Installation Guide for MASTERVOLT models including: 131906000 Battery Solar Charge Regulator, 131906000, Battery Solar Charge Regulator, Solar Charge Regulator, Charge Regulator
4 | Mastervolt - Innovative power systems for autonomous use.
SCM60 MPPT-MB | Mastervolt .
File Info : application/pdf, 24 Pages, 1.11MB
DocumentDocumentSOLAR CHARGEMASTER 60 MPPT BATTERY SOLAR CHARGE REGULATOR USER AND INSTALLATION MANUAL EN For the latest version of this manual, visit our website: NL Ga om deze handleiding in andere talen te downloaden naar onze website: DE Um diese Anleitung in anderen Sprachen herunterzuladen, besuchen Sie bitte unsere Website: FR Pour télécharger ce manuel dans d'autres langues, consultez notre site Web : ES Para descargar este manual en otros idiomas, visite nuestro sitio web: IT Per scaricare questo manuale in altre lingue, visitare la pagina del prodotto sul nostro sito Web: www.mastervolt.com 2 Solar ChargeMaster 60 MPPT User and Installation Manual OVERVIEW 1. Power On / Charge indicator LED (Section 2.6) 2. Fault indicator LED (Section 2.6) 3. Wiring fault indicator LED (Section 2.6) 4. Menu switch (Section 2.5) 5. LCD-display (Section 2.6) 6. Service port (do not use, for factory use only) 7. MasterBus ports (Section 3.6) 8. Temperature sensor jack (Section 3.6) 9. Grounding terminal (Section 3.6) 10. Battery voltage sense (Section 3.6) 11. Strain relief bracket (Section 3.6) 12. Solar input (Section 3.6) 13. Battery output (Section 3.6) 14. Terminal cover (Section 3.6) 15. Identification label (Section 1.4) Figure 1: Overview Solar ChargeMaster 60 MPPT User and Installation Manual 3 TABLE OF CONTENTS 1 GENERAL INFORMATION ................................................................................................................................................... 4 1.1 Use of this manual ......................................................................................................................................................... 4 1.2 Validity of this manual.................................................................................................................................................... 4 1.3 Use of pictograms.......................................................................................................................................................... 4 1.4 Identification label .......................................................................................................................................................... 4 1.5 Liability........................................................................................................................................................................... 4 2 OPERATION.......................................................................................................................................................................... 5 2.1 General.......................................................................................................................................................................... 5 2.2 Maintenance .................................................................................................................................................................. 5 2.3 Three Step charge algorithm ......................................................................................................................................... 5 2.4 Overview........................................................................................................................................................................ 6 2.5 MENU switch ................................................................................................................................................................. 6 2.6 LEDs and LCD display................................................................................................................................................... 7 3 INSTALLATION..................................................................................................................................................................... 8 3.1 Unpacking...................................................................................................................................................................... 8 3.2 Environment .................................................................................................................................................................. 8 3.3 Wiring and fuses ............................................................................................................................................................ 8 3.3.1 Battery output ..................................................................................................................................................... 8 3.3.2 Voltage sense (optional)..................................................................................................................................... 9 3.4 PV-array ........................................................................................................................................................................ 9 3.4.1 External DC Switch ............................................................................................................................................ 9 3.4.2 Specifications of the PV-array ............................................................................................................................ 9 3.5 Things you need .......................................................................................................................................................... 11 3.6 Connection .................................................................................................................................................................. 11 3.6.1 General ............................................................................................................................................................ 11 3.6.2 Installation step by step .................................................................................................................................... 