]) Output signal 2 (v out [m/s]) Accuracy Relay output (-R models) Communicaon (MOD models) Display (-D models) Operang condions Temperature Humidity IP protecon class Wire Cable gland Published: 14.11.2023 5 (25) Value 24 Vac/dc ± 10 % max. 80 mA + 40 mA with mA output + 10 mA with relay opon (DC supply voltage) 250 Vac, 6 A res., adjustable operang direcon, switching point and hysteresis 0...2 m/s, 0...10 m/s, 0...20 m/s, freely selectable v 0.15 m/s and 2 m/s (0.2 m/s + 2 % from reading) v > 2 m/s and 10 m/s (0.5 m/s + 3 % from reading) v > 10 m/s (1.0 m/s + 3 % from reading) -25...50 °C (probe) ±0.5 °C (air velocity > 0.5 m/s) 15 seconds 0...10 Vdc, load > 1 k 4...20 mA, load 20...400 0...10 Vdc, load > 1 k 4...20 mA, load 20...400 Vout: ± 0.025 V at 25 °C Iout: typically ±0.04 mA at 25 °C, load 100 max. ± 0.1 mA at 25 °C, load 20...400 3-screw terminal block (NC, COM, NO), potenal free SPDT 30 Vdc 6 A / 230 Vac 6 A res. (IEC 60664-1 OVC II) Modbus RTU 2-line display (12 characters/line), 46.0 x 14.5 mm Line 1: velocity / Line 2: temperature (default) Line 1: direcon of control output (oponal) Line 2: relay status (oponal) -25...50 °C (probe) 0...50 °C (transmier housing) 0...95 %rH (non-condensing) IP54, cable downwards 0.2...1.5 mm2 (24...16 AWG) M16 (2 x M16: -R models) Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 Property Mounng Materials Housing Cover Probe Duct flange Dimensions (w x h x d) Weight Storage temperature Conformance EMC RoHS WEEE LVD 2.3 Dimensions Value with a duct flange, probe immersion length adjustable: 50...80 mm (probe length 100 mm) 50...180 mm (probe length 200 mm) 50...380 mm (probe length 400 mm) ABS plasc PC plasc Stainless steel LLPDP 86 x 95 x 168 mm (probe length 100 mm) 86 x 95 x 268 mm (probe length 200 mm) 86 x 95 x 468 mm (probe length 400 mm) 220 g -20...70 °C CE 2014/30/EU 2011/65/EU + (EU) 2015/863 2012/19/EU 2014/35/EU UKCA S.I. 2016 No. 1091 S.I. 2012 No. 3032 S.I. 2013 No. 3113 S.I. 2016 No. 1101 All dimensions are in millimeters (mm). 86 36 17 15 6 (25) 71.5 95 46 168 / 268 / 468 Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 7 (25) 3 Safety precautions The product is developed, manufactured and tested according to high quality standards. However, instrucons for safe use shall be taken account when installing, using or disposing the product or parts of product. Read this user guide carefully before commissioning, using or servicing this device. To avoid any kind of damage to people or property, follow the instrucons carefully. HK Instruments is not liable for any hazards or damages to people or property which are caused by ignoring the using or installaon instrucons. To avoid electrical shock or damage to equipment, disconnect power before installing or servicing the product. Use only a proper wiring rated for the full operang voltage and maximum current in the system even in the event of a fault. To avoid potenal fire and/or explosion, do not use the product in potenally flammable or explosive atmosphere. The product condion must be checked before installaon. Do not drop the product or use excessive force during installaon. Do not use the product if any damages are visible. Aer installaon the product will be part of a system whose specificaons and performance characteriscs are not designed or controlled by HK Instruments. Refer to naonal and local authories to ensure that the installaon is funconal and safe. The product should only be used in professionally designed applicaons. Unauthorised modificaons are not allowed. The product must not be used in relaon with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in danger to human beings, animals or property. In this document, there are different kind of warnings and notes. The warning and note types are defined in the following table. Sign WARNING: CAUTION: Important: Descripon The warning symbol indicates a potenally hazardous situaon which, if not avoided, could result in death or serious injury. The cauon symbol indicates a potenally hazardous situaon which, if not avoided, could result in minor or moderate injury. The important symbol indicates a potenally hazardous situaon which, if not avoided, could result in damage to the device or property. Note: The note symbol indicates a useful p or a recommended way to complete a task. These notes also provide informaon that is useful but not crical to the user. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 8 (25) 4 Commissioning 4.1 Warm-up mode This device starts up in warm-up mode. The warm-up mode connues for 15 seconds aer startup. During the warmup me, the output signals are at the defined minimum values and the relay does not operate. If the device has a display, text Warming up is shown on the display. The device starts to operate correctly aer the warm-up me. 4.2 Mounting the product WARNING: Handle the product with care. Dropping the product may cause internal damage and unwanted funcons in the connected system. CAUTION: Place the product outside the reach of children and animals. Important: The product may only be installed in a locaon where the ambient condions meet the operang condion requirements. Note: Remove the device from the air duct before cleaning the duct. Operang condions Temperature Humidity -25...50 °C (probe) 0...50 °C (transmier housing) 0...95 %rH (non-condensing) 1. Check that the product is not damaged during transportaon. 2. Select the mounng posion on a straight duct. Measure the length of the straight duct to make sure that the probe is posioned correctly. See the figure below for the required minimum length of straight duct. · Round ducts: · D = duct diameter · Rectangular ducts: · If there is a horizontal curve or a change in the duct size: D = width of the duct · If there is a vercal curve or a change in the duct size: D = height of the duct 3. Use the duct flange as a template and mark the screw holes and the probe hole on the duct. 4. Drill the screw holes and the probe hole on the duct. The maximum screw diameter is 4 mm. The probe diameter is 10 mm. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 5. Mount the duct flange on the duct with screws. 9 (25) 6. Push the transmier probe into the duct through the hole on the flange. Make sure that the cable glands of the transmier point down. See the figure below for the correct mounng orientaon. 7. Adjust the probe to the correct depth. Make sure that the sensor element is in the middle of the duct. 8. Tighten the bolt and nut on the duct flange to hold the probe in posion. 4.3 Wiring WARNING: Device wiring and commissioning can only be carried out by qualified professionals. Always make the device wirings in de-energised electricity network. WARNING: Fuse at load supply (normally 6 A, 10 A, 16 A) does not always limit the relay output load current to 6 A. The relay maximum load is 250 Vac, 6 A res. WARNING: Add an external fuse to relay common connector. Use a me-lag fuse (max 6 A) that is in accordance with the standard IEC 60127-2. The product does not have an internal fuse for the relays. CAUTION: The product may only be connected to overvoltage category II electricity network according to IEC 60664-1. CAUTION: Use single stranded wires or use wire end sleeves if mul stranded wires are used. For CE and UKCA compliance, a properly grounded shielding cable is required. The relay models (-R) have two cable glands (the le and the right cable gland). Other models only have one cable gland (the le cable gland). 1. Open the cover. WARNING: Do not open the device cover when the relay mains supply voltage is connected. Always do the commissioning of the device in de-energised relay electricity network. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 10 (25) 2. Unscrew the strain relief on the le cable gland and route the cables for power in and signal out through the cable gland. 3. For relay models (-R), unscrew the strain relief on the right cable gland and route the cable for the relay through the cable gland. 4. Connect the wires according to the table below. Tout/B Vout/A 24V GND NC COM NO Tout/B Vout/A 24V GND NC COM NO Temperature measurement output signal: 0...10 Vdc, load > 1 k 4...20 mA, load 20...400 Air velocity measurement output signal: 0...10 Vdc, load > 1 k 4...20 mA, load 20...400 24 Vac/dc 0 V Relay output on -R models: 30 Vdc 6 A / 230 Vac 6 A res. 5. Tighten the strain reliefs. 