TM Installation and Instruction Manual

SURFACE MOUNT DUAL SENSE MOTION SENSOR HIM14

1. Technical Specifications

Product type Operating voltage Switched power Power consumption Detection angle Detection area (Max.)*
Detection range Hold time Stand-by time Stand-by dimming level Daylight threshold Warmming up time Operating temperature Sensor mode

Dual sense DALI sensor (HF and PIR, daylight harvest) 120~277VAC 50/60Hz Maximum 20pcs devices, maximum 40mA < 1W 360o Installation Height : 6m
Detection Range (Ø) :12m
10% / 50% / 75% / 100% 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min 0s / 10s / 1min / 5min / 10min / 30min / 1h / + 10% / 20% / 30% / 50% 50 ~ 500Lux, Disable 30s -20oC ~ +55oC PIR, HF, PIR+HF, PIR / HF

2. Installation
Warnings: 1. Installation must be carried out by a
qualified engineer in accordance with local regulations. 2. Disconnect supply before installing. 3. Install to a solid surface - vibrations may cause mis-triggering. 4. Ensure environmental conditions are suitable for electronic equipment
Blind A
Blind
B

C - Surface box B - Facia Cover

Infrared receiver HF Sensor module

PIR
Photocell LED indicator

Rotary switch preset

Sensor mode selection

A - Control Board

11 43.5 64.7 69.1

Note: the blinds are optional, they may be inserted behind the lens for focussing the detection range.

3. Rotary Switch Settings

A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels available:

Rotary switch preset (Please see the location in 2. Installation)

Channel
0 1 2 3 4 5 6 7 8 9 A B C D E F

Detection range
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

Hold time
5s 1min 5min 5min 5min 5min 10min 10min 10min 10min 20min 20min 30min 30min 30min 5s

Stand-by time
10s 5min 10min + + + 30min + + + 1h + + + + 10s

Stand-by dimming level
10% 10% 10% 10% 10% 30% 10% 10% 10% 30% 10% 30% 10% 30% 50% 10%

Daylight threshold
Disable 50Lux 50Lux 75Lux 100Lux 200Lux 50Lux 75Lux 100Lux 200Lux 100Lux 200Lux 100Lux 200Lux 400Lux 100Lux

Note: settings can also be changed by remote control HRC-11. The last action controls.

5. Functions
5.1 Daylight Harvest (Daylight Regulating)
The built-in daylight sensor can measure ambient natural light, and calculate how much electrical light is needed to reach the target lux level. The demand is given to the LED driver by DALI signal, so as to deliver the needed amount of electric light. The target lux level can be adjusted by remote control or long press on the push switch.

Light level

Hold time

Normal Electric Light

Energy Saving Zone

Stand-by time

Daylight controlled light Natural light

0

24 Time (hrs)

5.2 Lux Off Function
The light dims to minimum level even switches off completelly if ambient daylight is sufficient (natural light level exceeds target lux level), no matter it is during hold-time or stand-by time, with or without motion. Note: if the stand-by time is preset at "+", the light never turns off even when natural light is sufficient.

56 109
38.6

29 50.2 55.2

Note:We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

Direct junction "J" box mounting
a. Separate control board (A) from facia (B) & junction box (C).
b. Make electrical connections to control board (A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box. d. Set-up sensor modes as per sections 3 & 4
of this manual. e. Clip facial plate (B) to control board (A).

Surface mount assembly
a. Separate control board (A) from facia (B) & Surface box (C).
b. Securely mount surface box (C) to a flat and solid surface.
c. Make electrical connections to control board (A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of this manual.
e. Secure control board (A) to surface box (C). f. Clip facial plate (B) to control board (A).

C 56
A B

C 56
A B

4. Sensor Mode Selection
Sensor mode can be easily selected by choosing the correct combination of the DIP switches (see table below):

12

I

HF

II

PIR

III

HF+PIR

IV

HF/PIR

HF+PIR: Light is on when both HF and PIR sensors are activated.
HF/PIR: Light is on when HF or PIR sensors are activated.

HIM14-20190104-A1

5.3 Manual Override (Push Function)
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off the lights manually, or adjust the target lux level. This makes the product more user-friendly and offers more options to fit for extra-ordinary demands. * Short push (<1s): on/off function; ON ¹ OFF: the light turns off immediately and cannot be lighten for a certain time (equals to
hold time preset) even movement is detected. After this period, the sensor goes back to auto sensor mode. OFF ¹ ON: the light turns on and goes to auto sensor mode. * Long push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment
by remote control and push switch can overwrite each other, the last adjustment remains in memory.
5.4 Semi-auto Function (Absence Detection)
The motion sensor is employed, but only activated on the manual press of the push switch. With presence, the light remains on and can interact with ambient natural light, then dims down in absence, eventually switching off automatically after the stand-by time has expired. Note: end-user can choose either function 5.3 or 5.4 for application. Default function is 5.3.
5.5 Synchronization Function
By connecting the "SYNC" terminals in parallel (see wiring diagram), no matter which sensor detects motion, all HIM14 in the group will turn on the lights when surrounding natural light is below the daylight threshold. The sensor module is shared and the detection area could be widely enlarged in this way.
7. Detection Pattern

6. Wiring Diagram
SYNC P N L HIM14 DA+ DA-

- + L N LED LED driver DA- DA+

Max. 20pcs

L N
SYNC P N L HIM14 DA+ DA-

- + L N LED LED driver
DA- DA+

Max. 20pcs

Note: if neither function 5.3 nor 5.4 is desired, simply leave the "push" terminal disconnected.