12 3.7 Commissioning after installation .................................................................................................................................. 14 3.8 Decommissioning ........................................................................................................................................................ 14 3.9 Storage and transportation .......................................................................................................................................... 14 3.10 Re-installation .............................................................................................................................................................. 14 4 SETTINGS ........................................................................................................................................................................... 15 4.1 Configuration menu ..................................................................................................................................................... 15 4.1.1 Readout of software version............................................................................................................................. 15 4.1.2 Battery type and output current ........................................................................................................................ 15 4.2 MasterBus functions .................................................................................................................................................... 16 4.2.1 Monitoring......................................................................................................................................................... 16 4.2.2 Alarm ................................................................................................................................................................ 16 4.2.3 History .............................................................................................................................................................. 16 4.2.4 Configuration .................................................................................................................................................... 17 4.2.5 Events .............................................................................................................................................................. 18 4.2.6 List of events sources (Solar ChargeMaster as event source) ......................................................................... 18 4.2.7 List of event commands (Solar ChargeMaster as event target)........................................................................ 18 4.3 Use in combination with Mastervolt MLI battery .......................................................................................................... 18 5 TROUBLE SHOOTING........................................................................................................................................................ 20 6 TECHNICAL DATA ............................................................................................................................................................. 21 6.1 Specifications .............................................................................................................................................................. 21 6.2 Dimensions.................................................................................................................................................................. 22 4 Solar ChargeMaster 60 MPPT User and Installation Manual 1 GENERAL INFORMATION 1.1 USE OF THIS MANUAL This manual serves as a guideline for the safe and effective operation, maintenance and possible correction of minor malfunctions of the Solar ChargeMaster 60 MPPT. It is therefore obligatory that every person who works on or with the Solar ChargeMaster must be completely familiar with the contents of this manual and the Important Safety Instructions, and that he/she carefully follows the instructions contained herein. Installation of, and work on the Solar ChargeMaster 60 MPPT may be carried out only by qualified, authorised and trained personnel, consistent with the locally applicable standards and taking into consideration the Important Safety Instructions. 1.2 VALIDITY OF THIS MANUAL All specifications, provisions and instructions contained in this manual apply solely to standard versions of the Solar ChargeMaster delivered by Navico Group. This manual is only valid for the following model: Part number Model 131906000 Solar ChargeMaster 60 MPPT This model is further referred to as "Solar ChargeMaster". 1.3 USE OF PICTOGRAMS Safety instructions and warnings are marked in this manual and on the product by the following pictograms: CAUTION! Special information, commands and prohibitions in order to prevent damage. WARNING A WARNING refers to possible injury to the user or installer or significant material damage to the Solar ChargeMaster if the installer / user does not (carefully) follow the stated procedures. Read this manual before installation and use. 1.4 IDENTIFICATION LABEL Part number Serial number EO20A0678 Apparatus version "A" CAUTION! Never remove the identification label. Figure 2: Identification label The identification label is located at the right-hand side of the Solar ChargeMaster (see Figure 1). Important technical information required for service, maintenance & secondary delivery of parts can be derived from the identification label. 1.5 LIABILITY Mastervolt is a brand of Navico Group. Navico Group cannot be held liable for: · consequential damage due to use of the Solar ChargeMaster; · possible errors in the manuals and the results thereof. Solar ChargeMaster 60 MPPT User and Installation Manual 5 2 OPERATION 2.1 GENERAL The Mastervolt Solar ChargeMaster is a fully automatic battery charger which converts power from photovoltaic (PV) array to a regulated battery voltage. The PV-array connected to the Solar ChargeMaster is operated at its optimum voltage to obtain an optimal yield (Maximum Power Point Tracking). The Solar ChargeMaster can automatically adjust itself to a 12V, 24V or a 48V system. The 36V option must be selected manually. Under normal circumstances the Solar ChargeMaster remains switched on with the PV-array and batteries connected. If power from the PV-array is sufficient, the Solar ChargeMaster will initiate the charging process. WARNING The Solar ChargeMaster has no on/off switch. Charging will be initiated as soon as power from the PV-array becomes available. As long as there is MasterBus communication, the Solar ChargeMaster will consume power from the connected battery bank. The Solar ChargeMaster is protected against overload, short circuit, overheating and under and over voltage. CAUTION! The Solar ChargeMaster is not protected against: · Excessive overvoltage on the Solar input · Surges inducted by lightning. 