Airedale Ceiling Cassette Technical Manual

Models CSD, CSH and CCW

Document Number: AIR 8-105.11 | Date: June, 2023

Overview

The ceiling-mounted Cassette units provide independent temperature control for each area served. They offer thermostatic control for varying conditions to suit diverse requirements. Optional fresh air intakes are available for ventilation. Cassettes are available in three models: DX cooling, heat pump, or chilled water cooling, with optional electric or hot water heating. This design minimizes architectural compromise and can offer cost savings by reusing existing piping and wiring during modernizations. Airedale by Modine Cassettes incorporate design techniques to minimize noise, including low blower speeds, rigid construction, and sound-absorbent insulation. For individual comfort, units can be equipped with electro-mechanical or microprocessor-based controls, including infrared remote transmitters and compatibility with Building Management Systems via Carel microprocessor controls and network cards.

The Modine Breeze® AccuSpec program is a web-based tool for generating performance data based on actual job conditions, assisting in the configuration and selection of Airedale by Modine products. It can generate Submittal Schedules, Submittal Data, and Specifications.

As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.

Table of Contents

  • Model Identification
  • Standard Features
  • Accessories - Field Installed
  • Performance Data
  • Unit Dimensional Data
  • Technical Data

Model Identification

The model nomenclature is structured to define product type, configuration, capacity, voltage, generation, control code, heating option, filtration, freeze protection, power option, and communication option.

Digit 1 2,3 4,5 6 7 8 9 10 11 12 13
Code PT UC MBH SV G C HO FL FP PO CC
1 - Product Type (PT) C - Ceiling Cassette
2,3 - Unit Configuration (UC) SD - DX Cooling, SH - HP Heating and Cooling, CW - Chilled Water
4,5 - Nominal Capacity (MBH) 08 - 8,000 Btu/Hr, 12 - 12,000 Btu/Hr, 18 - 18,000 Btu/Hr, 20 - 20,000 Btu/HR, 24 - 24,000 Btu/Hr, 30 - 30,000 Btu/Hr, 33 - 33,000 Btu/Hr, 36 - 36,000 Btu/Hr, 42 - 42,000 Btu/Hr
6 - Supply Voltage (SV) A - 115V/60Hz/1ph, B – 208V/60Hz/1ph, C - 230V/60Hz/1ph, H – 277V/60Hz/1ph, J - 110V/50Hz/1ph, K – 220V/50Hz/1ph
7 - Generation (G) A - Current Design
8 - Control Code (C) C - Modine Controls System, E - Electro-Mechanical Controls, M - Microprocessor Controls (Infrared Remote Control)
9 - Heating Option (HO) N - None, A - Electric Heat, B - Hot Water Heating Coil – 4-pipe, C - Hot Water Heating – 2 Pipe (Uses CW Coil)
10 - Filters (FL) A - 60-80% Arrestance (Standard), B - MERV 10
11 - Heat Freeze Protection (FP) N - None, F - Hot Water Coil Freeze Protection
12 - Power Option (PO) N - None, D - Cassette Power Disconnect Switch
13 - Control Communication Option (CC) N - None, B - BACnet IP Compatible Network Card, M - BACnet MS/TP Compatible Network Card

Standard Features

General Description – Ceiling Cassette Unit

Digit 2,3: Unit Configuration (UC)

  • SD = DX Cooling: All direct expansion units feature a factory-installed thermal expansion valve and large surface area evaporator coils for optimal heat transfer and airflow. Coils are made from refrigeration-quality copper tubes with mechanically bonded aluminum fins.
  • SH = HP Heating & Cooling: Similar to DX Cooling units, these also include a factory-installed thermal expansion valve and large evaporator coils made from copper tubes with mechanically bonded aluminum fins.
  • CW = Chilled Water: Chilled water units use large surface area coils optimized for heat transfer and airflow. These coils are constructed from refrigeration-quality copper tubes with mechanically bonded aluminum fins and are circuited from headers to minimize water pressure drops.

Digit 4,5: Nominal Capacity (MBH)

Available capacities range from 08 (8,000 Btu/Hr) to 42 (42,000 Btu/Hr).

Digit 6: Supply Voltage (SV)

Available voltages include 115V/60Hz/1ph, 208V/60Hz/1ph, 230V/60Hz/1ph, 277V/60Hz/1ph, 110V/50Hz/1ph, and 220V/50Hz/1ph.

