Eaton DMM and DCM Switch-Disconnectors
Instruction Leaflet IL008025ZU
Safety Information
Electric current! Danger to life!
Installation, commissioning, and maintenance work must be carried out by qualified personnel only. This warning is provided in multiple languages.
Caution: Use protective covers and/or additional shielding if mounted without an enclosure.
Product Overview
This document provides installation and safety instructions for Eaton's DMM and DCM series switch-disconnectors.
The following models are covered:
- DMM-40, DMM-63, DCM-40, DCM-63
- DMM-80, DMM-100, DMM-125, DMM-160
Electrical Connections
The switch-disconnectors feature main terminals for power input and output, typically labeled L1, L2, L3 for phase connections, and N for neutral. Output terminals are labeled T1, T2, T3.
Connection Specifications:
Model Series | Wire Gauge (mm²) | Torque (Nm) |
---|---|---|
DMM-40, DMM-63, DCM-40, DCM-63 | 1.5 - 25 | 2 |
DMM-40, DMM-63, DCM-40, DCM-63 | 2.5 - 16 | 2 |
DMM-80, DMM-100, DMM-125, DMM-160 | 6 - 70 | 7 |
DMM-80, DMM-100, DMM-125, DMM-160 | 6 - 70 | 7 |
Terminal sizes vary: 14 mm (0.55") for DMM/DCM-40/63 series and 21 mm (0.83") for DMM-80/100/125/160 series.
Mounting holes are approximately Ø6 mm (0.24") for some models and Ø5 mm (0.2") for others.
Installation Procedure (Shaft Set)
The following steps describe the installation of a shaft set (SHAFTSETDCM/DMM):
- Use pliers to adjust the unit.
- Use pliers to connect a component.
- Use a screwdriver to attach a component.
- Attach a part using screws, tightening to 0.5 Nm (4.43 lb-in).
- Attach another part using screws, tightening to 0.5 Nm (4.43 lb-in).
- Attach a part using screws, tightening to 0.8 Nm (7.08 lb-in).
- Attach another part using screws, tightening to 0.8 Nm (7.08 lb-in).
- Attach a part using screws, tightening to 0.8 Nm (7.08 lb-in).
- Attach a part using screws, tightening to 0.8 Nm (7.08 lb-in).
Dimensions and Mounting
Front Mounting: The overall depth for front mounting is 171.7 mm (6.76").
Mounting Quantities:
- DMM-40, DMM-63, DCM-40, DCM-63 require 1 mounting unit.
- DMM-80, DMM-100, DMM-125, DMM-160 require 2 mounting units.
Detailed Dimensions:
Dimensions are provided for DMM/DCM-40/63 and DMM-80/100/125/160 series:
Dimension | DMM-40..., DMM-63..., DCM-40..., DCM-63... (mm / inch) | DMM-80..., DMM-100..., DMM-125..., DMM-160... (mm / inch) |
---|---|---|
a | 72 mm (2.83") | 108 mm (4.25") |
b | 136 mm (5.35") | 157 mm (6.18") |
c | 83 mm (3.27") | 105 mm (4.13") |
d | 22 mm (0.87") | 27 mm (1.06") |
e | 50.5 mm (1.99") | 81 mm (3.19") |
f | 20 mm (0.79") | 15.5 mm (0.61") |
g | 30 mm (1.18") | 27 mm (1.06") |
h | 92 mm (3.62") | 77 mm (3.03") |