Enthalpy Sensor Kit Installation Instructions
Model Numbers: 603364-35; 21Z09
Application
Sensors provide input to determine free cooling suitability. The enthalpy sensor provided in this kit senses both sensible temperature and humidity. This kit applies to LGM/LCM, LGH/LCH, KG/KC/KH, ZG/ZC/ZH, QG/QH/QC unit standard performance economizers and LGM/LCM/LGH/LCH high performance economizers. A separate kit is used for KG/KC/KH, ZG/ZC/ZH and QG/QH/QC high performance economizers. Refer to economizer installation instructions.
Note: Differential sensor applications must use the same two sensors.
Warnings and Cautions
⚠ WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
⚠ CAUTION
Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
Shipping and Packing List
Package 1 of 1 contains:
- 1- Sensor
- 2- #6-32 X 7/8" Screws
- 1- P104 Wiring harness (used for outdoor air sensing only)
- 1- P105 Wiring harness (used for return air sensing only)
- 1- J105 Wiring harness (used on KG/KC/KH092-300S only)
- 1- Bracket (used on LG/LC/KG/KC/KH 092-150 units only)
- 1- Wire tie
- 1- #10-16 X 5/8" SDST screw
IMPORTANT: Two kits must be installed if differential enthalpy sensing is specified.
Check packaging for shipping damage. Contact the last carrier immediately if any shipping damage is found.
Table 1: Outdoor Air Enabled For Free Cooling
No. Of Sensors | Outdoor Air Is Enabled For Free Cooling When: |
---|---|
1 | OA enthalpy, A7, is less than free cooling setpoint (single enthalpy). |
2 | OA enthalpy, A7, is less than RA enthalpy, A62 (differential enthalpy).* |
*Differential enthalpy not available with ZG/ZC/ZH and QG/QH/QC units.
Install Sensors
Note: Install the return air sensor before installing optional power exhaust dampers and gravity exhaust dampers. If gravity exhaust, power exhaust, or hoods are already installed, remove from unit.
- Disconnect all power to unit.
- Remove unit top back panel and retain screws. If economizer is already installed, remove hood.
- Install sensors as shown in Table 2.
Table 2: Sensor Installation
Sensor S | Unit | Kit Harness Used: | Sensor Location |
---|---|---|---|
1 | LG/LC 036-072 KG/KC/KH 024-090 |
P104 None* |
Figure 1 |
2 | LG/LC 036-072 KG/KC/KH 024-090 |
P104, P105** *P105, J105 |
Figure 1 |
1 | LG/LC 092-150 KG/KC/KH 092-150 |
P104 None* |
Figures 2 and 4 |
2 | LG/LC 092-150 KG/KC/KH 092-150 |
P104, P105** *P105, J105 |
Figures 2 and 4 |
1 | LG/LC 156-300 KG/KC/KH 156-300 |
P104 None** |
Figure 3 |
2 | LG/LC 156-300 KG/KC/KH 156-300 |
P104, P105* *P105, J105 |
Figure 3 |
1 | ZG/ZC/ZH | None* | Figure 5 |
2 | **ZG/ZC/ZH | NA NA |
Figure 5 |
1 | QG/QC/QH | None | Figure 6 |
2 | ***QG/QC/QH | N/A N/A |
Figure 6 |
*P104 not used; disconnect S175, reconnect to A7.
**J105 provided in unit.
***Differential enthalpy not available with ZG/ZC/ZH/QG/QC/QH units.
Specific Unit Installations
Install Sensor - ZG/ZC/ZH 036-150 UNITS
Note: S175 is factory-installed and wired in KG/KC/KH/ZG/ZC/ZH 024-300S economizers. Kit P104 harness is not used. When replacing S175 with an A7 enthalpy sensor, wire A7 with disconnected S175 wires.
- Remove factory-installed S175 outdoor air sensible sensor and bracket.