Digit 8: Control Code (CC)

  • C = Modine Controls System: Units feature a programmable microprocessor controller with pre-engineered control strategies, requiring a wall sensor, thermostat, or network interface card.
  • E = Electro-Mechanical Controls: Units are factory wired with an electro-mechanical system including relays and safety switches. A terminal strip is provided for wiring a 24V wall-mounted thermostat. Terminals for remote start/stop are included.
  • M = Microprocessor Controls: A custom-designed microprocessor allows room conditions to be maintained at a user-defined setpoint via a handheld infrared transmitter. The system monitors indoor coil and return air temperatures and includes a self-diagnostic feature. Alarms are displayed on the fascia receiver for low indoor coil temperature or sensor failure. The infrared transmitter controls ON/OFF, temperature settings, fan speed, operating mode, and air sweep. A built-in clock with a timer function is also included.

Digit 9: Heating Option (HO)

  • N = None: No heating option.
  • A = Electric Heat: Factory-fitted electric heating elements with thermal cut-out protection.
  • B = Hot Water Heating Coil - 4 Pipe: Includes a factory-fitted hot water heating coil (in addition to DX or chilled water coil) made of copper tubes and aluminum fins.
  • C = Hot Water Heating - 2 Pipe (Uses CW Coil): A combined chilled water/hot water coil for 2-pipe systems, providing heating or cooling based on mode.

Digit 10: Filtration (F)

  • A = 60-80% Arrestance (Standard): Reusable wire-framed filters, suitable for vacuum cleaning.
  • B = MERV 10: 1-inch thick, radial pleated disposable filters with a MERV 10 rating.

Digit 11: Heat Freeze Protection (FP)

  • N = None: No freeze protection.
  • F = Hot Water Coil Freeze Protection: A sensor prevents hot water coil freezing by opening the flow control valve and stopping the fan if a freeze condition is detected.

Digit 12: Power Option (PO)

  • N = None: No power disconnect option.
  • D = Cassette Power Disconnect Switch: A disconnect switch on the control panel allows for power disconnection prior to maintenance.

Digit 13: Control Communication Option (CC)

  • N = None: No communication option.
  • B = BACnet IP Compatible Network Card: Allows compatibility with BACnet IP building management systems.
  • M = BACnet MS/TP Compatible Network Card: Allows compatibility with BACnet MS/TP building management systems.

Construction and Components

Construction: Cases are made from lightweight galvanized sheet steel with integral fan mounting rails. Fire-resistant foam insulation provides thermal and acoustic insulation.

Fan: Backward curved centrifugal fans are statically and dynamically balanced for quiet operation. Impellers are aluminum or fire-retardant plastic. Fans are driven by an enclosed multi-speed external rotor motor with thermal overload protection and sealed bearings.

Condensate Pump: An integrated pump and check valve remove condensate. The pump is mounted on a removable bracket and includes a float switch to stop cooling if the pump fails.

Air Vanes: Outlet vanes prevent condensation. They are manually adjustable on models 08 and 12, and motorized on larger sizes, allowing auto sweep or fixed positions. Polystyrene blanking pieces are provided to block up to two fascia slots.

Alarm Status Relay: A relay provides unit failure notification, with a normally open contact available for field connection.

Accessories - Field Installed

Fresh Air Duct Collars

Available for units with fresh air knockouts. Allows connection of a 3" flexible duct. Includes a replacement filter for air balancing.

Supply Air Duct Collars

Allow for ducted conditioned air by removing branch duct knockouts (up to 2 per unit). Available for 5" or 6" flexible duct connection, depending on unit size. For models 08 and 12, it's recommended to use only one of the three knockouts due to unit capacity.

Shroud

A sheet metal shroud is available to cover the unit housing when not installed in a drop ceiling. It has a Painted Sky White with hammertone finish.

Control Valves

Three-way, three-port diverting or two-way, two-port control valves are supplied loose for on-site installation, actuated by a 24V signal. These are for controlling chilled water or hot water flow. Specific valve types (normally closed/open) depend on the system configuration (4-pipe, 2-pipe changeover).

Condensing Unit (for DX or Heat Pump units)

Refer to Breeze submittal for details.

Low Ambient Kit (Use with Condensing Units)

Provides fan speed control for compressor operation down to 0°F outside temperature.

