CompactLogix 5380 Controllers Specifications

The CompactLogix 5380 controllers are part of the Logix5000 family of controllers, offering a scalable solution for various applications. These controllers are designed for DIN rail mounting.

CompactLogix 5380 controllers can monitor and control local and remote I/O modules, as well as other devices connected via an EtherNet/IP network. Key functionalities include:

Summary of Changes

This publication revision includes information for the following CompactLogix 5380 controllers: 5069-L350ERM, 5069-L380ERM, and 5069-L3100ERM.

Features - CompactLogix 5380 Controllers

Feature5069-L306ER, 5069-L306ERM5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM5069-L320ER, 5069-L320ERM5069-L330ER, 5069-L330ERM5069-L340ER, 5069-L340ERM5069-L350ERM5069-L380ERM5069-L3100ERM
Controller tasks32 tasks, 1000 programs/task, All event triggers32 tasks, 1000 programs/task, All event triggers
Built-in communication ports1 USB port, 2 EtherNet/IP ports1 USB port, 2 EtherNet/IP ports
USB port communicationUSB 2.0, Type B, Full speed (12 Mbps) - Programming, configuration, firmware flash, and on-line edits onlyUSB 2.0, Type B, Full speed (12 Mbps) - Programming, configuration, firmware flash, and on-line edits only
Ethernet performance10 Mbps, 100 Mbps, 1 Gbps, Full Duplex only10 Mbps, 100 Mbps, 1 Gbps, Full Duplex only
EtherNet/IP modes supportedDual-IP mode, Linear/DLR modeDual-IP mode, Linear/DLR mode
Ethernet/IP network topologies supportedDLR, Star, LinearDLR, Star, Linear
EtherNet/IP nodes supported, max1624405055607080
Socket interfaces supported, max3232
Integrated motion controllerOnly controllerAs many as 2 axesAs many as 4 axesAs many as 8 axesAs many as 16 axesAs many as 20 axesAs many as 24 axesAs many as 28 axesAs many as 32 axes
Programming languagesLadder Diagram (LD), Structured Text (ST), Function Block Diagram (FBD), Sequential Function Chart (SFC)Ladder Diagram (LD), Structured Text (ST), Function Block Diagram (FBD), Sequential Function Chart (SFC)
Integrated safetyN/AN/A

Technical Specifications

Attribute5069-L306ER, 5069-L306ERM5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM5069-L320ER, 5069-L320ERM5069-L330ER, 5069-L330ERM5069-L340ER, 5069-L340ERM5069-L350ERM5069-L380ERM5069-L3100ERM
Controller capacity0.6 MB1 MB2 MB3 MB4 MB5 MB8 MB10 MB
Optional nonvolatile memory1784-SD1 card, 1784-SD2 card (shipped with the controller)1784-SD1 card, 1784-SD2 card (shipped with the controller)
Local I/O modules, max881631 (4)31313131
Module Power bus (MOD Power) voltage range18...32V DC18...32V DC
Module Power bus (MOD Power) current, max450 mA450 mA
Module Power bus (MOD Power) inrush850 mA for 125 ms850 mA for 125 ms
Module Power bus (MOD Power) Passthrough voltage range18...32V DC18...32V DC
Module Power bus (MOD Power) current rating, max(1)9.55 A9.55 A
Sensor Actuator (SA) Field Power voltage ranges0...32V DC, 0...240V AC, 47...63 Hz (ATEX/IECEX, 125V AC max)0...32V DC, 0...240V AC, 47...63 Hz (ATEX/IECEX, 125V AC max)
Sensor Actuator (SA) Field Power current, max10 mA (DC power), 25 mA (AC power)10 mA (DC power), 25 mA (AC power)
Sensor Actuator Power bus (SA Power) Passthrough voltage ranges0...32V DC, 0...240V AC, 47...63 Hz (ATEX/IECEX, 125V AC max)0...32V DC, 0...240V AC, 47...63 Hz (ATEX/IECEX, 125V AC max)
Sensor Actuator Power bus (SA Power) current rating, max(2)9.95 A (DC power), 9.975 A (AC power)9.95 A (DC power), 9.975 A (AC power)
Power dissipation, max8.5 W8.5 W
Thermal dissipation, max29 BTU/hr29 BTU/hr
Isolation voltage300V (continuous), Basic Insulation Type, SA and MOD Power to Backplane; 300V (continuous), Basic Insulation Type, SA to MOD Power; 300V (continuous), Basic Insulation Type, Ethernet to Backplane; 300V (continuous), Double Insulation Type, Ethernet to MOD Power; 300V (continuous), Double Insulation Type, Ethernet to SA Power; 50V (continuous), Functional Insulation Type, Ethernet to USB; 300V (continuous), Basic Insulation Type, USB to Backplane; 300V (continuous), Double Insulation Type, USB to MOD Power; 300V (continuous), Double Insulation Type, USB to SA Power. No isolation between Ethernet ports. Type tested at 1500V AC for 60 s.300V (continuous), Basic Insulation Type, SA and MOD Power to Backplane; 300V (continuous), Basic Insulation Type, SA to MOD Power; 300V (continuous), Basic Insulation Type, Ethernet to Backplane; 300V (continuous), Double Insulation Type, Ethernet to MOD Power; 300V (continuous), Double Insulation Type, Ethernet to SA Power; 50V (continuous), Functional Insulation Type, Ethernet to USB; 300V (continuous), Basic Insulation Type, USB to Backplane; 300V (continuous), Double Insulation Type, USB to MOD Power; 300V (continuous), Double Insulation Type, USB to SA Power. No isolation between Ethernet ports. Type tested at 1500V AC for 60 s.

