Instruction Manual for LOGICO2 models including: 0473 SMB and Shut Off Valve, 0473, SMB and Shut Off Valve, Shut Off Valve, Off Valve, Valve

smb sov 0473 en in hfe1202 r2 0

libr

Products - Logico2

0473 SMB and shut off valve


File Info : application/pdf, 4 Pages, 446.36KB

PDF preview unavailable. Download the PDF instead.

smb sov 0473 en in hfe1202 r2 0
Installation Instruction
0473 SMB and shut off valve

ENGLISH
Safety mode box with shut off valve for CO2 Safety System.
Important!
Retain this instruction manual for future reference: Please read these instructions carefully prior to start-up and use. Failure to follow any of these instructions could void product warranties. LogiCO2 assumes no responsibility for claims arising out of improper or careless use or handling of it's products.

Function
Safety mode box (SMB) with shut off valve is an accessory for the Mk9 and Mk90 CO2 Safety System that shuts off the CO2 gas distribution in case of a leakage. It consists of a magnetic valve, electronics box and cabling. The Shut off valve is designed for usage of CO2 with a pressure of 0,15 to 30 bar or 2,2 to 435 Psi.
SMB has a 1 meter Cat5 cable from the electronics box, with a blue RJ45 connector that is plugged in to the blue alarm signalling output cable side from either the Mk9 or Mk90 CO2 sensors. When the CO2 sensor indicates a high CO2 concentration, the magnetic valve will shut off the CO2 gas distribution. The valve is failsafe (shuts off at power loss).
The magnetic valve should be installed as early as possible in the CO2 gas distribution chain (close to the CO2 tank) in order to avoid possible CO2 leakage before the safety valve.
Install the electronics box in a suitable place where it is mechanically protected. Remove the cover by turning it counterclockwise 1/8 turn to access the mounting screw holes.

Technical specifications for SMB

Power supply:

Via CO2 Sensor

Relays:

1A/24V AC/DC

Material:

PC/ABS

Operating pressure: 0,15 to 30 bar / 2,2 to 435 Psi

Bursting pressure: >150 bar / 2 175 Psi

Treaded connection: 1/4" -18NPT

Dimensions (WxHxD): 78x78x37 mm / 3"x3"x1.5"

Ingress protection: IP55

Installation
The connection diagram below shows an example of how the SMB with shut off valve can be installed to a CO2 Safety System (Mk9 and Mk90).

Mk9 CO2 Sensor

CO2 Sensor

CO2

LogiCO2 Mk9

Certified by UL Ratings: 24Vdc, 68mA Made in Sweden

DIN Reg. No: 6L002
!

SIGN CO2 SENSOR MK90 EN



&$87,21 &2$/(57

$OWLWXGHVHWWR 'RQHE\

&26HQVRU'RQRWFRYHURUSODFHDQ\WKLQJ LQIURQWRIRURQWRSRIWKHVHQVRU

,QGLFDWLRQ *UHHQ/('

([SODQDWLRQ 8QLWLQRSHUDWLRQ

5HG/(' VHF
5HG/('
5HG/('
<HOORZ/('

&2$ZDUHQHVVLQGLFDWLRQ7KH&2OHYHOLVRYHUSSP1RGDQJHUEXWWKH&2LV XQQDWXUDOO\KLJK7KHGLVSOD\RQWKH&2VHQVRUZLOOVKRZ³+LJK´
/RZ$ODUP+LJKDPELHQW&2FRQFHQWUDWLRQOHYHORU7:$$ODUPSSPK7LPH :HLJKWHG$YHUDJH7KHGLVSOD\RQWKH&2VHQVRUZLOOVKRZ³$ODUP´RU³7:$+LJK$ODUP´ &RQQHFWHGUHPRWHZDUQLQJVWUREHZLOOEHDFWLYDWHG&DOO6HUYLFH
+LJK$ODUP'DQJHURXVO\KLJKDPELHQW&2FRQFHQWUDWLRQOHYHO7KHGLVSOD\RQWKH&2 VHQVRUZLOOVKRZ³+LJK$ODUP´7KHVHQVRUZLOOVWDUWIODVKLQJDQGFRQQHFWHGUHPRWHZDUQLQJ KRUQDQGVWUREHZLOOEHDFWLYDWHG&DOO)LUH'HSDUWHPHQW
&2VHQVRUIDXOW7KHGLVSOD\RQWKH&2VHQVRUZLOOVKRZ³(UURU´ &DOO6HUYLFH