PIR

PIR

PIR

A

B

HF

HF

HF

3m

3m

3m

HFPIwR atalknignegnatiacrlomssov8emment 10m

PIR tangential movement 5m

HF walking across 8m

4m HF walking across 8m
PIR tangential movement 10m

8. Description of the Button Functions (remote control HRC-11)

4

1

2

5

3

6 7

8

9

10

11

12

& A

4h

h

4h

13

14 HRC-11

Permanent ON/OFF [button 1 ] Press button 1 to select permanent ON or permanent OFF mode. * Press button 2 / 4 to resume automatic operation. The mode will change to AUTO Mode after power failure.
RESET [ button 2 ] Press button 2 , all settings go back to the rotary switch settings. Sensor mode return to DIP switch settings.
Shift [ button 3 ] Press button 3 , the LED on the top left corner flashes for indication. All values / settings in RED are in valid for 20 seconds.
Auto Mode [ button 4 ] Press button 4 to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
Semi-auto Mode [ button 3 & 4 ] 1. Press button 3 Shift (the red LED flashes for indication), 2. press button 4 to initiate semi-auto mode. The fixture is manually on
by push-switch and automatically off in semi-auto mode.
Power output [ button 5 ] Press button 5 , the light output shifts between 80% and 100%. Note: the function of "Sensor off" and "Twilight" are disabled.
Brightness +/- [ button 6 ] Press button 6 to adjust light brightness to reset the target lux level.
Scene prog. [ zone 7 ] (One-key-commissioning)
1. Press button "Start" to program. 2. Select the buttons in 8 "Detection range", 9 / 10 "Daylight threshold",
11 "Hold time", 12 "Stand-by time", 13 "Stand-by dimming level" to set all parameters. 3. Press button "Memory" to save all the settings programmed in the remote control. 4. Press button "Apply" to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +, stand-by dimming level 30%, steps should be: Press button 7 Start, button 8 100%, 10 Disable, 3 Shift, 11 5min, 3 Shift, 12 + , 13 30%, 7 Memory. By pointing to the sensor unit(s) and pressing 7 Apply, all settings are passed on the sensor(s).
Detection range [ zone 8 ] Press buttons in zone 8 to set HF detection range at 100% / 75% / 50% / 10%.

Hytronik Industrial Ltd. | www.hytronik.com 3rd Floor, block C, complex building, 155#, Bai'gang road south, Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023 Tel: 86-752-2772020 Fax: 86-752-2777877

Daylight threshold [ zone 9 ] Press buttons in zone 9 to set the daylight sensor at 50Lux / 100Lux / 300Lux / 500Lux or Disable as threshold / target Lux level. Note: 2Lux / 10Lux are disabled.
To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button 3 Shift at first.
Ambient daylight threshold [ button 10 ] 1. Press button 3 Shift, the red LED flashes for indication. 2. Press button 10, the ambient lux level is sampled and set as
daylight threshold / target Lux level.
Hold time [ zone 11 ] Press buttons in zone 11 to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min. Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button
3 Shift at first. 2. 2s is for test purpose only, stand-by time and daylight
sensor settings are disabled in this mode. * To exit from Test mode, press button 2 or any button in zone 11 .
Stand-by time [ zone 12 ] Press buttons in zone 12 to set the stand-by time at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +. Note: "0s" means on/off control; "+" means bi-level control, 100%
on when motion detected, and remains at the stand-by dimming level when no presence after hold-time.
Stand-by dimming level [ zone 13 ] Press buttons in zone 13 to set the stand-by dimming level at 10% / 20% / 30% / 50%.
Daylight harvest auto-configuration function 1. Press button "Shift", the red LED is on for indication. 2. Select a time period and the sensor will do light level measurement and determine/save the lowest light level (commission line) with 100% light on, so as to set the target lux level automatically. Note: 1. Make sure the light level measurement covers the night time.
2. The fixture will go into sensor mode after the measurement, all sensor settings remain unchanged
Dual tech & RF mode [ zone 14 ] 1. Press buttons in zone 14 to select sensor technology.
HF+PIR: Light is on when both HF and PIR sensors are activated. HF/PIR: Light is on when HF or PIR sensors are activated. 2. Learn / Erase, Transmit, RX100% and RX STBY% are disabled.
HIM14-20190104-A1



References

Adobe PDF library 15.00 Adobe Illustrator CC 23.0 (Windows)