Aereco Ambient Air Sensor TF5710_C

Humidity and Temperature | Installation and Operating Instructions

Description

This sensor measures ambient relative humidity as well as temperature. Its miniaturized sensitive element uses a CMOS capacitive relative humidity sensor and a band gap temperature sensor, providing a very precise and stable measurement with very low consumption. The sensor is self-calibrated. Output signal: Analog (0-10V).

Applications

Specially suitable for rooms where variations of humidity or temperature are relatively important and can be used to drive a system such as ventilation or air conditioning. Applications include:

Maintenance

Check frequently that the product is clean and remove dust if needed. No calibration is required. ⚠️ Caution: Never touch the sensing element, otherwise the detection may be damaged.

Warranty

The product is guaranteed for two years. Its validity is subject to conformed installation, use, and maintenance.

Manufacturer Information

This product is manufactured by Aereco S.A. in France.

62 rue de Lamirault
Collégien
77615 MARNE LA VALLEE CEDEX 3
FRANCE
www.aereco.com

Warnings

PLEASE READ THE FOLLOWING INSTRUCTIONS BEFORE INSTALLATION:

Installation

Sensors must be installed on the wall, at a height of at least 1.5 meters from the floor, or at the ceiling, and must respect the following recommendations:

Installation Steps

The sensor consists of a base (C), an electronic card (B), a plastic protection (D), and a front cover (A).

Diagram Description: The installation diagram shows the sensor components labeled A (front cover), B (electronic card), C (base), and D (plastic protection). It illustrates how to access and connect wires to the electronic card within the base.

  1. Remove the front cover (A).
  2. Unclip the electronic card (B) and the plastic protection (D) from the base (C).
  3. Fix the base (C) using 2 screws (not supplied). The screws and plug must be chosen according to the type of support.
  4. Connections: Use PVC wires with a minimum cross-section of 0.25 mm² for all wires. On the electronic card (B), connect the wires as follows:
    Terminal Function Description
    V+ Power Supply +12 VDC
    GND Power Supply 0 V
    S3 Analog Output (RH) 0-10 V signal mapping: 0 V = 0% RH; 10 V = 100% RH
    S4 Analog Output (Temperature) 0-10 V signal mapping: 0 V = 0°C; 10 V = +50°C
  5. Clip the electronic card inside the base (C).
  6. Put the cover (A) on the base (C).
  7. Connect the wires to the external devices (12 VDC supply and device driven by 0-10 V output).
  8. Only once all connections are made, plug in the system's supply.

Caution

Chemical vapors at high concentration combined with long exposure times may affect the sensor reading. During manufacturing and transport, sensors must be protected from high concentrations of chemical solvents and long exposure times. Out-gassing from glues, adhesive tapes, stickers, or packaging materials like bubble foils and foams should be avoided. The manufacturing area shall be well ventilated.

⚠️ Never connect the 12 VDC supply to S1 or S2, and the 0 V supply to GND, otherwise S1 and S2 outputs will be damaged.

A protection is implemented to safeguard the product in case of wrong connections, such as:

Technical Data

Parameter Value
Measurement principle Micro-machined metal oxide semiconductor (MOS) technology
Working range 0°C – +50°C
Precision RH 0% - 100% Relative Humidity; max +/-3% RH at 25°C, typical +/-2% on 20% -80% range.
Precision temperature max +/-0.4°C in [5°C; 60°C] range, typical 0.3°C.
Measuring time interval 60 s
Supply voltage 12 V DC +/- 10%
Average power consumption 15 mA
Peak current max. 1 A (use for fuse sizing)
Storage conditions 10...50°C, 0...60% RH
Output 0-10 V 0 to 10 V
Output data Voltage (S3 and S4) RH: 0V = 0% RH; 10V = 100% RH
Temp: 0V = 0°C; 10V = +50°C
Output data Current (S3 and S4) 400 mA
Models: Humidity And Temperature Ambient Air Sensor

File Info : application/pdf, 2 Pages, 235.47KB

PDF preview unavailable. Download the PDF instead.

TF5710 C

References

Adobe PDF Library 15.0 Adobe InDesign 16.1 (Windows)

Related Documents

Preview Aereco TF5701_B CO2 Ambient Air Sensor Installation and Operating Instructions
Installation and operating instructions for the Aereco TF5701_B CO2 ambient air sensor. This NDIR sensor measures CO2 levels from 0-2000 ppm with a 0-10V analog output. Includes technical specifications, applications, maintenance, and warranty information.
Preview Aereco BXC-EC Ventilation Unit Installation Guide
Comprehensive installation instructions for the Aereco BXC-EC ventilation unit, covering pressure measurement, airflow settings, and step-by-step mounting procedures.