Performance Data

Table 7.1 - Cooling Performance - DX Cooling Only and Heat Pump Units

Model Entering Air DB °F @ 50% RH High Medium Low
Total Cooling BTU/h Sensible Cooling BTU/h Total Cooling BTU/h Sensible Cooling BTU/h Total Cooling BTU/h Sensible Cooling BTU/h
CSD/CSH 187216,50014,40016,30013,90015,80013,100
7517,50014,90017,20014,40016,80013,500
8019,20015,60018,90015,10018,50014,200
CSD/CSH 247220,00016,80019,60016,10019,30015,600
7521,00017,30020,60016,50020,40016,000
8023,00018,00022,60017,20022,20016,700
CSD/CSH 307227,60025,00027,00023,60026,40022,200
7529,00025,80027,60025,00027,80022,800
8031,40027,00031,00025,40030,20023,800
CSD/CSH 367233,40028,40033,00027,60032,20026,200
7535,00029,20034,60028,20034,00026,800
8038,20030,40037,80029,40037,00027,800
CSD/CSH 427237,80031,60037,20030,20036,80029,400
7539,50032,40039,00031,00038,50030,000
8042,50033,40042,00032,00041,50031,000

Cooling capacities are based on 95/75°F DB/WB Outdoor Ambient.

Table 7.2 - Heating Performance - Heat Pump Units

Model Entering Air DB °F High Medium Low
Total Heating (BTU/h) Total Heating (BTU/h) Total Heating (BTU/h)
CSH 185019,10018,90018,600
6017,80017,60017,200
7016,40016,20016,000
CSH 245024,40024,00023,800
6022,80022,60022,200
7021,40021,00020,800
CSH 305030,40030,20029,800
6029,00028,80028,200
7027,40027,20026,800
CSH 365035,80035,60035,000
6034,20033,80033,400
7032,40032,00031,600
CSH 425039,50039,00039,000
6038,20037,80037,800
7037,20036,80036,600

Heating capacities are based on 47/43°F DB/WB Outdoor Ambient.

Table 8.1 - Cooling Performance - Chilled Water Units

Model Filter Entering Air DB °F @ 50% RH 40/50°F 45/55°F
TC BTUH SC BTUH FLOW GPM PR DROP PSI TC BTUH SC BTUH FLOW GPM PR DROP PSI
CCW 08STD.725,9004,9001.22.94,1003,9000.81.5
757,3005,5001.54.35,1004,5001.02.2
809,9006,5002.07.47,8005,5001.64.8
MERV 10724,0003,3000.81.62,8002,6000.60.8
755,0003,7001.02.33,5003,1000.71.2
806,8004,4001.33.85,4003,7001.12.5
CCW 12STD.728,8007,1001.71.76,1005,7001.20.9
7510,9008,0002.22.57,6006,6001.51.3
8014,6009,4002.94.211,2008,0002.22.6
MERV 10725,3004,3001.10.73,7003,4000.70.3
756,6004,8001.31.14,6003,9000.90.5
808,9005,7001.81.86,8004,8001.41.1
CCW 18STD.7214,20011,7002.81.510,0009,5002.00.8
7517,70013,2003.52.212,50010,8002.51.2
8023,90015,6004.83.718,20013,2003.62.3
MERV 107212,90010,5002.61.39,0008,5001.80.7
7516,00011,9003.21.811,3009,8002.31.0
8021,60014,0004.33.116,50011,9003.31.9
CCW 20STD.7214,50012,0002.91.610,2009,7002.00.8
7518,10013,5003.62.312,80011,1002.51.2
8024,50015,9004.93.918,60013,5003.72.4
MERV 107212,90010,5002.61.39,0008,5001.80.7
7516,00011,9003.21.811,3009,8002.31.0
8021,60014,0004.33.116,50011,9003.31.9
CCW 33STD.7224,40019,4004.93.117,20015,8003.41.6
7530,00021,8006.04.421,40018,0004.32.4
8040,30025,8008.07.431,10021,9006.24.6
MERV 107223,30018,5004.62.816,40015,1003.31.5
7528,70020,8005.74.120,50017,1004.12.2
8038,40024,6007.76.829,70020,8005.94.2
CCW 36STD.7226,80021,5005.33.618,90017,5003.81.9
7533,10024,1006.65.223,50019,9004.72.8
8044,60028,6008.98.834,30024,2006.95.5
MERV 107223,30018,5004.62.816,40015,1003.31.5
7528,70020,8005.74.120,50017,1004.12.2
8038,40024,6007.76.829,70020,8005.94.2

Test conditions based on ANSI/AHRI Standard 440. TC = Total Cooling Capacity. SC = Sensible Cooling Capacity. All duties based on 208V/1Ph/60Hz supply voltage and high fan speed except where stated otherwise. Pressure drops are coil only, excluding valves.

