Multifunctional Electrical Installation Tester
MI 3155 EurotestXD
Electrical Installation Safety
Product Overview
The MI 3155 EurotestXD is Metrel's newest flagship multi-functional measuring instrument, designed for industrial testing. It features an ergonomic design, an intuitive user interface, a memory organizer, and programmable AUTO SEQUENCES managed via a large color touch screen. It complies with standards like IEC/EN 61557 and IEC/EN/HD 60364-4-41, performing TRMS current measurements, RCD tests, line and loop impedance tests (3/4 wires), and earth resistance measurements. It also supports on-line voltage monitoring, phase sequence testing, varistor testing, PI/DAR calculation, luminance measurement, discharge time testing, ISFL measurements, IMD tests, and functional/visual inspections.
[Image: Front view of the Metrel MI 3155 EurotestXD tester, showing a large color touch screen displaying the main menu with options like Single Tests, Memory Organizer, Auto Sequences, and General Settings. The device has a rugged, ergonomic design with blue and black casing.]
Measuring Functions
- Live Transformer's Impedance Measurement with Four Wire Test
- Hi-precision Short Circuit Current evaluation with Calculated Hot factor
- 3-wire test of PE (RPE function) without extension lead conductor
- Autotest insulation function between L-N, N-PE and L-PE (R ISO ALL function)
- 4 wire continuity test
- Insulation resistance with DC voltage from 50 V to 2500 V and PI, DAR calculation
- Varistor test
- Continuity of PE conductors with 200 mA DC test current with polarity change
- Continuity of PE conductors with 7 mA test current without RCD tripping
- 2-wire and 3-wire high-current loop impedance (L-PE) measurement
- 3-wire loop impedance (L-PE) measurement with Trip Lock RCD function
- Touch voltage / Contact voltage measurement with external P/S probe
- 2-wire and 3-wire line impedance (L-L, L-N) measurement
- 1-phase / 3-phase TRMS voltage and frequency measurements
- Line, loop and RCD measurements at frequency range 16 ... 400 Hz
- Phase sequence
- Power and THD measurement (up to the 12th harmonic)
- RCD testing (general and selective, type AC, A, F, B, B+, MI RCD, EV RCD, PRCD, PRCD-K, PRCD-S)
- Earth resistance (3-wire and 2-clamps method)
- Specific earth resistance with Ro-adapter (option)
- TRMS leakage and load currents (option)
- First fault leakage current (ISFL)
- Testing of Insulation Monitoring Devices (IMDs)
- Machine mode support with time discharge
- Illumination (option)
- High resolution Loop impedance (mΩ) (option)
- EVSE (Electrical Vehicle Supply Equipment) support (option)
- Determining location of cables (option)
- QR and/or barcode scanner support (option)
Key Features
- Programmable AUTO SEQUENCES.
- Predefined profile dependent AUTO SEQUENCES.
- Predefined Automatic tests: Auto TT (U, ZIn, Zs, Uc); Auto TN/RCD (U, ZIn, Zs, Rpe); Auto TN (U, ZIn, Zlpe, Rpe); Auto IT (U, ZIn, Isc, Isfl, IMD).
- High resolution colour touch screen, 4.3" TFT.
- Functional inspections.
- Visual inspections.
- Custom inspections (visual and functional) which may be incorporated into AUTO SEQUENCES.
- EVSE AUTO SEQUENCES and function inspections.
- Machine functional and visual inspections.
- Built-in help screens for referencing on site.
- Built-in fuse tables for automatic evaluation of the line / loop impedance result.
- Monitoring of all 3 voltages in real-time.
- Automatic polarity reversal on continuity test.
- Automated RCD testing procedure (RCD AUTO).
- Automated Impedance testing procedure (Z AUTO).
- Measurement filtering according to the selected area group.
- Built-in charger and rechargeable batteries as standard accessory.
- BT communication with PC, Android tablets and smart phones via built-in BT.
- PC SW Metrel ES Manager (structure and report creation, data upload/download).
- Optional aMESM Android app (structure and report creation, data upload/download).
