Instruction Manual for BEKA models including: BA364G Counters Intrinsically safe, BA364G, Counters Intrinsically safe, Intrinsically safe

BA364G

Abbreviated Instruction manuals


File Info : application/pdf, 2 Pages, 810.81KB

PDF preview unavailable. Download the PDF instead.

ba364g short form
1.

DESCRIPTION

The BA364G is a field mounting intrinsically safe, two input

Counter which will function with a wide variety of sensors.

The instrument can display rate and total of the two inputs

and their sum or difference.

This abbreviated instruction sheet is intended to assist with installation, a comprehensive instruction manual describing safety certification, system design and configuration may be downloaded from the BEKA website or may be requested from the BEKA sales office.

The BA364G Counter has IECEx, ATEX, UKEX, ETL and cETL intrinsic safety certification for use in flammable gas and dust atmospheres. The certification information label, which is located on the top of the instrument assembly, shows the certification numbers and codes. Other certifications may be shown. Copies of certificates may be downloaded from the BEKA website.

Typical certification information label

2.

INSTALLATION

The BA364G Counter has a robust IP66 glass reinforced

polyester (GRP) carbon loaded enclosure incorporating an

armoured glass window & stainless steel fittings. It is suitable

for exterior surface mounting in most industrial environments,

or pipe mounting using an accessory kit.

If the enclosure is not bolted to an earthed post or structure, the earth terminal on the cable entry bonding plate, which may be assembled on the inside or outside of the enclosure, should be connected to local earthed metalwork or to the plant's potential equalising conductor.

Terminals A1, A2, A3 and A4 are only fitted when the Counter includes optional alarms. Similarly terminals C1, C2, C3 and C4 are only fitted when the instrument has an optional 4/20mA output. See full manual for details.

A

A

DISPLAY

A

A

Step A Unscrew the four captive 'A' screws and separate the indicator assembly and the back-box.

B

B

Insulated stud for joining cable screens

Earth

B

stud

B

Step B Secure the enclosure back-box to a flat surface with M6 screws through the four 'B' holes. Alternatively use a pipe mounting kit.

Step C Remove the temporary hole plug and install an appropriate IP rated cable gland or conduit fitting. Feed the field wiring through the cable entry.

A

A Step D

Terminate field wiring on the

instrument assembly. Replace

the assembly on the enclosure

back-box and tighten the four

A

A 'A' screws.

Fig 1 BA364G installation procedure

Abbreviated Instruction for
BA364G intrinsically safe two input field mounting Counter

P

E

Issue 3 24th November 2022
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK Tel: +44(0)1462 438301 e-mail: sales@beka.co.uk
web: www.beka.co.uk

122

Optional

84

stainless

25

steel

legend

plate.

120 DISPLAY

90

19

Four M6 clearance holes for

106

surface mounting.

To remove the scale card carefully pull the tab perpendicularly away from the instrument assembly. See Fig 2 for the location of the scale card tab.

Two M20 x 1.5 tapped cable

90

entries. Supplied with an IP66 stopping plug and one

temporary hole plug.

E P

Pulse input A + Add link to energise
pulse input A
Pulse input b + Add link to energise
pulse input b

Optional

A1 +

6 A2

5 4 A3

+

3 A4

Alarm 1 1
2
Alarm 2 RS1
RS2

10

9 4/20mA

8 7

output

P1

C4 P2

C3

+

C2 C1

Optional

+

Power supply

External reset + Pulse output

Scale Card tab

Fig 2 Dimensions and terminal connections
EMC For specified immunity all wiring should be in screened twisted pairs with screens earthed at one point within the safe area.

Hazardous area

Safe area

DISPLAY

RS2 RS1

6 5 4 3 10 9 8 7

+

+

Sensor A

Input A

21 +

Sensor b

Input b

Single channel positive polarity 28V: 93mA Zener barrier
+
Power supply

Remote reset in hazardous
area

Sensor output
Proximity detector Switch contact Open collector

Input A
Link 3 & 4

Voltage pulse

Don't link

Magnetic pick-off

3 & 4

Input b
Link 7 & 8
Don't link 7 & 8

Remote reset in safe area
Single channel positive polarity 28V: 93mA Zener barrier

Fig 3 Typical measurement loop

Scale card
The instrument's units of measurement and tag information are shown above the display on a slide-in scale card. New instruments are fitted with a scale card showing the information specified when the instrument was ordered, if this was not provided a blank scale card will be fitted which can easily be marked on-site. Custom printed scale cards are available from BEKA associates.

Fig 4 Inserting scale card into instrument assembly
To replace the scale card carefully insert it into the slot shown in Fig 2. Force should be applied evenly to both sides of the scale card to prevent it twisting. The card should be inserted until about 2mm of the transparent tab remains protruding.

3.

