Instructions for Orion INSTRUMENTS models including: MT Series, MT Series Industrial Temperature Switches, Industrial Temperature Switches, Temperature Switches, Switches

Product Catalogue

MT Series

PDF preview unavailable. Download the PDF instead.

6-MT-Temp
MD/MT TEMPERATURE SWITCHES MT
INSTALLATION DRAWING

98 (3.85)

Mounting Holes 2 Nos. Ø7.0

149 (5.86)
130 (5.11)

118 (4.64)

31 (1.22)

51 (2.0)

87 (3.42) 31 (1.22)

48 (1.88)

Cable Entry 1/2"NPT or M20x1.5

SS Capillary 2Mtr. Long (Options Available)

Bulb Diameter Ø9.5 (0.37)
100 (3.94)
Mounting Nut 3/8"BSP (Option Available)

129

APPROX. DIMENSIONS IN

mm inches

57 Bulletin No. KA220802

MD/MT TEMPERATURE SWITCHES
RANGE SELECTION TABLE

Range Code T1H

Range oC ( oF)
25 - 90 (77 - 194)

Differential* oC ( oF)
Approximate Maximum for "A1"
microswitch
15 (59)

Maximum Working Temperature
oC ( oF) 150 (302)

T2H

70 - 150 (158 - 302)

20 (68)

200 (392)

T3H

120 - 215 (248 - 419)

30 (86)

300 (572)

Note:
1. The minimum differential increases with the setpoint. The differential values mentioned in the above table are approximate maximum for FSR. The differential value will vary according to the pressure range selected and microswitch type. For actual values of differential please contact sales office.
2. When using 2SPDT switching arrangement, both microswitches may not actuate and/or deactuate at the same point. A small stage gap, normally upto +/- 5% FSR (depending on range code) may be observed. The On-Off differential (hysterisis) typically tends to be atleast double of those published for 1SPDT pressure switches.
If actuation and/or deactuation at same point is critical part of operation, then it can be achieved by using a separate DPDT relay. This relay will need a separate power supply for it's coil.

75Bulletin No. KA220802

130

HOW TO ORDER INDUSTRIAL TEMPERATURE SWITCHES

TEMPERATURE MD/MT SWITCHES

131

Group 1
Non standard allocation

Group 2
Gas Group Classification

Group 3 Cable Entry Size

Group 4 Switch Type

Group 5 Range Code (values in oC)

Group 6
Microswitch Type

Group 7
Temp. Bulb Material / Size

Group 8
Capillary Material / Size

Reserved for MD =

Non-standard Industrial

Options not temperature

covered in

switch with IP66

Catalogue. Will rated enclosure

Be given by as per IS/IEC

Manufacturer, 60529

Only after Agreement of Supply details With customer.

MT = Industrial temperature switch with IP66

rated enclosure

as per IS/IEC

60529

1 = Al. enclosure ½" NPT threads
*2 = Al. enclosure ¾" NPT threads
3 = Al. enclosure M20 X 1.5 threads
7 = SS enclosure, ½" NPT threads
*8 = SS enclosure, ¾" NPT threads
9 = SS enclosure, M20 X 1.5 threads

TF1 = Temperature Switch, fixed differential without scale
TF2 = Temperature Switch, fixed differential with scale in oC

T1H = 25 - 90 T2H = 70 - 150 T3H = 120 - 215

*TA1 = temperature switch,
adjustable differential
without scale

*TA2 = temperature switch, adjustable differential with scale in oC

*Not available for MT model For dual cable entry contact Sales Office

*Available with A6, A7, A9 & B9 (in group 6) only

A1 = General

B1 = Brass /

2 =

purpose

Dia. 9.5 mm, 123 SS316 /

microswitch, rated mm length, with 3/8" 2.0 meter

at 15 A; 250 VAC BSP (M) thermowell

*A6 = Adjustable connection

deadband

B2 = Brass /

*A7 = 2SPDT switching elements

Dia. 9.5 mm, 123 mm length, with 3/8" NPT (M) thermowell

*A8 = General

connection

purpose microswitch B3 = Brass /

*A9 = General

Dia. 9.5 mm, 123

purpose microswitch mm length, with 1/2"

B1 = General purpose AC/DC

NPT (M) thermowell connection

*B7 = 2SPDT Switching Elements

*B9 = 2SPDT Switching Elements for adjustable differential
* For detailed specifications of microswitches, please refer note under Range Selection Table

More options available. Please contact sales office.

E.g. An Industrial Temperature Switch, with 1/2"NPT cable entry in aluminum housing as 1 SPDT, fixed differential without scale, having 25°C to 90°C temperature range, with 15 Amp. microswitch, with Brass 9.5 mm diameter bulb, having length 123 mm with 3/8"BSP(M),with 2.0 meter SS316 capillary length shall be specified by

Group 1

Group 2

Group 3

Group 4

Group 5

Group 6

Group 7

Group 8

MD

1

TF1

T1H

A1

B1

2

Please specify full model number to avoid ambiguity.

57 Bulletin No. KA220802


cairo 1.16.0 (https://cairographics.org)