6952SGCBO / 6952SRCBO / 6952RCBORC / 6952RGCBO LED Exit Sign/Emergency Light Combo User Manual

Lavex

User Manual

Aug 26, 2024 — Do not use the equipment outdoors. • Mount the equipment securely at heights where it will not be tampered with by unauthorized personnel.

6 days ago —

6 days ago — User Manual. #6952SGCBO / 6952SRCBO / 6952RCBORC / 6952RGCBO. Slim. LED Exit Sign/. Emergency Light Combo with Battery Backup. PLEASE READ ENTIRE MANUAL BEFORE ...

PDF preview unavailable. Download the PDF instead.

6952sgcbo-6952srcbo-6952rcborc-952rgcbo manual ?srsltid=AfmBOoo54pwbGmpaGzKG rX-4urC2irEGihUxnv3l0cxRMLBpB1A0JK
User Manual
#6952SGCBO / 6952SRCBO / 6952RCBORC / 6952RGCBO
Slim
LED Exit Sign/ Emergency Light Combo
with Battery Backup

PLEASE READ ENTIRE MANUAL BEFORE USE

08/2024

User Manual

Table of Contents
Safety Instructions .............................................. 2 Important Information ......................................... 2 Battery................................................................................... 2 Replacement Lights .............................................................. 2

Installation Instructions........................................................ 3 Remote Lights....................................................................... 5 Operation Instructions ......................................................... 5

Safety Instructions
· Do not use the equipment outdoors. · Mount the equipment securely at heights where it will not be tampered with by unauthorized personnel. · Do not mount near gas or electric heaters. · Cap unused wires with the enclosed wire nuts or another approved method. · Do not use this equipment for anything other than its intended purpose. · Only use manufacturer approved hardware, not doing so will void the product listing and warranty and may
cause an unsafe condition. · Turn off power at the breaker box before servicing sign. · Use caution when servicing batteries. · Only qualified personnel should service this equipment. · Ensure wire terminations are secure and wires are properly tucked into appropriate wire channels.

Important Information
· To check, press the "TEST" button. The LED lights should turn on. · During a power failure, the LED lights will automatically turn on for at least 90 minutes. · Test the emergency lighting system monthly for at least 30 seconds and annually for 90 minutes. · Refer to local codes for additional requirements.
Battery
· The battery in this unit may not be fully charged. After connecting the unit to electricity, the battery will take up to 24 hours to be fully charged.
Replacement Lights
· Only use lights specified in the exit sign. Using other light types may result in transformer damage or unsafe conditions.

WWW.LAVEX.COM

2

User Manual

Installation Instructions
· Unit wiring must be completed by a certified electrician.
· Use flexible conduit only.
· It is recommended to put all emergency lighting on a dedicated breaker. Refer to local and state guidelines for your specific requirements.
· If your building has 277VAC, it is recommended to use that (red wire). If it does not, use the 120VAC (black wire). Both require using the neutral (white wire).

277V 120V

277V 120V

277VAC

120VAC

POWER

UNIT

POWER

UNIT

SOURCE

SOURCE

NEUTRAL

NEUTRAL

Electrical Diagrams

6952SRCBO / 6952SGCBO

YELLOW (+) BLUE (-)

LED
RED (+) BLACK (-) BATTERY 2.4V 1Ah

PCB/LED BOARD

RED (+) BLACK (-)
BATTERY 1.2V 1Ah

READY LIGHT

YELLOW (+) BLUE (-)

LED

TEST

RED 120V~277V WHITE (COMM)

POWER SUPPLY

6952RGCBO

WHITE (COMM) BLACK (120V) RED (277V)

TRANSFORMER

PCB/LED BOARD
BLUE (-) LED
YELLOW (+)

TEST BLUE (-) LED YELLOW (+)
(+) (-) "READY" LIGHT
BATTERY

6952RCBORC

WHITE (COMM) BLACK (120V) RED (277V)

TRANSFORMER

WWW.LAVEX.COM

PCB/LED BOARD
BLUE (-) LED
YELLOW (+)

BLUE (-) YELLOW (+)

TO REMOTE HEAD

TEST LED

(+) (-) "READY" LIGHT BATTERY

3

User Manual

1. Turn off AC power to the installation area.
2. Remove the Face Plate of the Unit.
3. Choose Mounting Configuration: Decide on end or wall mount. Plug any remaining holes with the appropriate plugs found in the box.

Fig. 1

J-BOX BRACKET

4a. Ceiling Mount (Fig. 1)

a. Secure the Bracket: Feed the source wires through the

277V

bracket and secure the bracket to the j-box.

CANOPY

b. Connect the Wires: Run the connection wires through the canopy and connect with the source wires.

BATTERY

Note: If your building has 277VAC, it is recommended to use that (red) If it does not, use the 120VAC (black). Both require using the neutral (white).

c. Attach the Canopy: Use the screws to attach the canopy to the bracket.

d. Attach the Housing: Snap the housing onto the canopy.

4b. Wall Mount (Fig. 2)
a. Knock Out: Knock out the center hole and the screw holes that match your j-box in the rear of the housing
b. Secure the Housing: Feed the source wires through the center hole and secure the housing to the j-box with screws.
c. Connect the Wires: Connect with the wires. Note: If your building has 277VAC, it is recommended to use that (red). If it does not, use the 120VAC (black). Both require using the neutral (white).

Fig. 2

5. Turn On the Power: Flip the circuit breaker back on for the installation area.
6. Connect the Battery: Insert the battery terminal wire into the two-pin male connector on the circuit board (Fig. 2). Note: Only connect the battery once AC power is available.
7. Secure the Faceplate: Secure the faceplate to the housing and remove the proper arrow as required.

BATTERY

J-BOX

FIXTURE

120V
120V 277V

WWW.LAVEX.COM

4

User Manual
Remote Lights
(6952RCBORC)
· Use yellow and blue wires for remote fixture(s). Route wires outside of the fixture separately or with AC supply wires.
· Make sure to keep all wires out of the way of the EXIT LEGEND so there are no shadows.
Operation
· Automatic Operation: During an electrical power failure, the LED lights will automatically turn on for a minimum of 90 minutes.
· Testing: To test, press the "TEST" switch. The emergency LED lights will illuminate. When the switch is released, the lights will turn off.