Instruction Manual for PHILIPS models including: EM164C, EM164C Emergency Twin Spot, Emergency Twin Spot, Twin Spot, Spot

EM164C HO BKD 15S UI

EM164C SM TWIN SPOT

prieš 1 dieną — trician and wired in accordance with the latest IEE electrical regulations or the national requirements. When the light source reaches its end of life.

EM164C HO BKD 15S UI

PDF preview unavailable. Download the PDF instead.

Mounting Instruction EM164C
P1

Emergency Twin Spot
EM164C SM TWIN SPOT

indoor 220V 50Hz 240V 60Hz

GLOW

Max.

LEDs IP65 WIRE
850 °C

45 °C Min. 0 °C

EM164C SM TWIN SPOT NM3 ELB IP65

Test auto

CCT (K) 6500

Lumen

kg

(lm)

P (W)

1000

8

1.45

Dimensions in mm

287.5 190

300 68.5

Inrush current
I mains (A) I max max/2
Tref

I nom. Time (us)

Electrical characteristics

Inom (mA) Imax (A) Tref (µs)

0.059 6.7 3.2

MCB

Luminaires Max.

B-10 A

118

B-13 A

154

B-16 A

189

C-10 A

118

C-13 A

154

C-16 A

189

!
ATTENTION
OBSERVE PRECAUTIONS FOR HANDLING
ELECTROSTATIC SENSITIVE DEVICES

-

-

trician and wired in accordance with the latest IEE

electrical regulations or the national requirements.

- When the light source reaches its end of life

the whole luminaire shall be replaced.

- Clean with dry cloth.

- Philips Lighting warranty is applicable only if the

indicated drivers are used.

912401483513 (EM164C SM TWIN SPOT NM3 ELB IP65) ©

1/5

Printed in China Data subject to change without notice Keep for future reference: www.lighting.philips.com

ALWAYS SWITCH OFF THE MAINS SUPPLY BEFORE
INSTALLATION OR SERVICING

225

1

2

67.5 135

x4 x4

x4
x1
3

4
2/5

L E
N

x4 Connect battery to converter

Unswitched Line

28 9 2x1.0_1.5mm2 max.

4-8mm

For continuity of termination of CPC

L Brown

5

N Blue

6

Unswitched Neutral

L EN

Brown Blue

SWITCH ON THE MAINS SUPPLY AFTER
INSTALLATION OR SERVICING

7
Battery replacement LiFePO4 -26650-6600mAh-6.4V

Torque values 1.52NM
8
Luminous Intensity Distribution

Disconnect battery to converter

Remove the battery

Replace the battery

Connect battery to converter

Spacing Data (1 lux)
Mounting Height (m)

2.50 3.00 3.50 4.00

5.78 6.70 7.15 7.55

13.60 15.81 16.96 17.99

13.69 15.89 16.98 17.95

13.43 15.57 16.59 17.49

5.51 6.38 6.78 7.13

3/5

1. For indoor use only. 2. The luminaire complies with IEC60598-1IEC 60598-2-22.
The luminaire must be installed by a qualified electrician and wired in accordance with the latest IEE Electrical regulations or the national requirements. 3. Turn off the power supply before checking, installation, maintenance or moving. 4. Do not switch on before complete installation. 5. Batteries shall only be replaced by the manufacturer or his service agent or a similar qualified person. 6. Batteries should be replaced when the luminaire no longer meets the 3 hours duration performance. 7. Product mains surge immunity is 0.5/1KV (diff. / comm. mode). To prevent excessive currents and voltages from damaging the device, make sure that the power supply input is equipped with additional protection devices such as surge protectors. For any questions regarding the product's surge protection, please consult the manufacturer's professional.

Please inform yourself about the local waste disposal, separation and collection system for electrical and electronic products and packaging. Please act according to your local rules and do not dispose your old product and packaging with your normal household waste. The correct disposal of the packaging, your product and/or batteries will help prevent potential negative consequences for the environment and human health.Batteries should be disposed separately from the municipal waste stream via designated collection facilities.When disposing a product that contains non-user replaceable batteries, the non-user replaceable batteries shall be removed by a professional.

Testing Record

Product: Month

Functional/Duration

1

2

3

4

5

6

7

8

9

10

11

12

Location: Year 1

Year 2

4/5

Installation Date:

Year 3

Year 4

Year 5

Emergency Twin Spot
Speci cations For Self Test
Function Test The function test is conducted every month for 3 minutes to check whether the battery connection is abnormal and discharge the battery. Duration Test An initial duration test is conducted when the battery is connected to the controller for the first time and connected to mains, but after 24 hours charging. The yearly duration test is conducted for 3 hours on one day within the 300th day to the 365th day every year. It will also check the connection of battery.

Description corresponding to the color and status of the charge indicator

Charge Indicator
Color

Status Permanent on

On Time (Seconds)
/

O Time (Seconds)
/

Green

Slow flash Fast flash

1s

1s

0.2s

0.2s

Normal flash

three times only

0.5s

0.5s

Description
Normal status when mains connected Duration test running Function test running Time reset

Red Both Off

Permanent on

/

Slow flash

1s

Fast flash

0.2s

Off

/

/ 1s 0.2s /

Battery connection is abnormal or failure Lamp connection is abnormal or failure Duration failure - the capacity of the battery is insufficient Emergency mode

It should be taken to check connectivity or replace the abnormal battery or lamp.

Test button for manual inspection on function test or duration test mode of operation

Duration

Description

Press for <2s Press for 3-5s Press for 5-8s

Simulate emergency mode.
Start duration test manually. The test can be aborted by pressing off (1-2s). * Must be conducted when the initial duration test finished and after another 24 hours battery charging. Start Function test manually for 60s. The test can be aborted by pressing off (1-2s).

Press for >10s Time Reset.

Note: When the mains is on, the green indicator will be permanently on. It will check the connection of battery and LED module. When the mains is off, no test will perform.
The luminaires whick perform the function and duration tests must be connected to the mains supply for at least uninterrupted 24 hours. If the mains is off during these tests, the tests will be postponed for 3 days.
When the fault is corrected, the indicator will only be reset to its normal status after mains reconnected or test switch pressed.
An accuracy of the timing of the test interval is ensured that it has an accuracy of ±75 s per week. The timing function will be retained through periods of mains supply failure or interruption for up to 7 days.
5/5