4.3.1 Modbus models (-MOD) It is recommended to use shielded twisted pair cable for Modbus cabling. The cable shield must be earthed only in one point, usually at the end of the main cable. For CE and UKCA compliance, a properly grounded shielding cable is required. 1. Open the cover. 2. Unscrew the strain relief. 3. Route the cables for power in and Modbus communicaon through the cable gland. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 4. Connect the wires according to the table below. 11 (25) Tout/B Vout/A 24V GND Tout/B Vout/A 24V GND Modbus RTU (RS-485) 24 Vac/dc 0 V 5. Tighten the strain relief. 4.4 Selecting the measurement range There are different methods for selecng the measurement range. The method used depends on the device opons: · Devices that do not have a display: Select the measurement range by installing jumpers as shown in the table below. · Models with display (-D): Select the output signal mode with jumpers and then the measurement range via the device menu. See secon Selecng the output mode on page 11 Selecting the measurement range with jumpers Install the jumpers according to the table below to select the measurement range for devices that do not have a display. J1 Tout/B J2 Vout/A mA V mA V 24V GND 0...2 m/s J1 J2 0...10 m/s 0...20 m/s 4.5 Selecting the output mode Models with analogue output signals have two jumpers for output signal mode selecon on the circuit board. Select the voltage (0...10 V) or the current (4...20 mA) output signal mode based on the system requirements. The current output is not scalable. The voltage output is scalable. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 12 (25) You can configure the output signal separately for air velocity and temperature. Set the jumpers in the correct posion to select the output signal mode (V/mA) for air velocity and temperature. See the table below for the jumper sengs. Tout mA V Vout mA V Output Temperature output Air velocity output Tout Vout Output signal mode: current (mA) Output signal mode: current (mA) Output signal mode: voltage (V) Output signal mode: voltage (V) Output signal mode: Output signal mode: current (mA) voltage (V) Output signal mode: Output signal mode: voltage (V) current (mA) 4.6 Configuring settings via device menu See the figure below for the full menu structure for all models excluding the Modbus models (-MOD). For Modbus model menu structure, see secon Available sengs for Modbus on page 17. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 NO V RANGE MAX 10 m/s VEL. UNIT m/s TEMP. UNIT °C PID IN USE no YES REFERENCE SP 5 m/s P-VALUE 1.00 I-VALUE 1.00 D-VALUE 1.00 AVT-D-R V OUT SCALE 0-10V Custom V OUT MIN 0 V T RANGE MIN 0 °C V OUT MAX 10 V T RANGE MAX 50 °C T OUT SCALE 0-10V Custom T OUT MIN 0 V RELAY DIR Rise T OUT MAX 10 V RELAY SP 5 m/s RELAY HYST 0.5 m/s EXIT MENU 13 (25) Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 A B Tout/B C Vout/A 24V GND 14 (25) A. SELECT buon B. UP buon C. DOWN buon 1. Open the cover. WARNING: Do not open the device cover when the relay mains supply voltage is connected. Always do the commissioning of the device in de-energised relay electricity network. 2. Press the SELECT buon for two seconds to acvate the device menu. 3. Use the UP and DOWN buons to navigate the menu. 4. Press the SELECT buon to change the value of a menu item. 5. Press the UP or DOWN buon to select a value. 6. Press the SELECT buon to accept the new value and to return to menu navigaon. 7. Navigate to the EXIT MENU view and press the SELECT buon to save the sengs and exit the menu. 4.6.1 Available settings for velocity and temperature For Modbus model sengs, see chapter Available sengs for Modbus on page 17. 4.6.1.1 Vel. unit menu You can select the velocity unit for the device display and the velocity output in the VEL. UNIT menu. The available velocity units are m/s and ft/min. The default value is m/s. 4.6.1.2 Temp. unit menu You can select the temperature unit for the device display and the temperature output in the TEMP. UNIT menu. The available temperature units are °C and °F. The default value is °C. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 15 (25) 4.6.1.3 PID in use menu NO PID IN USE YES no V RANGE MAX 10 m/s REFERENCE SP 5 m/s P-VALUE 1.00 I-VALUE 1.00 D-VALUE 1.00 You can select the if PID is in use in the PID IN USE menu. The available values are no and yes. The default value is no. If you select no, the next menu item is V RANGE MAX. If you select yes, the next menu items are REFERENCE SP, P-VALUE, I-VALUE and D-VALUE. V range max menu You can select the maximum value for air velocity measurement range in the V RANGE MAX menu. You can select the maximum velocity measurement range between 1 m/s and 20 m/s. The default value is 10 m/s. If you selected ft/min in the VEL. UNIT menu, you can select the maximum velocity measurement range between 200 /min and 4000 /min. You can adjust the value by 200 /min steps. The default value is 2000 ft/min. Reference SP menu You can select the reference setpoint for the PID controller in the REFERENCE SP menu. You can adjust the value by 0.1 m/s or 1 /min steps depending on the selected air velocity unit. The default value is 5 m/s or 1000 /min. P-value, I-value and D-value menus You can select the proporonal gain in the P-value menu. You can adjust the value by 0.01 unit steps. The default value is 1.00. You can select the integral gain in the I-value menu. You can adjust the value by 0.01 unit steps. The default value is 1.00. You can select the derivave gain in the D-value menu. You can adjust the value by 0.01 unit steps. The default value is 1.00. You can select the P-value, I-value and D-value between 0 and 99.99. 4.6.1.4 V out scale menu You can select the air velocity output scale in the V OUT SCALE menu. The available values are 0-5 V, 0-10 V, 2-10 V and custom. The default value is 0-10 V. If you select custom, you can set the minimum and maximum values for the air velocity output scale. V out min menu If you selected custom in the V OUT SCALE menu, you can select the minimum value for the air velocity output scale in the V OUT MIN menu. You can select a value between 0 V and 10 V. You can adjust the value by 1 V steps. The default value is 0 V. You can select a minimum value that is bigger than the maximum value to reverse the operang direcon. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 16 (25) V out max menu If you selected custom in the V OUT SCALE menu, you can select the maximum value for the air velocity output scale in the V OUT MAX menu. You can select a value between 0 V and 10 V. You can adjust the value by 1 V steps. The default value is 10 V. You can select a maximum value that is smaller than the minimum value to reverse the operang direcon. 4.6.1.5 T range min menu You can select the minimum value for temperature measurement range in the T RANGE MIN menu. You can select a value between -25 °C and 40 °C. You can adjust the value by 5 °C steps. The default value is 0 °C. If you selected °F in the TEMP. UNIT menu, you can select a value between -13 °F and 104 °F. You can adjust the value by 2 °F steps. The default value is 32 °F. 4.6.1.6 T range max menu You can select the maximum value for temperature measurement range in the T RANGE MAX menu. You can select a value between -15 °C and 50 °C. You can adjust the value by 5 °C steps. The default value is 50 °C. If you selected °F in the TEMP. UNIT menu, you can select a value between 5 °F and 122 °F. You can adjust the value by 2 °F steps. The default value is 122 °F. 4.6.1.7 T out scale menu You can select the temperature output scale in the T OUT SCALE menu. The available values are 0-5 V, 0-10 V, 2-10 V and custom. The default value is 0-10 V. If you select custom, you can set the minimum and maximum values for the temperature output scale. T out min menu If you selected custom in the T OUT SCALE menu, you can select the minimum value for the temperature output scale in the T OUT MIN menu. You can select a value between 0 V and 10 V. You can adjust the value by 1 V steps. The default value is 0 V. You can select a minimum value that is bigger than the maximum value to reverse the operang direcon. T out max menu If you selected custom in the T OUT SCALE menu, you can select the maximum value for the temperature output scale in the T OUT MAX menu. You can select a value between 0 V and 10 V. You can adjust the value by 1 V steps. The default value is 10 V. You can select a maximum value that is smaller than the minimum value to reverse the operang direcon. 