- Disconnect wiring to S175 and reconnect to A7 enthalpy sensor.
- Install A7 enthalpy sensor using S175 bracket holes. Secure with screws provided in kit.
Note: All contents of kit may be discarded except for the sensor and screws. Harnesses are not used in this application.
Diagram Description: Shows a horizontal unit with labels for S175 and a connection point.
Install Sensor - QG/QC/QH 036-150 UNITS
- Install sensor in the location shown above.
- Plug the red and black wires from the controllers "SO" and "SO+" terminals into the sensors + and - terminals.
- Discard unused harnesses.
Diagram Description: Shows a vertical unit with labels for Sensor Location and Controller Location.
Wiring Instructions
Wire A7 Sensor
Note: S175 is factory-installed and wired in KG/KC/KH/ZG/ZC/ZH 024-300S economizers. Kit P104 harness is not used. When replacing S175 with an A7 enthalpy sensor, wire A7 with disconnected S175 wires.
- Connect P104 harness plug to unit J104. See figure 1 for 024-090 units, figure 2 for 092-150 units, and figure 3 for 156-300S units.
- Connect the wires on the other end of the harness to A7 terminals S and + as marked on the wires. Make sure polarity is correct.
Note: Wiring to sensor is shown on D or D1 economizer wiring section. D or D1 is located on the compressor access panel or packaged with economizer.
Wire A62 Sensor - LG/LC/KG/KC/KH
Note: Discard J105 harness provided in kit when installing LGH/LCH units.
- Connect P105 harness plug to unit J105. See figure 1 for 036-072 units, figure 2 for 092-150 units, and figure 3 for 156-300S units. On KG/KC/KH units refer to Wire A6 section in this instruction to install J105.
- Connect the wires on the other end of the harness to A62 terminals S and + as marked on the wires. Make sure polarity is correct.
- Reinstall gravity exhaust damper, power exhaust, and outdoor air hood when applicable.
Note: Wiring to sensor is shown on D or D1 economizer wiring section. D or D1 is located on the compressor access panel or packaged with economizer.
Wire A6 Control - KG/KC/KH Units Only
- Install J105 harness jack in panel as shown in figure 8 for 024-090 units, figure 9 for KG/KC/KH 092-150 units and figure 3 for 180-300S units.
- Remove resistor between A6 enthalpy control terminals SR+ and SR. See figure 7.
- Connect the two leads from the wire harness to SR+ and SR terminals on the A6 control. Note the labeling on the wires for correct wiring.
- Turn A6 control setpoint dial completely clockwise to position "D". See figure 7.
Controller Configuration
Prodigy 2.0 M3 Unit Controller Configuration
Configure the Unit Controller for the enthalpy sensor use using the following menu: Go to SETUP / INSTALL and navigate through the various setup questions until Configuration ID 1 appears. Position two needs to set to either S for economizer - single enthalpy or D for economizer - dual enthalpy.
Prodigy M4 Unit Controller Configuration
Configure the unit through the mobile app. Go to SETUP / RTU Menu > Setup Install and navigate through the various setup questions until Configuration ID 1 appears. Position two needs to be set to either S for economizer - single enthalpy or D for economizer - dual enthalpy.
Note: Refer to M4 Setup Guide provided with the unit for more info.
Operation
Refer to Unit Controller manual for start-up and operation.
Diagrams
Figure 1: Install Sensors - LGM/LCM/LGH/LCH/KG/KC/KH 024-090 UNITS
Diagram Description: Shows the sensor and harness connections for outdoor and return air sensors on specific unit models.
Figure 2: Install Sensors - LG/LC/KG/KC/KH 092-150 UNITS
Diagram Description: Illustrates the placement of outdoor and return air sensors for LG/LC/KG/KC/KH 092-150 units.
Figure 3: Install Sensors 156-300S UNITS
Diagram Description: Depicts the sensor installation for 156-300S unit models, including division panel and control connections.