2.2 MAINTENANCE No specific maintenance to the Solar ChargeMaster is required. Examine your electrical installation on a regular base, at least once a year. Defects such as loose connections, damaged wiring etc. must be corrected immediately. If necessary, use a soft, clean cloth to clean the casing of the Solar ChargeMaster. Do not use any liquids or corrosive substances, such as solvents, alcohol, petrol or abrasive components. Note: In the event of decommissioning, refer to section 3.8. 2.3 THREE STEP CHARGE ALGORITHM See Figure 3. Battery charging is accomplished in three automatic stages: BULK, ABSORPTION and FLOAT. BATTERY VOLTAGE BULK ABSORPTION FLOAT CHARGE CURRENT TIME · BULK: At this stage the charger delivers its maximum current for quick charging from 0 to 80% · ABSORPTION: The charger has reached its maximum charge voltage and the charge current will slowly decrease until the battery is charged up to 100%. · FLOAT: This stage begins once the battery is fully charged. The battery remains in fully charged state. Figure 3: Three step charge system By installing the battery temperature sensor, the charge voltages are automatically adapted for deviating temperatures. 12V 15 For a 24V system, double the voltage. For a 36V system, triple the voltage. 14 For a 48V system, quadruple the voltage. Charge voltage (V) 13 12 11 -30 -20 -10 0 10 20 30 40 50 60 See Figure 4. When the battery temperature is low, the charge voltage increases. On the other hand, when the battery temperature is high, the charge voltage is decreased. Over charge and gassing are prevented this way. This will extend the life of your batteries. Battery temperature (°C) Figure 4: Temperature compensated charging 6 Solar ChargeMaster 60 MPPT User and Installation Manual 2.4 OVERVIEW BATTERY CAPACITY Estimation of the battery state of charge; WIRING FAULT Highlighted in case of error in the wiring; INPUT Actual solar input voltage (Volts) BATTERY VOLTAGE Actual battery voltage (Volts) LCD Display See section 2.6 BATTERY TYPE Battery type setting; see section 4.1.2 or 4.2.4 ERROR An error code is displayed in case of a fault condition; see section 2.6 POWER Actual charging power (Watt) CHARGING CURRENT Actual output current of the Battery Output (Amps) Power On / Charge indicator LED The batteries are being charged; see section 2.6 MENU switch See section 2.5 Fault indicator LED A fault condition is detected; see section 2.6 Wiring fault indicator LED A wiring fault is detected; see section 2.6 Figure 5: operation of the Solar ChargeMaster 2.5 MENU SWITCH MENU switch operation Press shortly 1 second >5 seconds Meaning Activate LCD-display Switch on Solar ChargeMaster again after a fault or error situation Configuration menu, see section 4.1 Solar ChargeMaster 60 MPPT User and Installation Manual 7 2.6 LEDS AND LCD DISPLAY LED indication LCD indication Meaning Green flashing (Off) (Off) -- Green solid on (Off) (Off) (Off) (Off) -(Off) -- (Off) (Off) (Off) -- -- (Off) -- 20 21 22 23 24 25 -- Red -- 01 + ERROR flashing 02 + ERROR 03 + ERROR 04 + ERROR 05 + ERROR 06 + ERROR 07 + ERROR 08 + ERROR Red solid on Normal operation, batteries are being charged. (every 0.5 second): Bulk charge stage (every second): Absorption charge stage (every 5 seconds):Float charge stage The Solar ChargeMaster is in Standby mode. This can be due to a MasterBus controlled command; see section 4.2. If used in combination with Mastervolt MLI battery: Stop charge event was triggered. Irradiation on the PV modules is insufficient (for instance during nighttime). The Solar ChargeMaster is in Standby mode to reduce power drain from the batteries. The display can be activated temporally by pressing the MENU switch shortly. The display will be deactivated automatically after 1 minute. No power from the PV-modules. Check wiring to PV-modules if the Solar ChargeMaster is switched off during daytime. Check for loose connections or incorrect polarity. Power on the Solar input is too low, irradiation on the PV modules is insufficient. This is a normal situation during sunrise and sunset. Pre-warning for too high voltage (>130V) on the Solar input. Output power de-rating due to too high internal temperature (>80°C/176°F) of the Solar ChargeMaster. Check cooling. See also section 3.2. Battery temperature low. Check batteries & battery temperature sensor. Battery temperature too high. Check batteries & battery temperature sensor. Battery sensor is short-circuited. Charge current is too high due to over-current/power situation on the Solar input. Check PV-array. Internal temperature of the Solar ChargeMaster is too high. Check cooling. See also section 3.2 Battery voltage too low (see section 6.1). Check batteries. Reduce load connected to the batteries and charge batteries. Battery voltage too high (>15V@12V / >30V@24V / >45V@36V / >60V@48V). Check batteries, check output voltage of other charging devices. Voltage from PV-modules is too high (>140V). Check PV-array. Battery temperature too low (<0°C/32°F). Check batteries, check battery temperature sensor. Battery temperature too high (>50°C/122°F). Check batteries, check battery temperature sensor. Battery voltage sense error: Difference between voltage measured at battery output and battery voltage sense function is too high. Check battery voltage sense wiring (section 3.3.2) Reversed polarity on the Battery connection. Check battery wiring. 8 Solar ChargeMaster 60 MPPT User and Installation Manual 3 INSTALLATION During installation commissioning and maintenance of the Solar ChargeMaster, the Important Safety Instructions are applicable at all times. 