Mk90 CO2 Sensor

CO2 Sensor

CO2

LogiCO2 Mk90

Certified by UL Ratings: 24Vdc, 117mA Made in Sweden

DIN Reg. No: 6L002
!

SIGN CO2 SENSOR MK90 EN



&$87,21 &2$/(57

$OWLWXGHVHWWR 'RQHE\

&26HQVRU'RQRWFRYHURUSODFHDQ\WKLQJ LQIURQWRIRURQWRSRIWKHVHQVRU

,QGLFDWLRQ *UHHQ/('

([SODQDWLRQ 8QLWLQRSHUDWLRQ

5HG/(' VHF
5HG/('
5HG/('
<HOORZ/('

&2$ZDUHQHVVLQGLFDWLRQ7KH&2OHYHOLVRYHUSSP1RGDQJHUEXWWKH&2LV XQQDWXUDOO\KLJK7KHGLVSOD\RQWKH&2VHQVRUZLOOVKRZ³+LJK´
/RZ$ODUP+LJKDPELHQW&2FRQFHQWUDWLRQOHYHORU7:$$ODUPSSPK7LPH :HLJKWHG$YHUDJH7KHGLVSOD\RQWKH&2VHQVRUZLOOVKRZ³$ODUP´RU³7:$+LJK$ODUP´ &RQQHFWHGUHPRWHZDUQLQJVWUREHZLOOEHDFWLYDWHG&DOO6HUYLFH
+LJK$ODUP'DQJHURXVO\KLJKDPELHQW&2FRQFHQWUDWLRQOHYHO7KHGLVSOD\RQWKH&2 VHQVRUZLOOVKRZ³+LJK$ODUP´7KHVHQVRUZLOOVWDUWIODVKLQJDQGFRQQHFWHGUHPRWHZDUQLQJ KRUQDQGVWUREHZLOOEHDFWLYDWHG&DOO)LUH'HSDUWHPHQW
&2VHQVRUIDXOW7KHGLVSOD\RQWKH&2VHQVRUZLOOVKRZ³(UURU´ &DOO6HUYLFH

RJ45 Splitter (blue) 1-1/1-2/1-4
Power Supply

Optional: Relay RCB

CO2 Sensor

CO2

LogiCO2 Mk9

Certified by UL Ratings: 24Vdc, 68mA Made in Sweden

DIN Reg. No: 6L002
!

CO2 Sensor

CO2

LogiCO2 Mk9

Certified by UL Ratings: 24Vdc, 68mA Made in Sweden

DIN Reg. No: 6L002
!

CO2 Sensor

CO2

LogiCO2 Mk9

Certified by UL Ratings: 24Vdc, 68mA Made in Sweden

DIN Reg. No: 6L002
!

CO2 Sensor

CO2

LogiCO2 Mk9

Certified by UL Ratings: 24Vdc, 68mA Made in Sweden

DIN Reg. No: 6L002
!

CO2 Sensor

CO2

LogiCO2 Mk9

Certified by UL Ratings: 24Vdc, 68mA Made in Sweden

DIN Reg. No: 6L002
!

CO2 Sensor

CO2

LogiCO2 Mk9

Certified by UL Ratings: 24Vdc, 68mA Made in Sweden

DIN Reg. No: 6L002
!