4.6.2 Relay settings RELAY DIR Rise RELAY SP 5 m/s RELAY HYST 0.5 m/s 4.6.2.1 Relay SP menu This menu is shown only if the transmier has a relay output (-R models). Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 17 (25) You can set the velocity setpoint for the relay in the RELAY SP menu. You can set this value with an accuracy of two decimals. The default value is 5 m/s or 1000 ft/min. 4.6.2.2 Relay dir menu This menu is shown only if the transmier has a relay output (-R models). Relay operang direcon defines if the relay switches on or off when the air velocity is more than the setpoint value. You can select the relay operang direcon in the RELAY DIR menu. The available values are Rise and Fall. The relay switches on if Rise is selected and the air velocity is more than the setpoint value. If Fall is selected, the relay switches on when the air velocity is less than the setpoint value. The default value is Rise. 4.6.2.3 Relay hyst menu This menu is shown only if the transmier has a relay output (-R models). This seng defines how much the air velocity must drop below the setpoint before the relay switches off if Rise is selected in the RELAY DIR menu. The funcon is opposite if Fall is selected in the RELAY DIR menu. You can set the hysteresis value for the relay in the RELAY HYST menu. You can select a value between 0.1 and 20.0 m/s. You can adjust the value by 0.1 m/s steps. The default value is 0.5 m/s. If you selected ft/min in the VEL. UNIT menu, you can select a value between 20 /min and 4000 /min. You can adjust the value by 20 /min steps. The default value is 100 ft/min. 4.6.3 Exit menu view Navigate to the EXIT MENU view and press the SELECT buon to save the sengs and exit the menu. 4.7 Available settings for Modbus The figure below shows the menu structure for the Modbus models (-MOD). These menu sengs are only available in Modbus models (-MOD). BAUD RATE 19200 ADDRESS 1 PARITY BIT None VEL. UNIT m/s TEMP. UNIT °C EXIT MENU 4.7.1 Baud rate menu You can select the baud rate in the BAUD RATE menu. The bus speed can be 9600, 19200 or 38400 bits/s. The default baud rate is 19200 bits/s. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 18 (25) 4.7.2 Address menu You can select the Modbus address in the ADDRESS menu. Address range is 1...247. The default value is 1. 4.7.3 Parity bit menu You can select Modbus parity in the PARITY BIT menu. The available values for bus parity are none, odd and even. The default seng is none. 4.7.4 Vel. unit menu You can select the velocity unit for the device display and the velocity output in the VEL. UNIT menu. The available velocity units are m/s and ft/min. The default value is m/s. 4.7.5 Temp. unit menu You can select the temperature unit for the device display and the temperature output in the TEMP. UNIT menu. The available temperature units are °C and °F. The default value is °C. 4.7.6 Exit menu view Navigate to the EXIT MENU view and press the SELECT buon to save the sengs and exit the menu. 4.8 Locking the cover WARNING: There is a hazardous voltage inside the R-model devices. Always lock the cover before the relay mains supply voltage is connected. 1. Close the cover. 2. Tighten the cover locking screw (-R models). A A. Cover locking screw 3. Make sure that the cover does not open without tools. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 5 Modbus 5.1 Terminating Modbus Insert the terminaon jumper in the last device of the network to terminate the Modbus network. 1. Disconnect the device supply voltage. 2. Open the cover. 3. Insert the terminaon jumper in posion (A). Tout/B A Vout/A 24V GND 19 (25) 4. Close the cover. 5. Reconnect the device supply voltage. 