OPERATION

The BA364G is controlled and configured via four front panel

push buttons. In the display mode i.e. when the instrument

is counting the push button functions are:

) + & Grand total - shows the least significant 8 digits of a 16 digit counter.
) + * Grand total - shows the most significant 8 digits of a 16 digit counter. If buttons are pressed for longer than 10 seconds the grand total will be reset to zero if the grand total reset function clr gtot is enabled.
To reset the grand total to zero from the operating mode press the ) and * buttons for ten seconds until CLr. no is displayed. Using the & or * button change the display to Clr . YE5 and press ) which will reset the grand total and restore the original display.
& + * If the local total reset function clr tot is enabled in the configuration menu, simultaneously pressing the & and * buttons for more than three seconds allows total A, total b or both totals to be selected by operating the & or * button. Operating the ) button will then reset the selected total and clear any stored output pulses.
( + & Shows each for 2 seconds: Firmware and version number Function of instrument: 2chcntr Options fitted: -A Alarms -P Pulse output (always fitted) -c 4/20mA output
( + * Provides direct access to the alarm setpoints when the Counter is fitted with optional alarms and the AC5P setpoints function has been enabled.
( + ) Access to configuration menu

Display DISPLAY mode

( )

)

code

(

0000

Security Code
Enter code by pressing
* or & & (
to move to next digit. Code 0000
allows direct access to the menu

4. CONFIGURATION Counters are supplied configured as requested at time of ordering, if not specified default configuration will be supplied but can easily be changed on-site. Fig 5 shows the location of each function within the configuration menu with a brief summary of the function. Please refer to the full instruction manual for detailed configuration information and for description of optional outputs. Access to the configuration menu is obtained by pressing the ( and ) buttons simultaneously. If the Counter's security code is set to default 0000 the first parameter input-a will be displayed. If the instrument is protected by a security code, code will be displayed. The four digit code must be entered to gain access to the menu.

Unless otherwise specified menu functions are shown on the upper display

Alarms functions appear here

4/20mA output functions appear here

()

&

*
input-a

*

)

)

)

)

)

)

)

)

)

)

)

)

)

** & cntedg-a &

update

* &

count

* &

di5p-1

* &

di5p-2

* &

dP

* &

5cale . t

* &

5cale . r

* &

t-ba5e

* &

filter

* &

up or dn

* &

clr val

* &

Loc clr

*

)

)

)

)

&

pul5e op

* &

clr gtot

* &

code

* &

r5et def

*

()

)

()

()

()

()

()

()

()

()

()

()

()

()

()

)

(

()

()

()

inp . type

* &

debounce

edge1

0 . 5

a : b

total

on

00000000

001 . 00

001 . 00

tb-01

24

up

00000000

clr tot

* &

clr gtot

clr . no

0000

0000

()

()

()

()

()

op . col

default

off

off

0000

Input-A
& or *
to select
Input type
op . col Open Collector
volt5 l Pulse <1V >3V
volt5 h Pulse <3V >10V
coil Magnetic pick-off
pr. det Proximity detector
contact Switch contact

Debounce
& or *
to select
level of debounce.
default heavy light

Counting edge input-A
& or *
to toggle between
edge1 volts rising edge
and
edge2 volts falling edge

Update
& or *
to select interval between display updates, may be set to 0 . 5, 1, 2, 3, 4 or 5 seconds

Count

Upper Display Lower Display

& or *
to select Input type
a : b Input A + Input b
a :-b Input A Input b

& or *
to select display whether total or rate is shown on upper display

& or *
to turn lower display
on or off

a con b
A count direction controlled by b

a rel b
Quadrature counting mode

Decimal point
& or *
to select position of
decimal point and
( to toggle
between rate and total displays

Total scale factor
Dividing factor which defines total display.
& or *
to adjust value
and ( to
move to next digit or decimal point

Rate scale factor
Dividing factor which defines rate display.
& or *
to adjust value
and ( to
move to next digit or decimal point

Timebase
& or *
to select rate display timebase.
tb-01 for pulses/sec
tb-60 for pulses/min

Filter input
& or *
to adjust value of each digit
and ( to
transfer control to the next digit.
First digit: filter magnitude

tb-3600

Second digit:

for pulses/hour step response

Note: While making adjustments
the filtered rate display is
shown on lower display so stability can be assessed

Direction of count
& or *
to toggle between up and dn

Reset value
& or *
to adjust value of each digit
and ( to
transfer control to the next digit

Local total reset
& or *
to turn the local total reset function on or off. When on, total display may be reset when
& and *
are pressed simultaneously for more than 3 seconds in the display mode

Local grand total reset
& or *
to turn the local grand total reset
function on or off. When on, grand total display may be reset when
) and *
are pressed simultaneously for more than 10 seconds in the display mode

Grand total reset press
& or *
to select clr . ye5 to reset grand total to zero.
Confirm instruction by entering 5ure.
Press
& or *
to adjust each
digit and (
to move to next digit

Define Security Code
Enter by pressing
& or * and (
to move to next digit.
Default code 0000 allows direct access to configuration
menu

Reset configuration
to factory defaults
Confirm instruction by entering 5ure.
Press
& or *
to adjust each
digit and (
to move to next digit

)

)

)

)

&

enbl

* &

5ource

* &

divide

*

*

& duration

()

()

()

()

off

5caled

1000

0 .1

* Followed by identical function for input b
Unless otherwise specified menu functions are shown on the upper display

Fig 5 Configuration menu

Manuals and datasheets can be downloaded from http://www.beka.co.uk/ba364g

The BA364G is CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU.
It is also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations
UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations UKSI 2016:1091 (as amended).
Fig 5 Configuration menu

Alarm Enable
* or &
to toggle between on and oFF

Source or Divides scaled output pulse output pulse

Duration of each pulse

* or &
to select pulse source.
5CALEd Input pulse frequency may be divided and duration extended.
OR
dirECt A Retransmission
of input A
OR
dirECt b Retransmission
of input b

* or &
to select frequency dividing factor for scaled output pulse
1 10 100 1000 10000

* or &
to select duration of scaled output pulse in ms
0 . 1 0 . 5
1 2 . 5
5 10 25 50 100 250 500

These functions only appear in sub-menu when 5CALEd is
selected in the 5ourCE function