Figure 4: Install A62 Bracket - LG/LC/KG/KC/KH 092-150 UNITS
Diagram Description: Shows how to install the A62 bracket for the return air sensor on LG/LC/KG/KC/KH 092-150 units.
Figure 5: Install Sensor - ZG/ZC/ZH 036-150 UNITS
Diagram Description: Illustrates the sensor installation for ZG/ZC/ZH 036-150 units, including removal of the S175 sensor.
Figure 6: Install Sensor - QG/QC/QH 036-150 UNITS
Diagram Description: Shows the sensor installation for QG/QC/QH 036-150 units, indicating sensor and controller locations.
Figure 7: A6 CONTROL - KG/KC/KH APPLICATIONS ONLY
Diagram Description: A wiring diagram for the A6 control, showing resistor removal and setpoint dial.
Figure 8: WIRE A6 ENTHALPY CONTROL KG/KC/KH 024-090 UNITS ONLY
Diagram Description: Wiring diagram for A6 enthalpy control on KG/KC/KH 024-090 units.
Figure 9: WIRE A6 ENTHALPY CONTROL KG/KC/KH 090-150 UNITS ONLY
Diagram Description: Wiring diagram for A6 enthalpy control on KG/KC/KH 090-150 units, showing harness routing.
Related Documents
![]() |
Lennox Enthalpy Sensor Kit Installation Instructions Comprehensive guide for installing the Lennox Enthalpy Sensor Kit (603364-35; 21Z09) with economizer units. Covers packing, application, sensor installation for various models, wiring, and controller configuration. |
![]() |
Installation Instructions for D4P120 & D4S Smoke Detector Kits Comprehensive guide for installing D4P120 and D4S Smoke Detector Kits with KC/KG/KH and LCM/LGM/LCH/LGH HVAC units, including packing lists, application details, and wiring diagrams. |
![]() |
Lennox Germicidal Light Kit C1UVCL10B-2 Installation Instructions Detailed installation guide for the Lennox Germicidal Light Kit C1UVCL10B-2, designed for LG/LC/LH/LD/KG/KC/KH/KD 078-152 HVAC units. Includes safety warnings, specifications, and wiring diagrams. |
![]() |
Lennox LonTalk Module (54W27) Installation Guide for Rooftop Units Comprehensive installation instructions for the Lennox LonTalk Module (54W27), detailing setup, configuration, and integration with Lennox M2, M3, and CORE (M4) unit controllers for HVAC rooftop systems. Learn about LonWorks network connectivity and operational parameters. |
![]() |
Float Switch Kit Installation Instructions for Lennox Rooftop Units Comprehensive installation guide for the Float Switch Kit (602799-08; 21Z07) designed for Lennox LG/LC/LH/LD/SG/SC 024-360 series rooftop units. Covers application, parts, installation steps, and unit controller configuration for M2, M3, and M4 controllers. |
![]() |
Lennox Energence LGH Rooftop Units (20-30 Tons): High Efficiency Packaged Gas/Electric Specifications Detailed specifications, features, and performance data for Lennox Energence LGH series high-efficiency packaged gas/electric rooftop units (20-30 tons). Covers models LGH242, LGH300, LGH360, including control system, options, and technical details. |
![]() |
Lennox Energence® Rooftop Units: Commercial Gas/Electric HVAC Specifications Discover the Lennox Energence® series of packaged gas/electric rooftop units (7.5-12.5 Tons). Featuring high energy efficiency, the Prodigy® 2.0 Control System, Environ™ Coil System, and MSAV® blower, these units offer advanced HVAC performance and low operating costs for commercial buildings. |
![]() |
Lennox Prodigy Control System Operation Manual Comprehensive operation manual for the Lennox Prodigy Control System, detailing setup, navigation, troubleshooting, alarms, USB service reports, and SmartWire system integration for commercial HVAC units. |