Technical Specifications
Function | Measuring range | Resolution | Accuracy | |
---|---|---|---|---|
CONTINUITY | Test Current 7 mA 2-wire | 0.00 Ω ... 19.99 Ω | 0.1 Ω | ±(5% of r. + 3 digits) |
20.0 Ω ... 1999 Ω | 1 Ω | ±(5% of r. + 3 digits) | ||
Test Current 200 mA 2-wire, 4-wire | 0.00 Ω ... 19.99 Ω | 0.01 Ω | ±(3% of r. + 3 digits) | |
20.0 Ω ... 199.9 Ω | 0.1 Ω | ±(5% of r.) | ||
200.0 Ω ... 1999 Ω | 1 Ω | ±(5% of r.) | ||
INSULATION RESISTANCE | R iso, R iso all ¹ Test Voltage 50/100/250 V | 0.00 MΩ ... 19.99 MΩ | 0.01 MΩ | ±(5% of r. + 3 digits) |
20.0 MΩ ... 99.9 MΩ | 0.1 MΩ | ±(10% of r.) | ||
100.0 MΩ ... 199.9 MΩ | 0.1 MΩ | ±(20% of r.) | ||
R iso, R iso all ¹ Test Voltage 500/1000 V | 0.00 MΩ ... 19.99 MΩ | 0.01 MΩ | ±(5% of r. + 3 digits) | |
20.0 MΩ ... 199.9 MΩ | 0.1 MΩ | ±(5% of r.) | ||
200 MΩ ... 999 MΩ | 1 MΩ | ±(10% of r.) | ||
R iso, R iso all ¹ Test Voltage 2500 V | 0.00 MΩ ... 19.99 MΩ | 0.01 MΩ | ±(5% of r. + 3 digits) | |
20.0 MΩ ... 199.9 MΩ | 0.1 MΩ | ±(5% of r.) | ||
200 MΩ ... 999 MΩ | 1 MΩ | ±(10% of r.) | ||
1.00 GΩ ... 19.99 GΩ | 0.01 GΩ | ±(10% of r.) | ||
DAR, PI | 0.01 ... 9.99 | 0.01 | ±(5% of r. + 2 digits) | |
10.0 ... 100.0 | 0.1 | ±(5% of r.) | ||
Varistor test AC, DC ² | 0 V ... 1000 V (DC) | 1 V | ±(3% of r. + 3 digits) | |
0 V ... 625 V (AC) | (-0%/+15%) of r. ± 10 digits | |||
RCD Uc | 0.00 V ... 19.99 V | 0.1 V | (-0%/+15%) of r. | |
20.0 V ... 99.9 V | ||||
RCD (t), RCD I Ramp | 0.00 ms ... 40.0 ms | 0.1 ms | ±1 ms | |
0.0 ms ... max. time | +3 ms | |||
0.2xIΔN ... 1.1xIΔN (AC, MI, EV a.c.) | 0.05xIΔN | ±0.1xIΔN | ||
0.2xIΔN ... 1.5xIΔN (A, IΔN ≥30 mA) | ||||
0.2xIΔN ... 2.2xIΔN (A, IΔN <30 mA) | ||||
0.2xIΔN ... 2.2xIΔN (B, MI, EV d.c.) | ||||
IMPEDANCE | Zline (L-L, L-N), Ipsc, Zline 4-wire ³ | 0.00 Ω ... 9.99 Ω | 0.01 Ω | ±(3% of r. + 3 digits) |
10.0 Ω ... 99.9 Ω | 0.1 Ω | |||
100 Ω ... 999 Ω | 1 Ω | ±(10% of r.) | ||
1.00 kΩ ... 9.99 kΩ | 10 Ω | |||
Zloop (L-PE), Ipfc, Zloop 4-wire ³ | 0.00 Ω ... 9.99 Ω | 0.01 Ω | ±(3% of r. + 3 digits) | |
10.0 Ω ... 99.9 Ω | 0.1 Ω | |||
100 Ω ... 999 Ω | 1 Ω | ±(10% of r.) | ||
1.00 kΩ ... 9.99 kΩ | 10 Ω | |||
Zs RCD ⁴ | ||||
VOLTAGE | TRMS (0, 14 ... 500 Hz) | 0 ... 550 V | 1 V | ±(2% of r. + 2 digits) |
Frequency | 0.00 Hz .. 9.99 Hz | 0.01 Hz | ±(0.2% of r. + 1 digits) | |
10.0 Hz ... 499.9 Hz | 0.1 Hz | |||
CURRENT | TRMS, AC with A 1018, range=20 A | 0.0 mA ... 99.9 mA | 0.1 mA | ±(5% of r. + 5 digits) |
100 mA ... 999 mA | 1 mA | ±(3% of r. + 3 digits) | ||
1.00 A ... 19.99 A | 0.01 A | ±(3% of r.) | ||
TRMS, AC with A 1019, range=20 A | 0.0 mA ... 99.9 mA | 0.1 mA | Indicative | |
100 mA ... 999 mA | 1 mA | ±(5% of r.) | ||
1.00 A ... 19.99 A | 0.01 A | ±(3% of r.) | ||
TRMS, AC/DC with A 1391, range=40 A | 0.00 A ... 1.99 A | 0.01 A | ±(3% of r. + 3 digits) | |
2.00 A ... 19.99 A | 0.01 A | ±(3% of r.) | ||
