SensoMAG F10

Conventional Fire Alarm Fixed Temperature Detector

General Information and Compatibility

ATTENTION: Read carefully these installation instructions before installing the device!

The SensoMAG F10 detector is compatible with any conventional Fire Panel with a fire alarm threshold between 10mA and 15mA (or between 10mA and 30mA when using the B24RD fire base).

Compatible Base Types

The SensoMAG F10 detector can be used with four different base types:

Installation Steps

  1. Choose the proper place for installation of the fire detector, referring to the provided installation guidelines. Note: Do not install the detector near natural heat sources, such as above cookers, ovens, or fireplaces.
  2. To "lock" the detector to the base, remove the small triangular "tooth" and break off the plastic key from the base. Keep the plastic key in a safe place for future detector opening.
  3. Mount the fire base on the ceiling of the protected premises using fixings appropriate for the mounting surface.
  4. Connect the detector base to the fire panel using the wiring diagram. ATTENTION: Disconnect the line power before installing the detector!
  5. Insert the detector into the base and rotate clockwise until it clicks into place. Continue rotating until the detector is locked to the base.
  6. If the detector is locked to the base, use the plastic key to open it for maintenance or cleaning. Lightly press the plastic key into the base opening and simultaneously rotate the detector head counter-clockwise.
  7. ATTENTION: If removing the detector's PCB for service maintenance, align the colored dot sticker on the PCB with the mark on the plastic body (visible from the outside) when remounting. The hole next to the colored dot must align with the pin on the plastic body. Gently press downwards to fix the PCB in place.
  8. Test the detector for proper operation and LED indication.

Wiring Diagram

The wiring diagram illustrates connections for various base types (B12L/U, B24/B24-HP, B24D, B24RD) to a Fire Panel and an Intruder Alarm Panel. It also indicates the necessity of a 100K resistor in parallel at the beginning of the line if the EOL-module is only a capacitor.

Jumper Operation Mode: The detector features a jumper for selecting between Latch Mode (Jumper ON) and Unlatch Mode (Jumper OFF).

Testing and Maintenance

Testing Procedure

  1. Apply power to the detector.
  2. Wait for 30 seconds.
  3. Apply a heat tester (e.g., Cordless Heat Detector Tester or Heat Tester 110V-240V) at a distance of 20cm to test the heat sensor. The fire detector should enter the fire condition within 8 seconds, with both LEDs lighting up.
  4. Power off the detector for a minimum of 2 seconds. After resetting, the detector will enter duty mode, and the LEDs will turn off.

Maintenance Schedule

Regular maintenance should be performed as follows:

LED Indication

Technical Specifications

Parameter Specification
Operating Voltage Range 9 - 30 V DC (Nominal 12/24VDC)
Average current consumption in quiescent state < 50μA
Alarm state current (with B24, B24-HP, B24D bases) 20 mA / 12:30V
Alarm state current (with B24RD base) 33 mA/12V; 49mA/24V; 57mA/30V
Alarm state current (with B12L/U base) 18 mA/9V; 29mA/12V; 32mA/15V
Class (in accordance with EN 54-5) A2/S
Output in alarm state at terminal RI (+IN/+OUT) 20mA (max) / -3.3V
Degree of protection IP30
Wire Gauge for terminals 0.4mm² - 2.0mm²
Operational temperature range -10°C to +60°C
Relative humidity resistance (93 ± 3)% @ 40°C
Dimensions (incl. base) Ø102mm, h 42mm* / ø103mm, h 56mm**
Weight (incl. base) 160g* / 170g**

* B12L/U, B24, B24D, B24RD
** B24-HP

Models: F10 B12L-U Conventional Fire Alarm Fixed Temperature Detector, F10 B12L-U, Conventional Fire Alarm Fixed Temperature Detector, Fixed Temperature Detector, Temperature Detector

File Info : application/pdf, 2 Pages, 805.39KB

PDF preview unavailable. Download the PDF instead.

datas

References

Corel PDF Engine Version 20.0.0.633 CorelDRAW 2018

Related Documents

Preview SensoIRIS WSST Intelligent Fire Alarm Sounder and Strobe Installation Guide
Installation instructions and technical specifications for the Teletek Electronics SensoIRIS WSST intelligent analogue addressable fire alarm sounder and strobe, compliant with EN 54-3 and EN 54-23 standards.
Preview Teletek iRIS4 Fire Alarm Panel: Versatile Installation Solution
Discover the Teletek iRIS4, a highly versatile fire alarm panel designed for installations with high standards. It supports up to 1000 addressable devices, networking of up to 64 panels, remote access via Teletek-Cloud, and offers smart control capabilities for various applications.
Preview Teletek Electronics IRIS Analogue Addressable Fire Panel Installation and Programming Manual
Comprehensive guide for the installation and programming of the Teletek Electronics IRIS Analogue Addressable Fire Panel (Model CE0832). Covers panel versions, specifications, mounting instructions, programming menus, maintenance, and usage instructions.
Preview BRAVO KBD Wireless Control Keyboard: Installation & Operation Guide | Teletek Electronics
Comprehensive user manual for the Teletek Electronics BRAVO KBD wireless control keyboard. Learn about installation, operation, programming, and troubleshooting for your security system.
Preview Teletek Electronics: Hırsız ve Yangın Alarm Sistemleri Ürün Kataloğu
Teletek Electronics tarafından sunulan hırsız alarm sistemleri ve yangın algılama sistemleri ürün kataloğu. Kapsamlı ürün yelpazesi, teknik özellikler ve sertifikalar hakkında bilgi edinin.
Preview AJAX GPRS Communication Module Installation, Programming and Operation Manual
This manual provides comprehensive instructions for the installation, programming, and operation of the AJAX GPRS Communication Module. It covers general information, functional characteristics, connection diagrams, software setup using ProsTE, user management, and troubleshooting.