5.2 Modbus properties The Modbus communicaon is only available in -MOD models. The parameter memory durability allows at least 1 000 wring cycles. Note: The changes to the Modbus communicaon sengs take effect aer you restart the device. Protocol Bus speed Data bits Parity Stop bits Modbus ID Unit load RS-485 Modbus RTU 9600/19200*/38400 bit/s 8 none*/odd/even 1 1* 1/8 UL * factory seng 5.3 Modbus function codes The device supports the following Modbus funcon codes. Decimal 3 4 6 16 HexadecimalFuncon 0x03 Read Holding Registers 0x04 Read Input Registers 0x06 Write Single Register 0x10 Write Mulple Registers Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug 5.4 Modbus registers 5.4.1 Input registers General Register 0 1 2 3 4...99 Parameter descripon Velocity m/s Velocity /min Temperature °C Temperature °F Reserved for future use Device model details Register 9800 9801 9802 Parameter descripon Register count Format version Display 9803 Buons 9804 9805 Number of relays Analogue outputs 9806 Modbus 9807 MyTool Connector 9808 PID controller Published: 14.11.2023 Data type U16 U16 S16 S16 Values 0...2000 0...4000 -250...500 -130...1220 Data type U16 U16 U16 Values 0...99 0...65535 0...1 U16 0...1 U16 0...1 U16 0...1 U16 0...1 U16 0...1 U16 0...1 Device information Register 9900 9901 9902 9903 9904 9905 9906...9908 9909 9910 9911 9912 Parameter descripon Device type Hardware version Producon number, MS word Producon number, LS word Configuraon number, MS word Configuraon number, LS word Reserved for MyTool® Ethernet MAC address 1 Ethernet MAC address 2 Ethernet MAC address 3 Wireless MAC address 1 Data type U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 Values 0...65535 0...65535 0...65535 0...65535 0...65535 0...65535 0 0 0 0 Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. 20 (25) Range 0...20 m/s 0...4000 /min -25.0...50.0 °C -13.0...122.0 °F Range 0...99 0...65535 0. no 1. yes 0. no 1. yes 0....1 0. no 1. yes 0. no 1. yes 0. no 1. yes 0. no 1. yes Range 0...65535 0...65535 0...65535 0...65535 0...65535 0...65535 0 0 0 0 User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 21 (25) Register 9913 9914 9915 Parameter descripon Wireless MAC address 2 Wireless MAC address 3 Memory state Data type U16 U16 U16 Values 0 0 0...9 9916 Configuraon compability number U16 9917 Firmware ID, MS word U16 9918 Firmware ID, LS word U16 9919. Firmware version (major, minor) U16 9920 Firmware version (revision, build) U16 9921...9923 Reserved for MyTool® U16 9924 MyTool® compability number U16 5.4.2 Holding registers 0...65535 0...65535 0...65535 0...65535 0...65535 25 0 Range 0 0 0. Idle 1. Loading latest configuraon 2. Saving latest configuraon 3. Loading default configuraon 4. Saving default configuraon 5. Loading calibraon 6. Saving calibraon 7. Saving applicaon state 8. Chip erase in progress 9. Cloud configuraon management 0...65535 0...65535 0...65535 0...65535 0...65535 25 0. Compability number not assigned (feature is not in use) Modbus Register 0 Parameter descripon Baud rate 1 Address 2 Parity bit 3 4 5...199 Velocity unit Temperature unit Reserved for future use Data type U16 Values 0...2 U16 1...247 U16 0...2 U16 0...1 U16 0...1 Range 0. 9600 1. 19200 2. 38400 1...247 0. none 1. even 2. odd 0. m/s 1. /min 0. Celsius 1. Fahrenheit Default 1 1 0 0 0 MyTool Register 200 Parameter descripon PID in use Data type U16 Values 0...1 Range 0. no 1. yes Default 0 Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 Register 201 202 203 204 205 206 207 208 Parameter descripon Velocity range max. (m/s) Velocity range max. (/min) PID velocity setpoint (m/s) PID velocity setpoint (/min) PID P factor PID I factor PID D factor V / VPID out scale Data type U16 U16 U16 U16 U16 U16 U16 U16 Values 1...20 2...40 1...2000 2...4000 0...9999 0...9999 0...9999 0...3 209 V / VPID out scale custom min. U16 0...10 210 V / VPID out scale custom max. U16 0...10 211 Temperature range min. (°C) U16 -25...40 212 Temperature range min. (°F) U16 -13...104 213 Temperature range max. (°C) U16 -15...50 214 Temperature range max (°F) U16 5...122 215 T out scale U16 0...3 216 T out scale custom min. 217 T out scale custom max. 218 Relay operang direcon 219 Relay setpoint (m/s) 220 Relay setpoint (/min) 221 Relay hysteresis (m/s) 222 Relay hysteresis (/min) Other holding registers Register 9900...9915 9995...9998 9999 63000...63999 64000...64999 Parameter descripon Device name 00...15 Device control data Device control header Calibraon (reserved) Firmware update (reserved) U16 0...10 U16 0...10 U16 0...1 U16 1...2000 U16 2...4000 U16 1...2000 U16 2...4000 Data type U16 U16 U16 Values 0...65535 0...65535 0...65535 22 (25) Range 1...20 m/s 200...4000 /min 0.01...20 m/s 2...4000 /min 0...99.99 0...99.99 0...99.99 0. 0...5 V 1. 0...10 V 2. 