20.0 A ... 39.9 A | 0.1 A | ±(3% of r.) | ||
TRMS, AC/DC with A 1391, range = 300 A | 0.00 A ... 19.99 A | 0.01 A | Indicative | |
20.0 A ... 39.9 A | 0.1 A | Indicative | ||
40.0 A ... 299.9 A | 0.1 A | ±(3% of r. + 5 digits) | ||
EARTH RESISTANCE | 3 wire ⁵ | 0.00 Ω ... 19.99 Ω | 0.01 Ω | ±(5% of r. + 5 digits) |
20.0 Ω ... 199.9 Ω | 0.1 Ω | |||
200.0 Ω ... 9999 Ω | 1 Ω | |||
2 clamp | 0.00 Ω ... 19.99 Ω | 0.01 Ω | ±(10% of r. + 10 digits) | |
20.0 Ω ... 30.0 Ω | 0.1 Ω | ±(20% of r.) | ||
30.1 Ω ... 39.9 Ω | 0.1 Ω | ±(30% of r.) | ||
Specific earth resistance | 0.0 Ωm ... 99.9 Ωm | 0.1 Ωm | ±(5% of r.) for Re 1 Ω ... 1999kΩ | |
100 Ωm ... 999 Ωm | 1 Ωm | ±(10% of r.) for Re 2 kΩ ... 19.99kΩ | ||
1.00 kΩm ... 9.99 kΩm | 0.01 kΩm | ±(20% of r.) for Re > 20 kΩ | ||
10.0 kΩm ... 99.9 kΩm | 0.1 kΩm | |||
100 kΩm ... 9999 kΩm | 1 kΩm | |||
POWER | Power (P, S, Q) | 0.00 W (VA, Var) ... 99.9 kW (kVA, kVar) | 0.1% ... 99.9% | |
Power factor | -1.00 ... 1.00 | |||
HARMONICS | Voltage THD | 0.1 % ... 99.9 % | 0.1% ... 99.9% | |
Voltage harmonics | 0.1 V ... 500 V | |||
Voltage THD | 0.1 % ... 99.9 % | |||
Current harmonics and Current THD | 0.00 A ... 199.9 A | 0.1 mA | ±(5% of r. + 3 digits) | |
FIRST FAULT LEAKAGE CURRENT (ISFL) | 0.0 mA ... 19.9 mA | 0.1 mA | ||
IMD TEST | Threshold indicative insulation resistance | 5 ... 640 kΩ | 5 kΩ | Indicative values, up to 128 steps |
ILLUMINANCE | Type B | 0.01 lux ... 19.99 lux | 0.01 lux | ±(5% of r. + 2 digits) |
20.0 lux ... 199.9 lux | 0.1 lux | ±(5% of r.) | ||
200 lux ... 1999 lux | 1 lux | ±(10% of r. + 3 digits) | ||
2.00 klux ... 19.99 klux | 10 lux | ±(10% of r.) | ||
Type C | 0.01 lux ... 19.99 lux | 0.01 lux | ±(5% of r. + 2 digits) | |
20.0 lux ... 199.9 lux | 0.1 lux | ±(5% of r. + 3 digits) | ||
200 lux ... 1999 lux | 1 lux | ±(10% of r. + 3 digits) | ||
2.00 klux ... 19.99 klux | 10 lux | ±(10% of r.) | ||
DISCHARGING TIME | Discharging time | 0.0 s ... 10.0 s | 0.1 s | ±(5% of r. + 2 digits) |
Peak voltage | 0 V ... 550 V | 1 V | ±(5% of r. + 3 digits) | |
GENERAL | Power supply | 7.2 V (4400 mAh Li-Ion battery pack) | ||
Overvoltage category | 600 V CAT III; 300 V CAT IV | |||
Protection class | double insulation | |||
COM port | BT, USB, RS232 | |||
Display | Colour TFT display, 4.3 inch, 480 x 272 pixels | |||
Weight | 1.78 kg | |||
Size (l x h x w) | 252 x 111 x 165 mm |
Standards
- Functionality: EN 61557; DIN 5032
- Other reference standards for testing: IEC/EN/HD 60364-4-41; IEC/EN 61008; IEC/EN 61009; BS 7671; AS/NZ 3017
- Electromagnetic compatibility (EMC): IEC/EN 61326-1
- Safety: IEC/EN 61010-1; IEC/EN 61010-031; IEC/EN 61010-2-030; IEC/EN 61010-2-032
Applications
- Testing of TT, TN and IT systems
- Testing of single and multiphase systems
- Initial and periodic testing of domestic and industrial installations
- LV Installation safety testing
- Maintenance
- Lightning installations