RJ45 Splitter (red) 1-1/1-2/1-4
Possibility to expand with up to twelve Mk9/ Mk90 CO2 Sensors. Observe! Use Power Barriers in accordance with instructions.

Horn/Strobe

! WARNING !

CO2 ALERT

CARBON DIOXIDE GAS
DO NOT ENTER THIS AREA WHEN SIREN IS SOUNDING AND LIGHT IS FLASHING!
Emergency Actions · Evacuate the Area Immediately. · Call the Fire Department from
outside of the building.
Non-Emergency Action · If light only is flashing,
call CO2 Service at:

HFE1061 EN

! WARNING !

CO2 ALERT

CARBON DIOXIDE GAS
DO NOT ENTER THIS AREA WHEN SIREN IS SOUNDING AND LIGHT IS FLASHING!
Emergency Actions · Evacuate the Area Immediately. · Call the Fire Department from
outside of the building.
Non-Emergency Action · If light only is flashing,
call CO2 Service at:

HFE1061 EN

Mk9 Central Unit

Gas Monitor Central Unit

LogiCO2

Certified by UL Ratings: 24Vdc, 32mA Made in Sweden

Mk9

!

Optional: SMB & Shut off valve

SIGN C-U MK9 EN

CO2 Safety System - Mk9 What to do in case of an ALARM?
1. Keep Calm! 2. Turn off the sounding alarm on the Central Unit by pressing the RESET button on the front. 3. Check the type of alarm and which Sensor is giving the alarm by following the instructions below.

INDICATION
Central Unit: · The red diode is ON · Constant sound signal Display: · Sensor number, alternating
ALARM and CO2 %
Central Unit: · The red diode is blinking · Beeping sound signal Display: · Sensor number, alternating
ALARM and CO2 %
Central Unit: · The red diode is blinking · Beeping sound signal Display: · Sensor number, alternating
ALARM and CO2 ppm value
CO2-Sensor: · Beeping sound signal every
5 seconds Display: · High and CO2 %
Central Unit: · The yellow diode is blinking · Beeping sound signal Display: · Sensor number, (Fault
information)
After an alarm, always reset the system.
To insure that communication, warning lamps and sounders function.

CAUSE

ACTION

HIGH-ALARM !
TAKE PRECAUTIONS
High concentration of CO2

DO NOT ENTER the risk zone.
Evacuate the area. Call the fire department.

LOW-ALARM High concentration of CO2

A service technician should only enter the room under the supervision of another person.
Open the doors and the windows as much as possible.

TWA-ALARM There is a small CO2 leak that has lasted for over
8 hours
CO2 AWARENESS INDICATION

Open the doors and the windows as much as possible. Find and stop the leakage, if not found, call service.
Phone: ..................................
Be aware that the CO2 concentration is over 5000 ppm. There is no danger.

SYSTEM FAULT
ALARM RESET ALARM TEST

Check the manual, communication cables and CO2-Sensor. If no fault is found, call service.
Phone: ..................................
Press reset button until "Alarm cleared!" is shown in the display.
Press reset button until "Testing system..." is shown in the display.

Sensor 1 2 3 4 5 6 7 8

Place

CO2

2

Annual function control of the safety valve
To test the safety valve, make sure that the red diode on the valve is on, indicating that the valve is powered on and open. Test the opening and closing of the valve by pressing the red test button on the SMB connection box. The red diode on the valve should turn off and you should hear a clear clicking sound.

Annual function and installation check of the SMB and shut off valve

Checklist SMB and shut off valve

YES NO

Is the SMB shut off valve installed on the downside from the emergency shut off valve?

Is the red diode on the shut off valve ON?

Does the red diode on the shut off valve turn on and off when the red test button is pressed?

Does the valve make a clicking sound when the red test button is pressed?

3

Manufactured by:
LogiCO2 International AB Box 9097 400 92 Gothenburg, Sweden

E-mail: info@logico2.com Web: www.logico2.com

© 2021-09-07 R2.0 LogiCO2 HFE1202 EN