Dimensions and Mounting

Weight, approx: 0.768 kg (1.693 lb)

Dimensions (HxWxD), approx: 143.97 x 98.10 x 136.81 mm (5.67 x 3.86 x 5.39 in.)

Location: DIN rail mount (horizontal mount only)

DIN rail: Compatible zinc-plated, chromate steel DIN rail (EN50022 - 35 x 7.5 mm).

Removable terminal block: RTBs are available in separately ordered 5069 RTB kits. The MOD power connection uses a 4-point RTB, and the SA power connection uses a 6-point RTB.

Temperature code: North American T4, ATEX T4, IECEx T4.

Environmental Specifications

CompactLogix 5380 Controllers

AttributeSpecifications
Temperature, operating0°C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, nonoperating-40...+85 °C (-40...+185 °F)
Temperature, surrounding air, max60 °C (140 °F)
Relative humidity5...95% noncondensing
Vibration5 g @ 10...500 Hz
Shock, operating30 g
Shock, nonoperating50 g
EmissionsIEC 61000-6-4
ESD immunity6 kV contact discharges, 8 kV air discharges
Radiated RF immunity10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz; 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz; 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz; 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B immunity+ 4 kV at 5 kHz on power ports; ± 2 kV at 5 kHz on Ethernet ports
Surge transient immunity± 1 kV line-line (DM) and ± 2 kV line-earth (CM) on power ports; ± 2 kV line-earth (CM) on Ethernet ports
Conducted RF immunity10 Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Voltage variation10 ms interruption on MOD Power port

1784-SD1, 1784-SD2 Cards

Attribute1784-SD11784-SD2
Temperature, operating0°C < Ta < +60 °C (+32 °F < Ta < +140 °F)-40...+85 °C (-40...+185 °F)
Temperature, storage-40...+85 °C (-40...+185 °F)-65...+150 °C (-85...+302 °F)
Relative humidity5...95% noncondensing5...95% noncondensing
Vibration15 g peak to peak15 g peak to peak
Shock, operating30 g30 g
Shock, nonoperating50 g50 g
EmissionsIEC 61000-6-4IEC 61000-6-4
ESD immunity6 kV contact discharges, 8 kV air discharges6 kV contact discharges, 8 kV air discharges
Radiated RF immunity10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz; 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz; 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz; 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz; 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz; 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz; 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

Certifications

CompactLogix 5380 Controllers

Certification (1)Specifications
c-UL-usUL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CEEuropean Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements; EN 61000-6-2; Industrial Immunity; EN 61000-6-4; Industrial Emissions; EN 61131-2; Programmable Controllers (Clause 8, Zone A & B). European Union 2006/95/EC LVD, compliant with: EN 61010-2-201; Control Equipment Safety Requirements.
RCMAustralian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions.
ExEuropean Union 94/9/EC ATEX Directive, compliant with: EN 60079-0; General Requirements; EN 60079-15; Potentially Explosive Atmospheres, Protection "n"; II 3 G Ex nA IIC T4 Gc; DEMKO 15 ATEX 1455X (when used at or below 125V AC). IECEx System, compliant with: IEC 60079-0: General Requirements; IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"; II 3 G Ex nA IIC T4 Gc; IECEX UL 15.0007X (when used at or below 125V AC).
KCKorean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3.
EtherNet/IPODVA conformance tested to EtherNet/IP specifications.

1784 Memory Cards

Certification (1)Specifications
CEEuropean Union 2004/108/EC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions; EN 61326-1; Meas./Control/Lab., Industrial Requirements; EN 61000-6-2; Industrial Immunity; EN 61131-2; Programmable Controllers (Clause 8, Zone A & B).
RCMAustralian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions.
KCKorean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3.