- Testing on high and low frequency installations (industrial, aircraft, railway, mining, chemistry, ferry boat)
- Construction sites
- Mobile LV Generator Units
- Machine and switchboard testing
- Medical installation testing
- Fire brigades, ambulance, military and police vehicles
- Mobile Video/Audio, Concert Halls, Fairs, Playgrounds
- Electrical Vehicle Supply Equipment (EVSE) testing
- Observation of insulation trends
Optional Accessories
- A 1569 Power supply adapter 12 V / 3 A
- A 1567 4400mAh battery pack
- A 1568 8800mAh battery pack
- A 1551 Small carrying bag with Metrel logo
- A 1552 Large carrying bag with Metrel logo
- P 1101 BASIC to PRO licence key upgrade for Metrel ES Manager
- A 1401 BLK Tip commander
- A 1018 Current clamp (low range, leakage)
- A 1019 Current clamp
- A 1391 AC/DC Current clamp
- A 1172 Luxmeter sensor, type B (PS/2)
- A 1173 Luxmeter sensor, type C (PS/2)
- A 1191 Receiver R10K
- A 1192 Selective probe for R10K
- A 1437 Test lead with Kelvin probe
- S 2027 Earth test set, 3-wire, 50 m
- S 2058 Insulation test plates
- A 1012 Test lead, green, 4 m
- A 1154 Test lead, black, 4 m
- A 1026 Test lead, red, 20 m
- A 1153 Test lead, black, 20 m
- A 1164 Test lead, black, 50 m
- S 2012 Continuity test lead, 10 m, 2 pcs (red, black)
- S 2025 Test lead, 1.5 m, 2 pcs (black, red)
- A 1198 Magnetic contact probe
- A 1201 Insulated rod for CONTINUITY measurement
- A 1202 Additional extension part for A 1201
- A 1532 EVSE adapter
- A 1199 Ro-adapter
- A 1143 Euro Z 290 A
Ordering Information
Standard Set MI 3155 ST
- Instrument MI 3155 EurotestXD
- 4400 mAh battery pack
- Power supply adapter 12 V / 3 A
- Plug commander, 1.5 m
- Test lead, 4-wire, 1.5 m
- Test lead, 3-wire, 1.5 m
- Test lead, 2-wire, 2,5 kV, 1.5 m
- Test probe, 4 pcs (black, blue, green, red)
- Crocodile clip, 6 pcs (black - 2 pcs, blue - 1 piece, green - 1 piece, red - 2 pcs)
- Earth set 20 m
- USB cable
- Soft carrying bag
- Soft carrying neck belt
- Metrel ES Manager BASIC license*
- Short instruction manual
- Instruction manual (CD)
- Guide for testing and verification of Low voltage installations (CD)
- Calibration certificate
- Metrel ES Manager (program installation) A 1481 (CD)
Euro Set MI 3155 EU
- MI 3155 ST
- 8800 mAh battery pack instead of 4400 mAh battery pack
- Current clamp A 1018 (low range, leakage)
- Current clamp A 1019
- Metrel ES Manager PRO license*
- Metrel aMESM Android app
- *Metrel ES Manager can be downloaded free of charge from Metrel Web server.
Manufacturer Information
METREL D.D.
Measuring and Regulation Equipment Manufacturer
Ljubljanska 77, SI-1354 Horjul, Slovenia
T +386 (0)1 75 58 200, F +386 (0)1 75 49 226
metrel@metrel.si, www.metrel.si
Note! Photographs in this catalogue may slightly differ from the instruments at the time of delivery. Subject to technical change without notice.