3.1 UNPACKING The delivery includes the following items: · Solar ChargeMaster; · Mounting bracket; · Strain relief bracket; · Battery temperature sensor; · MasterBus terminator; · Battery voltage sense connector (pre-assembled); · Important Safety Instructions; · This user manual. After unpacking, check the contents for possible damage. Do not use the product if it is damaged. If in doubt, contact your supplier. 3.2 ENVIRONMENT Obey the following stipulations during installation: · The Solar ChargeMaster is designed for indoor use only. It is suited for use in Marine, Mobile and stationary applications. · Ambient operating temperature: -20°C ... 55°C / -4°F ... 131°F (power de-rating above 40°C / 104°F to decrease the internal temperature). · Humidity: 5-95%, non-condensing. · The Solar ChargeMaster must be mounted to a vertical, solid and heat-resistant surface, with the connecting cables downwards. · Do not expose the Solar ChargeMaster to excessive dust, aggressive environments, ammonia or salt. · Make sure that the hot air that is developed during operation can be discharged. The Solar ChargeMaster must be mounted in such a way that obstruction of the airflow along the heatsink on the backside of the casing will be prevented. · No objects must be located within a distance of 20 cm / 8 inch to the side and 50 cm / 20 inch above and below the Solar ChargeMaster. · Do not locate the Solar ChargeMaster in the same compartment as the batteries. · Do not install the Solar ChargeMaster straight above the batteries because of possible corrosive sulphur fumes. · Although the Solar ChargeMaster fully complies with all applicable EMC limits, it may still cause harmful interference to radio communication equipment. If such interference appears, it is recommended to increase the separation between the Solar ChargeMaster and the equipment, to relocate the receiving antenna or to connect the equipment to a circuit different from that to which the Solar ChargeMaster is connected. 3.3 WIRING AND FUSES 3.3.1 Battery output WARNING The wire and fuse sizes stated in this manual are given as example only. Prescribed wire and fuse sizes may be different due to local applicable regulations and standards. Keep in mind that high current will pass through the DC wiring. Keep the cable length as short as possible, this will keep the system efficiency as high as possible. The recommended minimum cross sections of the wiring are: Connection Battery Minimum DC Cable cross section <3m / 10ft length 3 - 5m / 10 - 16ft 25mm² / AWG4 35mm² / AWG2 Use boot lace ferrules on the wire ends. These ferrules must be crimped with a proper crimping tool. Use the following wire colors for DC wiring: Wire color Red Black Meaning Positive Negative Connect to: + (POS) (NEG) Lay the positive and negative cables next to each other to limit the electromagnetic field around the cables. The negative battery cable should be connected directly to the negative post of the battery bank or the ground side of a current shunt. Do not use the chassis frame as the negative conductor. Tighten securely. The positive battery cable must be fused and connected to the positive post of the battery bank. The recommended DC fuse is: Connection Battery fuse DC fuse 80A Solar ChargeMaster 60 MPPT User and Installation Manual 9 3.3.2 Voltage sense (optional) To compensate the charge voltage of the Solar ChargeMaster for losses over the battery cables the voltage sense function can be used. Connect wiring as indicated in Figure 6. Recommended cable cross section and DC fuse: Connection Minimum DC Cable cross section DC-fuse Voltage sense 0.75mm² / AWG18 3A Note: Do not connect the voltage sense wiring if the Shunt device function is enabled (section 4.2.4) 3.4 PV-ARRAY 3.4.1 External DC Switch WARNING When the PV-array is exposed to light, it supplies a DC voltage to the Solar ChargeMaster which can be dangerous to touch. For this reason, use of an external DC-switch to disconnect the PV-modules from the Solar ChargeMaster is strongly recommended and can even be mandatory. For example, international standard IEC60364-7-712 prescribes a DC switch in solar electric installations in buildings Please acquaint yourself with locally applicable regulations and standards on this aspect. Alternatively, before attempting any maintenance or cleaning the PV-array should be protected from light exposure, e.g. by covering the PV modules. 3.4.2 Specifications of the PV-array CAUTION! Do not connect Solar ChargeMasters in parallel on the PV-array side. The Solar ChargeMaster can be used with any PV-array configuration that satisfies the following requirements: · Maximum open circuit PV voltage: 145 V DC; · The MPP voltage from the PV-array must be at least 5Volts higher than the battery voltage. Configuration examples for PV-arrays consisting of monocrystalline or polycrystalline PV-modules: Battery voltage UNOM = 12V Panel type # in series # in parallel* 36 cells 1 5 or 6** Max. 900Wp 60 cells 1 3 Max. 900Wp 72 cells 1 2 or 3** Max. 900Wp Battery voltage UNOM = 36V Panel type # in series # in parallel* 36 cells 3 5 or 6** Max. 2700Wp 60 cells 2 3 Max. 2700Wp 72 cells 2 3** Max. 2700Wp Battery voltage UNOM = 24V Panel type # in series # in parallel* 36 cells 2 5 or 6** Max. 1800Wp 60 cells 1 3 Max. 1800Wp 72 cells 1 2 or 3** Max. 1800Wp Battery voltage UNOM = 48V Panel type # in series # in parallel* 36 cells 3 5 or 6** Max. 3600Wp 60 cells 2 3 Max. 3600Wp 72 cells 2 3** Max. 3600Wp * If more than two PV-strings are connected in parallel, string fuses must be integrated in both the positive and negative legs of the string cabling. Fuse ratings should be chosen 50 % higher than the MPP current of the PV modules used. ** See the following caution. CAUTION! Never connect voltages higher than specified to the PV-input, as this will cause permanent damage to the Solar ChargeMaster. Always verify the maximum open circuit PV voltage at lowest possible temperature in which the PV-array will be used! Note: The Solar ChargeMaster will automatically limit the input current and power to its specified rating (see section 6.1). Excess power will not be converted. In case of high risk of lightning strikes, installation of external Surge Protection Devices (SPD) is recommended. 