Table 9.1 - Heating Performance - Chilled Water Units with Optional Heating Coil

Model Filter Hot Water 180°F Inlet / 160°F Outlet
70°F Entering Air DB 60°F Entering Air DB 50°F Entering Air DB
Capacity (btuh) PD (psi) Flow (gpm) Capacity (btuh) PD (psi) Flow (gpm) Capacity (btuh) PD (psi) Flow (gpm)
CCW 08STD.17,1002.81.718,9003.31.920,6003.82.0
MERV 1013,4001.81.314,7002.11.516,1002.51.6
CCW 12N/AN/AN/AN/AN/AN/AN/AN/AN/A
CCW 18STD.27,3001.12.730,0001.33.032,8001.53.3
MERV 1024,8000.92.527,3001.12.729,8001.33.0
CCW 20STD.27,9001.12.830,7001.43.133,5001.63.3
MERV 1024,8000.92.527,3001.12.729,8001.33.0
CCW 33STD.41,2001.44.145,3001.74.549,4002.04.9
MERV 1042,3001.54.245,9001.74.649,3002.04.9
CCW 36STD.45,2001.74.549,8002.05.054,3002.35.4
MERV 1042,3001.54.245,9001.74.649,3002.04.9

All duties based on 208V/1Ph/60Hz supply voltage and high fan speed except where stated otherwise. Pressure drops are coil only, excluding valves.

Table 9.2 - Heating Performance - Chilled Water Units with 2-Pipe Changeover

Model Filter Hot Water 180°F Inlet / 160°F Outlet
70°F Entering Air DB 60°F Entering Air DB 50°F Entering Air DB
Capacity (btuh) PD (psi) Flow (gpm) Capacity (btuh) PD (psi) Flow (gpm) Capacity (btuh) PD (psi) Flow (gpm)
CCW 08STD.21,0006.32.123,1007.52.325,1008.82.5
MERV 1014,2003.11.415,6003.71.617,0004.31.7
CCW 12STD.29,0003.12.931,9003.73.234,8004.43.5
MERV 1017,4001.21.719,1001.51.920,8001.72.1
CCW 18STD.55,1003.65.560,4004.26.065,6004.96.5
MERV 1049,2002.94.953,9003.45.458,6004.05.8
CCW 20STD.55,1003.65.560,4004.26.065,6004.96.5
MERV 1049,2002.94.953,9003.45.458,6004.05.8
CCW 33STD.80,5005.58.088,2006.48.895,9007.59.5
MERV 1076,5005.07.683,9005.98.491,2006.89.1
CCW 36STD.89,3006.68.997,9007.89.7106,4009.110.6
MERV 1076,5005.07.683,9005.98.491,2006.89.1

All duties based on 208V/1Ph/60Hz supply voltage and high fan speed except where stated otherwise. Pressure drops are coil only, excluding valves.

Table 10.1 - Heating Performance - DX Cooling and Heat Pump Units with Optional Heating Coil

Model Entering Air DB °F @ 50% RH Hot Water 180°F Inlet / 160°F Outlet
Heating Capacity BTU/h Flowrate GPM Pressure Drop PSI
CSD/CSH 185046,3894.81.3
6042,5984.41.1
7038,7464.00.9
CSD/CSH 245050,2795.31.5
6046,1534.81.2
7041,9934.41.0
CSD/CSH 305067,9127.13.3
6062,2776.52.8
7056,6095.92.3
CSD/CSH 365071,6367.53.6
6065,6406.93.1
7059,6006.22.6
CSD/CSH 425077,3868.14.2
6070,8037.43.5
7064,2686.73.0

All duties based on high fan speed except where stated otherwise. Pressure drops are coil only, excluding valves.

Unit Dimensional Data

The following figures provide dimensional information for different chassis sizes of the Ceiling Cassette units.

Figure 11.1 - Dimensions - Small Chassis: CCW08 and CCW12 (in inches)

This diagram shows the overall dimensions and port locations for the small chassis models CCW08 and CCW12. Key labeled components include:

  • 1: CW OUTLET
  • 2: CW INLET
  • 3: HW INLET (Optional)
  • 4: HW OUTLET (Optional)
  • 5: BRANCH DUCT OPENING (x3)
  • 6: FRESH AIR INTAKE (x2)
  • 7: PUMP INSPECTION PORT
  • 8: CONDENSATE DRAIN
  • 9: CONTROL PANEL
  • 10: MOUNTING BRACKET
  • 11: ELECTRIC HEAT FUSE BOX OR TRANSFORMER

Diagram shows top, side, and front views with various dimensions indicated.

