WindowMaster WSA 311 Smoke Detector
Installation and Wiring Guide
(Version 2204)
1. English (EN)
1.1 Description
Smoke detector for early fire detection with visual signal on the detector itself via red LED. Includes mounting base.
1.2 Mounting
Product Dimensions:
- Side View: The detector is cylindrical with a base. Approximate dimensions: Diameter 100.4 mm, Height 46.50 mm.
- Top View: Shows the detector's top surface with mounting holes and internal features. Approximate dimensions: Outer Diameter 100.4 mm, Mounting hole circle diameter 65.00 mm, Individual mounting hole diameter 4.20 mm. Internal spacing dimensions of 72 mm and 60 mm are indicated.
Note: Installation must always be horizontal, beneath the ceiling.
1.3 Wiring
Detector Interconnection (Daisy-chaining):
Detectors are connected in series using "COM", "IN", and "OUT" terminals. The diagram shows connections for a "Last auto. detector" and a "First auto. detector".
Connection to Central Unit:
For connection to a smoke panel or RWA-Zentrale (central unit), refer to the specific instruction manuals for those systems. The diagrams show connection points labeled X and Y, with a note indicating that if a resistor is installed in the RWA-Zentrale, the resistor needs to be moved to the last detector in the chain.
Endmodules and Resistors:
The wiring diagrams reference the use of WSC 204, WSC 310**, and WSC 320** active endmodules, as well as WSC 5xx 10kΩ resistors. Specific instructions for WSC 310/320 are noted.
VdS Approval: The device has VdS Approval No: G204039.
1.4 LED Status
Feature | Description of feature | Red LED Status | Yellow LED Status |
---|---|---|---|
StartUp™ | Confirms that the detectors are wired in the correct polarity. | Flashes once per second | No Flash |
FasTest™ | Maintenance procedure, takes just 4 seconds to functionally test and confirm detectors are functioning correctly. | Flashes once per second | No Flash |
DirtAlert™ | Shows that the drift compensation limit has been reached. | No Flash | Flashes once per second in StartUp (Stops flashing when StartUp finishes) |
SensAlert™ | Indicates that the sensor is not operating correctly. | No Flash | Flashes every 4 seconds (Flashes once per second in StartUp) |
Normal operation | At the end of StartUp and FasTest (without flashing LED as standard). | No Flash | No Flash |
Flashing LED version | Detector's red LED flashes in normal operation (at the end of FasTest). | Flashes every 4 seconds | No Flash |
1.5 Important Information
- The packaging can be disposed of together with ordinary household waste.
- Electrical products must be disposed of in conformity with national regulations for electronic waste and not with usual household waste.
- In case of technical problems, please contact WindowMaster.
2. German (DE)
This section provides the same information as section 1 in German. Key points include:
- Beschreibung: Rauchmelder zur Brandfrüherkennung, mit optischer Anzeige bei Auslösung, inkl. Montagesockel.
- Montage: Hinweis: Rauchmelder immer horizontal einbauen.
- Anschluss: Similar wiring diagrams and notes as in the English section, including VdS approval.
- LED Status: A table detailing LED indications for StartUp, FasTest, DirtAlert, SensAlert, Normal Operation, and Flashing LED version.
- Wichtige Informationen: Notes on disposal and contacting WindowMaster for technical issues.
3. Danish (DK)
This section provides the same information as section 1 in Danish. Key points include:
- Beskrivelse: Røgmelder til detektering af brand med optisk indikator (rød LED), ved udløsning. Inkl. montagesokkel.
- Montage: Bemærk: røgmelderen skal altid indbygges horisontalt.
- Tilslutning: Similar wiring diagrams and notes as in the English section, including VdS approval.
- LED Status: A table detailing LED indications for StartUp, FasTest, DirtAlert, SensAlert, Normal Operation, and Flashing LED version.
- Vigtig information: Notes on disposal and contacting WindowMaster for technical issues.