10 Solar ChargeMaster 60 MPPT User and Installation Manual Do not use this port MasterBus ports PV-array Load External DC-switch (see section 3.4) A: Voltage sense fuse Note that voltage sense is optional. B: Battery fuse C: Load fuse Battery switch A B C Battery temperature sensor BATTERY Figure 6: Wiring diagram Above schematic is to illustrate the general placement of the Solar ChargeMaster in a circuit. It is not meant to provide detailed wiring instructions for any particular electrical installation. 11 Solar ChargeMaster 60 MPPT User and Installation Manual 3.5 THINGS YOU NEED Make sure you have all the parts you need to install the Solar ChargeMaster: · Solar ChargeMaster (included); · Battery temperature sensor with cable and plug (included); · DC cables to connect the Solar ChargeMaster; see section 3.3.1 for specifications; · DC-fuse holder with a DC-fuse, to be integrated in the positive DC-cable to the battery; see section 3.3.1; · Option: Wiring, fuse and fuse holder for voltage sense connection; see section 3.3.1; · Screws / bolts (Ø 4mm max.) (with plugs) to mount the Solar ChargeMaster to a surface; · DC-switch to disconnect the PV-modules from the Solar ChargeMaster, see section 3.4.1; · PV-panels; see section 3.4.2; · Batteries; · Battery switch; · Appropriate and reliable cable terminals, strain reliefs, battery terminals and boot lace ferrules. We recommend as a minimum tool kit: · Isolated Phillips screwdriver nr.2 or flat blade screwdriver 5 mm to fix the DC-cables; · Tools to fix the screws / bolts with plugs to mount the Solar ChargeMaster to a surface. 3.6 CONNECTION 3.6.1 Note: General WARNING Let installation work be done by a licensed electrician. All electrical systems must be disconnected from any power source during the entire installation! CAUTION! · Short circuiting or reversing DC polarity may lead to damage to the Solar ChargeMaster, the cabling and/or the terminal connections. · Follow all steps of the installation instructions in order of succession as described. CAUTION! Too-thin cables and/or loose connections can cause dangerous overheating of the cables and/or terminals. Therefore, tighten all connections well, in order to limit transition resistance as far as possible. Use cables of the correct size. Use additional strain reliefs to prevent the transmission of stress to the screw connectors. CAUTION! The negative connections of the Solar ChargeMaster are common and therefore have the same electrical potential. If grounding is required, always do this on the negative wires. Use one grounding point only. Minimum wire cross section for grounding: 10mm² / AWG8. If the battery temperature remains within 15-25°C, connection of the battery temperature sensor is optional. Do not connect the battery temperature sensor to the Temperature sensor jack (Figure 1, item 8) if Battery Type is set to Lithium or if the Shunt device function is enabled, see section 4.2.4 12 Solar ChargeMaster 60 MPPT User and Installation Manual 3.6.2 Installation step by step 1 Fix the strain relief bracket to the casing of the Solar ChargeMaster. 4 Fix the enclosure to the wall by fastening the other screws as well. Figure 7 2 Mark the position of the mounting spots by using the mounting bracket. Then fix the mounting bracket to the wall. Figure 8 3 Place the Solar ChargeMaster over the mounting bracket and then move it downwards until it is suspended from the mounting bracket. Figure 10 5 If grounding is required, connect the grounding terminal to the central grounding point of the electrical installation; see Figure 1, item 10. See also section 3.6.1 Figure 11 6 Take off the terminal cover by releasing the screw. Figure 9 Figure 12 13 Solar ChargeMaster 60 MPPT User and Installation Manual 7 Connect the wiring to the battery. See figure 6. Fix the wires to the strain relief by means of tie-wraps. Integrate a fuse holder in the positive battery wire, but do not place the fuse yet. WARNING Risk of shock! When the PV-array is exposed to light, it supplies a dangerous DC voltage. See section 3.4.1. 10 Connect the PV-array Figure 13 8 If required, connect the battery voltage sense wires. Integrate a fuse holder in the positive battery wire, but do not place the fuse yet. 11 Close the terminal cover. Figure 16 Figure 14 9 Attach the battery temperature sensor to the casing of the battery. Plug the temperature sensor cable into the Temperature sensor jack (Figure 1, item 8). Figure 17 12 Option: Connect the Solar ChargeMaster to the MasterBus network. Figure 15 Figure 18 13 Check all wiring: positive to +, negative to . See also Figure 6 for wiring example. Continue with section 1.1 for commissioning of the Solar ChargeMaster. 14 Solar ChargeMaster 60 MPPT User and Installation Manual 3.7 COMMISSIONING AFTER INSTALLATION CAUTION! Check the polarity of all wiring before commissioning: positive connected to positive (red cables), negative connected to negative (black cables). 1 If all wiring is OK, place the DC-fuse in the Battery voltage sense wiring. 2 Place the DC-fuse between the Battery output of Solar ChargeMaster and the battery. Move the battery switch in the "ON" position. WARNING When placing this fuse, a spark can occur, caused by the capacitors used in the Solar ChargeMaster. This is particularly dangerous in places with insufficient ventilation, due to the gassing of the batteries an explosion can occur. Avoid having flammable materials close by. 3 The Solar ChargeMaster will initiate the charging process if the voltage from the PV-array is 5VDC higher than the battery voltage; see chapter 2. Note: If the Solar ChargeMaster does not switch on, press the MENU switch for 1 second. 4 Continue with chapter 4 for settings. CAUTION! If the system voltage is still set to automatic detection (Auto), and the batteries are discharged to the point that the voltage is below the system threshold, the Solar ChargeMaster will assume that the complete system changed to a lower voltage. The result might be that the batteries do not reach their full capacity. To prevent this, select the required system voltage from a display like the EasyView 5, or from a PC with MasterAdjust. 