Figure 12.1 - Dimensions - Medium Chassis: CCW18 and CCW20 (in inches)

This diagram illustrates the dimensions and port locations for the medium chassis models CCW18 and CCW20. Key labeled components include:

  • 1: CW OUTLET
  • 2: CW INLET
  • 3: HW INLET (Optional)
  • 4: HW OUTLET (Optional)
  • 5: FRESH AIR INTAKE (x3)
  • 6: BRANCH DUCT OPENING (x4)
  • 7: PUMP INSPECTION PORT
  • 8: CONDENSATE DRAIN
  • 9: CONTROL PANEL
  • 10: MOUNTING BRACKET
  • 11: ELECTRIC HEAT FUSE BOX OR TRANSFORMER

Diagram shows top, side, and front views with various dimensions indicated.

Figure 13.1 - Dimensions - Large Chassis: CCW33 and CCW36 (in inches)

This diagram details the dimensions and port locations for the large chassis models CCW33 and CCW36. Key labeled components include:

  • 1: CW OUTLET
  • 2: CW INLET
  • 3: HW INLET (Optional)
  • 4: HW OUTLET (Optional)
  • 5: FRESH AIR INTAKE (x3)
  • 6: BRANCH DUCT OPENING (x4)
  • 7: PUMP INSPECTION PORT
  • 8: CONDENSATE DRAIN
  • 9: CONTROL PANEL
  • 10: MOUNTING BRACKET
  • 11: ELECTRIC HEAT FUSE BOX OR TRANSFORMER

Diagram shows top, side, and front views with various dimensions indicated.

Figure 14.1 - Dimensions - Medium Chassis: CSD/CSH 18 and CSD/CSH 24 (in inches)

This diagram presents the dimensions and port locations for the medium chassis DX/Heat Pump models CSD/CSH 18 and CSD/CSH 24. Key labeled components include:

  • 1: DX LIQUID LINE
  • 2: DX SUCTION LINE
  • 3: HW INLET (Optional)
  • 4: HW OUTLET (Optional)
  • 5: FRESH AIR INTAKE (x3)
  • 6: BRANCH DUCT OPENING (x4)
  • 7: PUMP INSPECTION PORT
  • 8: CONDENSATE DRAIN
  • 9: CONTROL PANEL
  • 10: MOUNTING BRACKET
  • 11: ELECTRIC HEAT FUSE BOX OR TRANSFORMER

Diagram shows top, side, and front views with various dimensions indicated.

Figure 15.1 - Dimensions - Large Chassis: CSD/CSH 30, CSD/CSH 36 and CSD/CSH 42 (in inches)

This diagram shows the dimensions and port locations for the large chassis DX/Heat Pump models CSD/CSH 30, CSD/CSH 36, and CSD/CSH 42. Key labeled components include:

  • 1: DX LIQUID LINE
  • 2: DX SUCTION LINE
  • 3: HW INLET (Optional)
  • 4: HW OUTLET (Optional)
  • 5: FRESH AIR INTAKE (x3)
  • 6: BRANCH DUCT OPENING (x4)
  • 7: PUMP INSPECTION PORT
  • 8: CONDENSATE DRAIN
  • 9: CONTROL PANEL
  • 10: MOUNTING BRACKET
  • 11: ELECTRIC HEAT FUSE BOX OR TRANSFORMER

Diagram shows top, side, and front views with various dimensions indicated.