Controller Minimum Spacing Requirements

The minimum distance between the CompactLogix 5380 system and enclosure walls, wireways, and adjacent equipment varies based on the current operating temperature. The minimum distance on all sides of the system is as follows:

IMPORTANT: CompactLogix 5380 systems can only be mounted horizontally.

Controller Dimensions

Visual representation of controller dimensions:

Top View: Shows the controller with end cap and I/O modules.

Side View: Shows the controller mounted on a DIN rail.

Front View: Displays the controller with its ports and indicators.

Overall Dimensions:

Controller Use With Other Devices

Your controller can control and communicate with the following devices:

Control I/O Modules

The CompactLogix 5380 controllers can monitor and control local and remote I/O modules.

Local I/O Modules

A CompactLogix 5380 system uses 5069 Compact I/O modules as its local I/O modules. The number of local I/O modules supported varies by controller catalog number:

Cat. No.Local 5069 Compact I/O Modules Supported, Max
5069-L306ER, 5069-L306ERM8
5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM8
5069-L320ER, 5069-L320ERM16
5069-L330ER, 5069-L330ERM(1)31
5069-L340ER, 5069-L340ERM31
5069-L350ERM31
5069-L380ERM31
5069-L3100ERM31

(1) When using Logix Designer application version 29.00.00, the number of local I/O modules is limited to 16. With version 30.00.00 or later, support increases to 31 local I/O modules.

Remote I/O Modules

The controller can connect to remote I/O modules over an EtherNet/IP network. For optimal performance, use 5069 Compact I/O modules for remote I/O.

Module TypeI/O Module Family
Chassis-based I/O1746 SLC I/O, 1756 ControlLogix I/O, 1769 Compact I/O, 5069 Compact I/O
In-cabinet I/O1734 POINT I/O, 1794 FLEX I/O
On-Machine I/O1732 ArmorBlock I/O, 1738 ArmorPOINT I/O

Communicate with Display Devices

The controller can communicate with these display devices over an EtherNet/IP network:

Device TypeDisplay
Industrial computersAllen-Bradley integrated-display rotating media (HDD) and solid-state (SSD) computers; Allen-Bradley integrated-display computers with keypad; Allen-Bradley non-display computers
Graphic terminalsPanelView Plus and PanelView CE terminals; PanelView standard terminals
Message displaysInView message displays

Communicate with Other Controllers

The controller can communicate with these programmable controllers:

Controller TypeController Family
Programmable automation controllerCompactLogix 5370
CompactLogix 5380
Compact GuardLogix 5370 (safety)
ControlLogix 5570
ControlLogix 5580
GuardLogix 5570 (safety)
1756 Armor ControlLogix (safety)
1756 Armor GuardLogix (safety)
1768 Compact GuardLogix (safety)
Programmable logic controllers1768 CompactLogix
1769 Modular CompactLogix
1769 Packaged CompactLogix
1789 SoftLogix 5800
PowerFlex with DriveLogix
1785 PLC-5 (1)
1747 SLC (1)
Programmable logic controllers1761 MicroLogix (2)
1762 MicroLogix (2)
1763 MicroLogix
1764 MicroLogix (2)
1766 MicroLogix

(1) Requires a built-in Ethernet port or a 1761-NET-ENI, EtherNet/IP RS-232-C interface. (2) Requires a 1761-NET-ENI, EtherNet/IP RS-232-C interface.

Ethernet Node Limits

When configuring a CompactLogix 5380 control system, account for the number of Ethernet nodes in the I/O configuration section of the Studio 5000 Logix Designer application project.

Maximum Number of Ethernet Nodes

The number of supported nodes varies by controller:

Cat. No.Ethernet Nodes Supported
5069-L306ER, 5069-L306ERM16
5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM24
5069-L320ER, 5069-L320ERM40
5069-L330ER, 5069-L330ERM50
5069-L340ER, 5069-L340ERM55
5069-L350ERM60
5069-L380ERM70
5069-L3100ERM80

Devices added to the I/O configuration section count towards the Ethernet node limit. Examples include:

CompactLogix 5380 Controller Accessories

The following accessories are used with a CompactLogix 5380 controller:

End Cap

An end cap (catalog number 5069-ECR) must be installed on the right side of the last module in a CompactLogix 5380 system. The end cap is shipped with the controller.

SHOCK HAZARD: The end cap covers exposed interconnections. Failure to install the end cap before powering the system can result in equipment damage or injury from electric shock.