3.8 DECOMMISSIONING To put the Solar ChargeMaster out of operation, follow these instructions in order of succession: 1 Switch off all loads that are connected to the Solar ChargeMaster; 2 Disconnect the PV-array by switching off the switch between the PV-array and the Solar ChargeMaster (or protect the PV- array from light exposure, e.g. by covering the PV modules); 3 Move the battery switch in the "OFF" position and remove the DC-fuse between the Solar ChargeMaster and the battery; 4 Check with a suitable voltage meter whether the Battery connection of the Solar ChargeMaster is voltage free; 5 Disconnect the negative cable to the PV-array from the terminal block of the Solar ChargeMaster. Isolate the core of the wire with insulating tape; 6 Do the same for the positive cable to the PV-array; 7 Disconnect all other remaining wiring. Now the Solar ChargeMaster can be demounted in a safe way. 3.9 STORAGE AND TRANSPORTATION When not installed, store the Solar ChargeMaster in the original packing, in a dry and dust free environment. Always use the original packing for transportation. Contact your local Mastervolt Service Centre for further details if you want to return the apparatus for repair. 3.10 RE-INSTALLATION To reinstall the Solar ChargeMaster, follow the instructions as described in this chapter (chapter 3). 15 Solar ChargeMaster 60 MPPT User and Installation Manual 4 SETTINGS Adjustment of the settings of the Solar ChargeMaster can be made in two different ways: · By means of the Configuration menu; see section 4.1; · Via the MasterBus network; see section 4.2. Some settings can only be changed in this way. WARNING The MLI charging voltages on this charger fit the Mastervolt Li-ion (MLI) batteries but do not necessarily fit other Li-ion batteries! See also section 4.3. Always follow the instructions provided by the battery manufacturer! CAUTION! Invalid settings of the Solar ChargeMaster can cause serious damage to your batteries and/or the connected load! Adjustments of settings may be undertaken by authorized personnel only. Note: If your Solar ChargeMaster is not new, you have to take into account that former users may have changed the settings. 4.1 CONFIGURATION MENU 4.1.1 Readout of software version To check the version of the installed software: · Hold the MENU switch (Figure 1) pressed until the Battery type indication starts blinking; · The version of the installed software is shown at the right upper side of the display (Figure 19); · After 10 seconds the Solar ChargeMaster returns to the normal operation mode. Software version Figure 19: Software version 4.1.2 Battery type and output current To change the setting for Battery type or maximum output current: · Hold the MENU switch (Figure 1) pressed until the setting for Battery type ("b1", "b2", "b3", etcetera) is shown; · Press the MENU switch shortly to toggle between configuration modes: Battery type ("b") or Maximum output current ("C"). · Hold the MENU switch pressed to until the selected configuration mode starts blinking. · Press the MENU switch shortly to scroll through the settings as shown in below table. · Hold the MENU switch pressed until the preferred setting stops blinking to confirm the desired setting. When the MENU switch is not touched for 10 seconds, the Solar ChargeMaster returns to the normal operation mode without changing a setting. Indication Battery type / voltage Indication Maximum output current b1 Flooded C1 10A b2 Float voltage 13.6V* C2 20A b3 AGM / Gel (float voltage 13.8V)* C3 30A b4 Flooded traction C4 40A b5 Mastervolt MLI (see section 4.3) C5 50A b6 User defined (see section 4.2.4) C6 60A * For a 24V system, double the voltages. For a 36V system, triple the voltages. For a 48V system, quadruple the voltages. Figure 20: Battery type and output current 16 Solar ChargeMaster 60 MPPT User and Installation Manual 4.2 MASTERBUS FUNCTIONS Adjustment of the settings of the ChargeMaster can be made via the MasterBus network (by means of a remote control panel like the EasyView 5, or a Mastervolt USB interface connected to a PC with MasterAdjust software). Note: Refer to the user manual of the MasterBus remote control panel for more information about MasterBus. 4.2.1 Monitoring Value General Device state Charge state Solar voltage Charge current Battery voltage Battery temp. Total energy Charger temp. On/Off Shunt State Meaning Shows the actual operation mode of the Solar ChargeMaster (Charging / Standby / Alarm/Off) Actual state of charge algorithm: Bulk / Absorption / Float / Off Voltage at the Solar input Output current of the Battery output Voltage measured at the Battery output. If the voltage sense wires are connected: voltage measured at the Battery voltage sense input. If the Shunt device function is enabled for a MasterShunt (MSH) or an MLI Ultra (BAT) (section 4.2.4): voltage measured by the MasterShunt / MLI Ultra. Actual battery temperature measured by the Battery temperature sensor. If the Shunt device function is enabled for a MasterShunt (MSH): Battery temperature measured by the MasterShunt. "---" is shown if no battery temperature sensor is used or when Battery Type is set to "MLI". Total amount of energy (kWh) converted by the Solar ChargeMaster (measured at the Battery output) Temperature of the Solar ChargeMaster Button to toggle the Device state. NOTE: If the Solar ChargeMaster was switched off by means of this button, it will switch on again the next day (after sunset and sunrise). Shows whether a current measuring shunt is connected or not. See configuration for settings Default On Not selected, Connected Adjustable range (read only) (read only) (read only) (read only) (read only) (read only) (read only) (read only) On/Off (read only) (read only) 4.2.2 Alarm Value Over current Solar volt. high Battery low Battery high Battery temp. Charger temp. Temp sense error Shunt mismatch Hardware error Meaning Load connected to the Battery output is too high Input voltage at the Solar input is too high Battery voltage is too low (see section 6.1) Battery voltage is too high (see section 6.1) Battery temperature is out of range <0°C/32°F or >50°C/122°F Internal temperature of the Solar ChargeMaster is too high Battery temperature sensor is in short circuit Setting for nominal voltage (12, 24, 36 or 48V) at the MasterShunt or the nominal voltage of the MLI Ultra battery differs from nominal voltage detected by the Solar ChargeMaster. Check