Technical Data

Figure 16.1 - Technical Data – DX Cooling Only and Heat Pump Units

DESCRIPTION UNITS Model Digit 2,3 + Model Size
SD/SH 18 SD/SH 24 SD/SH 30 SD/SH 36 SD/SH 42
CONSTRUCTIONMaterial: FasciaHigh Impact Polystyrene (Pearl Grey color), UL94 VO Fire Rating
Material: ChassisGalvanized Steel
EVAPORATORTypeFinned Tube
Quantity11111
Face Areaft²4.04.05.25.25.2
Nominal Airflow - H/M/LCFM590/540/465670/590/540920/800/6801000/920/8001130/1000/920
Discharge4-Way
FANTypeCentrifugal
Quantity11112
Diameterin14.0
Horsepower (per fan)HP1/61/61/61/61/6
REFRIGERATIONNumber of Circuits11111
Refrigerant TypeR-410A
WEIGHTSWeight - Chassislbs6666979797
Weight - Fascialbs1818212121
CONNECTIONSSuction (1)in0.750.750.750.750.75
Liquid (1)in0.3750.3750.3750.3750.375
Condensate (ID)in0.3750.3750.3750.3750.375
FILTRATIONTypeWashable Polyester Foam (Standard)
Sizein11.6 x 23.2 x 0.211.6 x 23.2 x 0.211.6 x 23.2 x 0.211.6 x 23.2 x 0.211.6 x 23.2 x 0.2
Nominal SizeinMERV 10MERV 10MERV 10
Quantity22333
CONDENSATE PUMPMaximum Headin3030303030
Nomincal Flowrategpm0.10.10.10.10.1
Electric Heating CapacitykW3.03.05.05.05.0
OPTIONSMax Supply Air Branch Duct Connectionsqty22222
Supply Air Branch Duct Diameterin5.06.06.06.06.0
Ducted Supply Air Volume (2)CFM115130180200220
Fresh Air Connectionsqty33333
Fresh Air Duct Diameterin3.03.03.03.03.0
Fresh Air Volume (3)CFM6065859095

1. Refrigerant line sizes should always match condensing unit connection sizes. 2. Maximum air volume available through one branch duct 6' long, with Cassette fan(s) at high speed and corresponding fascia aperture closed. 3. Maximum fresh air through all knockouts connected to one 10' long duct with fan at high speed. Fresh air volume will depend on duct configuration, fan speed, and filter type. 4. For electrical data, please refer to the submittal data in Breeze AccuSpec.

Figure 17.1 - Technical Data – Chilled Water Units

DESCRIPTION UNITS Model Digit 2,3 + Model Size
CW08 CW12 CW18 CW20 CW33 CW36
CONSTRUCTIONMaterial: FasciaHigh Impact Polystyrene (Pearl Grey color), UL94 VO Fire Rating
Material: ChassisGalvanized Steel
CHILLED WATER COILTypeFinned Tube
Quantity111111
Face Areaft²1.82.82.82.85.25.2
Nominal Airflow - Standard - H/M/LCFM330/300/260360/330/300600/540/460620/600/540940/850/7401080/940/850
Nominal Airflow - MERV 10 - H/M/LCFM200 / 170 / 160520 / 490 / 450880 / 760 / 690
Discharge4-Way
Unit Water Volumegal0.290.450.450.450.790.79
Maximum Inlet Water Pressurepsi125
FANTypeCentrifugal
Quantity111111
Diameterin12.015.015.015.014.014.0
Horsepower (per fan)HP1/81/61/61/61/61/6
WEIGHTSWeight - Chassislbs406464649797
Weight - Fascialbs181821212121
CONNECTIONSChilled Water Inletin0.6250.8750.8750.8750.8750.875
Chilled Water Outletin0.6250.8750.8750.8750.8750.875
Condensate (ID)in0.3750.3750.3750.3750.3750.375
FILTRATIONTypeWashable Polyester Foam (Standard)
Sizein14.5 x 13.5 x 0.213.0 x 13.0 x 1.011.6 x 23.2 x 0.211.6 x 23.2 x 0.212.0 x 25.0 x 1.012.0 x 25.0 x 1.0
TypeMERV 10MERV 10MERV 10MERV 10
Sizein11.6 x 23.2 x 0.211.6 x 23.2 x 0.212.0 x 25.0 x 1.012.0 x 25.0 x 1.0
Quantity112233
CONDENSATE PUMPMaximum Headin303030303030
Nomincal FlowrateGPM0.10.10.10.10.10.1
Electric Heating CapacitykW1.53.03.03.05.05.0
OPTIONSMax Supply Air Branch Duct Connectionsqty222222
Supply Air Branch Duct Diameterin5.05.06.06.06.06.0
Ducted Supply Air Volume (1)CFM80100125125200220
Fresh Air Connectionsqty223333
Fresh Air Duct Diameterin3.03.03.03.03.03.0
Fresh Air Volume (2)CFM406065659095

1. Maximum air volume available through one branch duct 6' long, with Cassette fan(s) at high speed and corresponding fascia aperture closed. 2. Maximum fresh air through all knockouts connected to one 10' long duct with fan at high speed. Fresh air volume will depend on duct configuration, fan speed, and filter type. 3. For electrical data, please refer to the submittal data in Breeze AccuSpec.