2...10 V 3. Custom 0...10 V 0...10 V -25...40 °C -13...104 °F -15...50 °C 5...122 °F 0. 0...5 V 1. 0...10 V 2. 2...10 V 3. Custom 0...10 V 0...10 V 0. Rise 1. Fall 0.01...20 m/s 2...4000 /min 0.01...20 m/s 2...4000 /min Default 10 20 500 1000 100 100 100 1 0 10 0 32 50 122 1 0 10 0 500 1000 50 100 Range [0...255], [0...255] 0...65535 0...65535 Default 0 0 0 Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 23 (25) 6 Maintenance 6.1 Cleaning the probe and the sensor element Dust, grease and other dirt can accumulate on the sensor element over me and decrease the measurement accuracy of the sensors. Clean the probe and the sensor element regularly. The required cleaning interval depends on the air cleanliness. Do not clean the sensor element with detergents or other chemicals. 1. Disconnect the device supply voltage. For the -R models, disconnect the device supply voltage and the relay mains supply voltage. 2. Clean the probe with a so cloth. A B A. Probe B. Sensor element 3. Clean the sensor element with compressed air. Apply compressed air lighly to the sensor element to prevent damage. Important: Do not use too high pressure, touch the sensor element or use other cleaning methods that cause mechanical stress. Mechanical stress damages the sensor element and changes the measurement accuracy of the sensors. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 24 (25) 7 Disposal The device is considered as electrical and electronic equipment for disposal in terms of the applicable European Direcve. At the end of life the product must enter the recycling system at an appropriate collecon point. · The device must be disposed through channels provided for this purpose. · The disposal must be completed according to the local and currently applicable laws and regulaons. Generally all metals can be recycled as material. Plascs and cardboard packaging material can be used in energy recovery. Printed circuit boards need selecve treatment according to IEC 62635 guidelines. To aid recycling, plasc parts are marked with an appropriate idenficaon code. Contact your local HK Instruments distributor for further informaon on environmental aspects and recycling instrucons for professional recyclers. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ug Published: 14.11.2023 25 (25) 8 Warranty policy The seller is obligated to provide a warranty of five years for the delivered goods regarding material and manufacturing. The warranty period is considered to start on the delivery date of the product. If a defect in raw materials or a producon flaw is found, the seller is obligated, when the product is sent to the seller without delay or before expiraon of the warranty, to amend the mistake at his/her discreon either by repairing the defecve product or by delivering free of charge to the buyer a new flawless product and sending it to the buyer. Delivery costs for the repair under warranty will be paid by the buyer and the return costs by the seller. The warranty does not comprise damages caused by accident, lightning, flood or other natural phenomenon, normal wear and tear, improper or careless handling, abnormal use, overloading, improper storage, incorrect care or reconstrucon, or changes and installaon work not done by the seller. The selecon of materials for devices prone to corrosion is the buyer's responsibility, unless otherwise is legally agreed upon. Should the manufacturer alter the structure of the device, the seller is not obligated to make comparable changes to devices already purchased. Appealing for warranty requires that the buyer has correctly fulfilled his/her dues arisen from the delivery and stated in the contract. The seller will give a new warranty for goods that have been replaced or repaired within the warranty, however only to the expiraon of the original product's warranty me. The warranty includes the repair of a defecve part or device, or if needed, a new part or device, but not installaon or exchange costs. Under no circumstance is the seller liable for damages compensaon for indirect damage. Copyright HK Instruments 2023 www.hkinstruments.fi Informaon is subject to change without prior noce. User guide Version 8.2 2023 EN - 1130100000ugApache FOP Version 2.1 DITA Open Toolkit