battery voltage and settings of the MasterShunt or voltage of the MLI Ultra battery. Internal hardware error. Contact Navico Group. Adjustable range (read only) (read only) (read only) (read only) (read only) (read only) (read only) (read only) 4.2.3 History This menu shows the historical data of the Solar ChargeMaster. Value Meaning Solar Total energy Total amount of energy (kWh) converted by the Solar ChargeMaster (measured at the Battery output) Adjustable. range (read only) 17 Solar ChargeMaster 60 MPPT User and Installation Manual 4.2.4 Configuration Below parameters can be changed via the MasterBus network by means of a remote control panel or by means of an interface connected to a PC with MasterAdjust software. See applicable user manuals for details. Value Device Language Name Lock config Factory settings Charger Max Charge curr. Battery type Absorption Float Max. absorp. time System voltage Meaning Factory setting Adjustable. range Language that is displayed on a monitoring device connected to the MasterBus Name of this device. This name will be recognized by all devices connected to the MasterBus Option to lock the configuration (requires installer rights) Button to reset the Solar ChargeMaster to default settings (requires installer rights) English SCM [serial number]* EN, NL, DE, FR, ES, IT, NO, SV, FI, DA 0-12 chars Setting of the maximum output current 60A 10...60A Selection of pre-set charge algorithm. Individual adjustments of Absorption, Float and Max. absorpt. time are only possible if "User defined" is selected here. Flooded Flooded, Gel, AGM, Traction, MLI, User defined Absorption voltage (@ 25°C); see section 2.3 14.25V ** 12.00-15.50V ** Float voltage (@ 25°C); see section 2.3 13.25V ** 12.00-15.50V ** Maximum absorption timer 240min 0-1440min Select the rated system voltage instead of Auto. (requires installer rights) Auto*** Auto, 12 Volt, 24 Volt, 36 Volt, 48 Volt WARNING An incorrect setting can cause overvoltage and DAMAGE the connected batteries! Shunt Shunt device Processor 1 Version Revision MB bootloader Processor 2 Version Selection of the shunt device to which the Solar ChargeMaster is connected. This can either be a MasterShunt (MSH) or a MLI Ultra battery (BAT). Enabling this function allows the Solar ChargeMaster to: - Compensate the charge voltage for cable losses (Voltage sense function); - Adjust the actual Charge state based on the state of charge of the battery - Compensate the charge voltage for deviating battery temperatures (MasterShunt only) No connection Firmware version of the Solar ChargeMaster Product version Firmware bootloader version Firmware version of MasterBus No connection, MSH+Product Name, BAT+Product Name (read only) (read only) (read only) (read only) * See section 1.4 ** For a 24V system, double the voltage. For a 36V system, triple the voltage. For a 48V system, quadruple the voltage. *** Does not apply to 36V. 18 Solar ChargeMaster 60 MPPT User and Installation Manual 4.2.5 Events Value Event x source Event x target Event x command Event x data Event x+1 Meaning Event-based command Event by the ChargeMaster that should result in an action by another device on the MasterBus network. Event-based command Selection of device on the MasterBus network that should take action due to an event by the ChargeMaster. Event-based command Action to be taken by the selected device. Factory setting Disabled Event-based command Value of the action to be taken by the selected device. The next event appears after enabling Event x. Disabled Adjustable. range (See List of event sources, section 4.2.6) (See Device list) (See List of event commands in the manual of the selected device,) (See List of event commands in the manual of the selected device,) See Event x. 4.2.6 List of events sources (Solar ChargeMaster as event source) Below the list of event sources of the Solar ChargeMaster is shown. These event sources can be used to initiate an event command and an event action at another device that is connected to the MasterBus. Event source Disabled Device state Bulk Absorption Float Battery low Solar low Any alarm Description (no event programmed) A change in the Device state occurs Charge state is Bulk Charge state is Absorption Charge state is Float Battery voltage is too low (see section 6.1) Input voltage at the Solar input is too low (see section 6.1) Any of the Alarms is triggered (see section 4.2.2) 4.2.7 List of event commands (Solar ChargeMaster as event target) Below is shown the list of event commands and event data of the Solar ChargeMaster. Other devices connected to the MasterBus can be programmed to initiate these commands and actions at the Solar ChargeMaster. Event command On/Off Bulk Abs Float Description Command to switch on/off the Solar ChargeMaster. NOTE: If the Solar ChargeMaster was switched off by means of this event command, it will switch on again the next day (after sunset and sunrise). Command to toggle the Charge state to Bulk Command to toggle the Charge state to Absorption Command to toggle the Charge state to Float 4.3 USE IN COMBINATION WITH MASTERVOLT MLI BATTERY If the Solar ChargeMaster is used in combination with a Mastervolt MLI Ultra type Li-ion battery, charging shall be terminated if the MLI Ultra battery generates the Stop charge event. The Solar ChargeMaster is able to process such a Stop Charge event. Follow next additional steps to install the Solar ChargeMaster in combination with a Mastervolt MLI type Li-ion battery: 1 Connect the DC main wiring and other components as indicated in Figure 21. 2 Connect the MasterBus cabling between the devices as indicated. Do not install the battery temperature sensor! 3 Add a MasterBus control panel to the MasterBus network. 4 Configure the following Stop Charge event at the Li-ion battery: Configuration Event source Event target Event command Event data Event 1 (obligatory) Stop Charge SCM [serial number] (see section 1.4) On/Off Copy invert 19 Solar ChargeMaster 60 MPPT User and Installation Manual 5 Set the Battery type to Mastervolt MLI (see section 4.1.2 or 4.2.4). 6 Option: enable the Shunt device function of the Solar ChargeMaster by selecting the MLI Ultra battery (BAT) as shunt device (see section 4.2.4). 7 Continue with the "Commissioning" section in the manual of the MLI Ultra battery. 