Memory Cards

Memory cards (Secure Digital or SD cards) provide nonvolatile memory for user programs and tag data. The Logix Designer application allows manual saving/loading of data or configuration for power-up loading from nonvolatile memory.

A 1784-SD2 card is shipped with the controller. For additional SD cards, Rockwell Automation recommends using their 1784-SD1 (1 GB) and 1784-SD2 (2 GB) cards.

Attribute1784-SD11784-SD2
Memory1 GB2 GB
Supported controllersCompactLogix 5380 controllersCompactLogix 5380 controllers
Weight, approx1.76 g (0.062 oz)1.76 g (0.062 oz)

Removable Terminal Kits

Order 5069 RTB kits to connect MOD power and SA power. The MOD power connection uses a 4-point RTB, and the SA power connection uses a 6-point RTB.

Cat. No.Description
5069-RTB64-SCREWContains: 5069-RTB6-SCREW (6-point RTB, screw-type terminals) and 5069-RTB4-SCREW (4-point RTB, screw-type terminals).
5069-RTB64-SPRINGContains: 5069-RTB6-SPRING (6-point RTB, spring-type terminals for SA power) and 5069-RTB4-SPRING (4-point RTB, spring-type terminals for MOD power).

Ethernet Communication Cables

Wiring details for Ethernet cables:

Connector NumberColor1585J 8-pin Cables with Support for 10/100/1000 Mbps1585J 8-pin Cables with Support for 10/100 Mbps1585J 4-pin Cables with Support for 10/100 Mbps
1White/OrangeTxData +TxData +TxData +
2OrangeTxData -TxData -TxData -
3White/GreenRxData +RxData +RxData +
4BlueUnusedUnusedN/A
5White/BlueUnusedUnusedN/A
6GreenRxData -RxData -RxData -
7White/BrownUnusedUnusedN/A
8BrownUnusedUnusedN/A
AttributeValue
Connector typeRJ45 male to RJ45 male
Connector angleStraight-through
LengthVaries by catalog number

Additional Resources

These documents provide additional information on related products from Rockwell Automation:

Publications can be viewed or downloaded at http://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

PDF preview unavailable. Download the PDF instead.

ID-SPE-v1-5069-td002 -en-p Acrobat Distiller 10.0.0 (Windows)

Related Documents

Preview Allen-Bradley 5069L340ERM CompactLogix 5380 Controller Datasheet
Detailed datasheet for the Allen-Bradley 5069L340ERM CompactLogix 5380 PLC CPU-module. Includes electrical, communication, construction, and dimension specifications, along with related accessories.
Preview Allen-Bradley 1492CH174613 I/O Conversion System Datasheet
Datasheet for the Allen-Bradley 1492CH174613 I/O Conversion System, compatible with SLC500 and 5069 Compactlogix, featuring 13 slots, PLC mounting rack capabilities, and detailed construction and dimension specifications.
Preview Compact 5000 I/O Digital 16-point Relay Output Module Installation Instructions
This document provides installation instructions for the Compact 5000 I/O Digital 16-point Relay Output Module (Catalog Number 5069-OW16). It covers system requirements, component installation, wiring diagrams, and safety considerations for this industrial automation module.
Preview SLC to CompactLogix Programming Migration Guide - Rockwell Automation
A comprehensive guide for migrating SLC programs and I/O to CompactLogix systems, detailing the process, requirements, and considerations for a smooth transition. This document provides insights into leveraging existing infrastructure while minimizing costs and risks.
Preview ControlLogix System Selection Guide
This guide provides information on selecting and configuring ControlLogix systems, including controllers, I/O modules, communication modules, and accessories. It covers features, specifications, and application examples for various ControlLogix and GuardLogix products.
Preview Allen-Bradley Compact GuardLogix 5069 5069L330ERMS3 SIL3 PLC CPU Module
Detailed information on the Allen-Bradley Compact GuardLogix 5069 5069L330ERMS3, a SIL3 PLC CPU module with 3MB controller memory and 1.5MB safety memory, supporting up to 60 EtherNet/IP nodes. Features include Studio 5000 Logix Designer compatibility and industrial control capabilities for safety-critical applications.
Preview SLC 500 Hardware Migration Guide: Upgrade to CompactLogix
This guide provides comprehensive instructions for migrating from SLC 500 hardware to newer Allen-Bradley CompactLogix and Compact 5000 I/O systems. It covers controller and I/O module replacements, including wiring diagrams and software requirements for a smooth transition.
Preview Manual del Usuario de los Controladores CompactLogix 1769
Guía completa para la instalación, configuración, programación y operación de los controladores CompactLogix 1769 de Allen-Bradley. Incluye detalles sobre comunicación, E/S, y desarrollo de aplicaciones.