1. MLI Ultra battery 5. Loads 2. Battery fuse in positive battery line 6. DC positive cable 3. Safety relay 7. DC negative cable 4 Mastervolt Solar ChargeMaster 60 MPPT 8. MasterBus cable 9. MasterBus terminator Figure 21: Use of the Solar ChargeMaster in combination with a Mastervolt MLI Ultra battery 20 Solar ChargeMaster 60 MPPT User and Installation Manual 5 TROUBLE SHOOTING If you cannot solve a problem with the aid of this chapter, contact your local Mastervolt Service Centre. See www.mastervolt.com/technical-support. Make sure you have the following information present: · Part and serial number; see section 1.4 · Software version; see section 4.1.1 Malfunction No output voltage and/or current Display shows ERROR or an error code A red LED is on or blinking No display Output voltage too low, charger supplies maximum current Charge current too low Battery not fully charged Battery is discharged too fast Batteries are too warm, gassing Possible cause What to do Solar ChargeMaster was switched off due to a previous fault situation Investigate the cause of the fault situation (section 2.6) and correct the problem. Press MENU-switch for one second to switch on the Solar ChargeMaster again. Check section 2.6 for an overview of fault indications of the LEDs and the LCD display Check section 2.6 for an overview of fault indications of the LEDs and the LCD display The Solar ChargeMaster is in Standby mode Load that is connected to the batteries is larger than charger can supply. Batteries not 100% charged Wrong battery type setting Batteries almost fully charged High ambient temperature Low irradiation on the PV-array. Output current is limited Current to load is too high Charge time too short Battery temperature too low Defective or worn-out battery Wrong battery type setting Battery capacity reduced due to sulphation or due to plate corrosion Defective battery (short circuit in cell) Battery temperature too high Wrong battery type setting Press the MENU switch shortly to activate the display Reduce load taken from the batteries. Measure battery voltage. After some time this will be higher. Check settings (see section 4.1.2 or 4.2.4). Nothing, this is normal when the battery is almost fully charged. Nothing; if ambient temperature is above 40°C / 104°F the charge current is automatically reduced. Check PV-array, check for shading. Check settings (see section 4.1.2 or 4.2.4). Reduce load taken from the batteries. Use an additional battery charger Use the battery temperature sensor. Check battery and replace if necessary. Check settings (see section 4.1.2 or 4.2.4). Charge and recharge a few times, this might help. Check battery and replace if necessary. Check battery and replace if necessary. Use the battery temperature sensor. Check settings (see section 4.1.2 or 4.2.4). 21 Solar ChargeMaster 60 MPPT User and Installation Manual 6 TECHNICAL DATA 6.1 SPECIFICATIONS Model Solar ChargeMaster 60 MPPT Article no. Nominal battery voltage (UNOM) PV-INPUT Maximum connected PV power 131906000 Auto detection,12V, 24V and 48V (36V must be selected manually) @ UNOM = 12V @ UNOM = 24V @ UNOM = 36V @ UNOM = 48V 900Wp 1800Wp 2700Wp 3600Wp Maximum input PV power* 800W 1600W 2400W 3200W Full power voltage MPPT range 15 V ~ 115 V 30 V ~ 115 V 45 V ~ 115 V 60 V ~ 115 V Absolute maximum PV Voltage MPP tracking 145VDC 145VDC Yes, integrated MPP tracker 145VDC 145VDC Start-up voltage Maximum PV input current EU efficiency Peak static power conversion efficiency Battery voltage + 3VDC 50ADC >97% >98% Static MPPT efficiency >99% BATTERY OUTPUT Maximum charge current (IMAX) Charge voltage, Absorption @ UNOM = 12V 60 A 14.25V (Traction: 14.45V) @ UNOM = 24V 60 A 28.5V (Traction: 28.9V) @ UNOM = 36V 60 A 42.75V (Traction: 43.35V) @ UNOM = 48V 60 A 57.0V (Traction: 57.8V) Charge voltage, Float; Low voltage disconnect / reconnect 13.25V (AGM, gel: 13.8V, MLI: 13.5V) 8.5V / 9.0V 26.5V (AGM, gel: 27.6V, MLI: 27.0V) 17.0V / 18.0V 39.75V (AGM, gel: 41.4V, MLI: 40.5V) 25.5V / 27.0V 53.0V (AGM, gel: 55.2V, MLI: 54.0V) 34.0V / 36.0V High voltage disconnect / reconnect 15.0V / 14.5V 30.0V / 29.0V 45.0V / 43.5V 60.0V / 58.0V Battery temperature compensation DC consumption (at night) DC consumption (on, no charging) 30 mV/°C <1mA <130mA 60 mV/°C <1mA <130mA 90 mV/°C <1mA <130mA 120 mV/°C <1mA <130mA Charge algorithm Three step (Bulk, Absorption, Float) Battery types** Flooded, AGM, Gel, Traction, MLI (Mastervolt Lithium-Ion). GENERAL Galvanic isolation between PV and battery No, common negative conductor Dimensions in mm [inch] (h x w x d) 168 x 398 x 107 mm [6.6 x 15.7 x 4.2 inch]; see also section 6.2 Weight Operating Temperature Range Full Power Temperature range Non-operating Temperature range Relative Humidity 5.5 kg [12.1Lbs] 20°C TAMB +55°C [4°F TAMB 131°F] (power de-rating > 40°C / 104°F) 20°C TAMB +40°C [4°F TAMB 104°F] (no power de-rating) 40°C TAMB +75°C [4°F TAMB 167°F] (storage temperature) 5% to 95% non-condensing Protection degree IP23 MasterBus connectivity Terminals Yes Screw terminals, max. wire size 35mm2 * Automatic limitation of input power; excessive power will not be converted ** Refer to section 4.1.2 or 4.2.4 for battery type settings. Specifications are subject to change without prior notice. 22 Solar ChargeMaster 60 MPPT User and Installation Manual 6.2 DIMENSIONS Figure 22: Dimensions of the Solar ChargeMaster in mm [inches] 23 Solar ChargeMaster 60 MPPT User and Installation Manual This page intentionally left blank We welcome your feedback and suggestions! Send feedback on this document to info@mastervolt.com Europe, Middle East & Africa Technical Support T: +31 (0) 20 34 22 100 E: ts.emea@navicogroup.com Location & Shipping Navico Group EMEA Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Americas & Caribbean Technical Support T: +1 262 293 0600 / 800 307 6702 E: tech.mastervolt@navicogroup.com Location & Shipping Navico Group US N85 W12545 Westbrook Crossing Menomonee Falls, WI 53051 United States Asia Pacific Technical Support T: +64 9 415 7261 E: technical.apac@navicogroup.com Location & Shipping Navico Group APAC 12 Rothwell Avenue Rosedale, Auckland 0632 New Zealand Document version: 10000009952/03 (March 25) Copyright ©2025 Navico Group EMEA. All rights reserved.