INSTRUCTION MANUAL MT550 DIGITAL
INSULATION TESTER

2

Contents

Page no

1. Safety Information.............................................................................4

2. Safety Symbols..................................................................................4

3. Specifications....................................................................................4

3.1. General Information.................................................................4

3.2. Electrical Specifications............................................................5

4. Parts & Controls.................................................................................7

5. Battery Replacement.........................................................................7

5.1. How to connect test leads.........................................................7

5.2. Battery Check-UP & Replacement...............................................7

5.3. Test Lead Check.......................................................................7

6. Insulation Resistance Measurements...................................................8

6.1. Measurements at 200M/250V..................................................8

6.2. Measurements at 2000M/1000V..............................................8

6.3. Lock Power On Feature.............................................................8

7. Low Resistance (Continuity) Measurements..........................................9

8. AC/DC Voltage Measurements............................................................9

9. Power Tools and Small Appliances........................................................9

3

1. SAFETY INFORMATION · Read the following safety information carefully before attempting to
operate or service the meter. · To avoid damages to the instrument do not apply the signals which
exceed the maximum limits shown in the technical specifications tables. · Do not use the meter or test leads if they look damaged. Use extreme
caution when working around bare conductors or bus bars. · Accidental contact with the conductor could result in electric shock. · Use the meter only as specified in this manual; otherwise, the protection
provided by the meter may be impaired. · Read the operating instructions before use and follow all safety
Information. · Caution when working with voltages above 60V DC or 30V AC RMS. Such
voltages pose a shock hazard. · Before taking resistance measurements or testing acoustic continuity,
disconnect circuit from main power supply and all loads from the circuit. 2. SAFETY SYMBOLS
Caution refer to this manual before using the meter.
Dangerous voltages.
Meter is protected throughout by double insulation or reinforced insulation.
When servicing, use only specified replacement parts. CE Comply with EN-61010-1
3. SPECIFICATIONS 3.1. General Information
Environment conditions: 1. Installation Categories III 2. Pollution Degree 2 3. Altitude up to 2000 meters 4. Indoor use only 5. Relatively humidity 80% max. 6. Operation Ambient 0~40ºC Maintenance & Cleaning: 1. Repairs or servicing not covered in this manual should only be
performed by qualified personnel. 2. Periodically wipe the case with a dry cloth. Do not use abrasives or
solvents on this instruments.
4

Function

Range

Display

Large LCD with dual display

Measurement Range 200, 200k, 200M/250V, 200M/500V, 2000M/1000V, 750V/ACV, 1000V/DCV.

Sampling Rate

2.5 times per second.

Zero Adjustment

Automatic adjustment.

Over Range Indicator Number 1 of highest digit is displayed.

Low Battery Indication The is displayed when the battery Voltage drops below the operating voltage.

Operating Temperature 0ºC to 40ºC (32ºF to 104ºF) and Humidity below 80% RH

Storage Temperature -10ºC to 60ºC (14ºF to 140ºF) and Humidity below 70% RH

Battery

6 x AA

Dimensions

200(L) x 92(W) x 50(H) mm

Weight

Approx. 700g include battery

Accessories

Test Leads, 6 Batteries, Carrying Case, Manual.

3.2. Electrical Specifications

Accuracies are specified in the way: ±(...% of reading +...digits) at 23ºC±5ºC, below 80% RH.

OHMS Range
200 200k

Resolution Accuracy

0.01 0.1

±(1%+2)

Max. open Circuit Voltage 4.5V 3.0V

Overload Protection
250Vrms

Continuity Beeper

Range Resolution
0.1 Short circuit current

Accuracy
Resistance40 200mA

Max. open Circuit Voltage 4.5V

Overload Protection
250Vrms

5

DC Voltage

Range

Resolution

1000V

1V

Accuracy ±(0.8%+3)

Input

Overload

Impedance Protection

10M

1000Vrms

AC Voltage (40Hz~400Hz)

Range

Resolution Accuracy

750V

1V

±(1.2%+10)

Input Impedance
10M

Overload Protection
750Vrms

Meg OHMS
Range 200M/250V 200M/500V 0~1000M/1000V 1000~2000M /1000V

Resolution Accuracy

0.1M

0.1M

±(3%+5)

1M

±(5%+5)

Terminal Voltage 250V +10%~-0% 500V +10%~-0%
1000V +10%~-0%

Range

Test Current

200M/250V

250K(load)

200M/500V

500K(load)

0~1000M

1mA

/1000V

1000~2000M

1M

/1000V

Short Circuit Current 1mA

6

4. PARTS & CONTROLS

1. Digital Display

6. Rotary Function switch

2. Data Hold Button 7. V Jack

3. Lock Button

8. COM input jack

4. Backlight Button

9. Pothook

5. Test Button

10. Battery Cover

5. BATTERY REPLACEMENT 5.1. How to connect test leads.
a) On M Range: Connect the red test lead into the "V" terminal and the black lead into the "COM" terminal.
b) On 200 and ACV Range: Connect the red test lead into the "V" terminal and the black lead into terminal "COM"
5.2. Battery Check-UP & Replacement a) As battery power is not sufficient. LCD will display. Replacement of 6 pcs new batteries, type 1.5V size "AA" is required. b) Place back the battery cover and four the screws.
5.3. Test leads check Set the range select switch to the 200 range. With the tip and alligator clip of the test leads connected. The indicator should read 00.0. When the leads are not connected the display will read infinity indicated by "1". This will ensure that test lead are under working condition.
7

6. INSULATION RESISTANCE MEASUREMENTS 6.1. Measurements at 200M/250V This is the voltage used for the majority of insulation resistance tests on normal installation requirement. To measure insulation resistance, press the test button to power on the tester. The LCD will displayed the insulation resistance. Section VII indicated that subdivision of large installations might be necessary because of the large number of parallel insulation resistance. In such a case, an installation may be divided into sections, each being separately tested. Each section must have not less than fifty outlets, an outlet being a switch, socket, lighting point etc. A switched socket counts as one outlet. The minimum acceptable insulation resistance is 1M. For a large installation, the capacitance of the insulation will be high, and it will take longer for it to become charged by the direct testing voltage. Care must be taken not to take a reading until there is a steady reading, indicating that the charging process is complete. Note: The charge stored in the insulation will be discharged automatically when the test button is released. Be careful not to turn the range switch knob whilst the test button is pressed, or the instrument will be damaged. 6.2. Measurements at 2000M/1000V Some specifications require testing at 1000V. This voltage must also be selected where the supply voltage of the installation is between 500V and 1000V. First, set the range switch to 1000V and then proceed as indicated in a above for 500V testing. The above note also applies to testing at 1000V. In addition the following applies. Note: Make sure that the circuit under does not include components Which will be damaged by the 1000V applied. Many normal components of an installation are likely to be damaged if tested at 1000V. Examples are power factor correction capacitors, low voltage mineral insulated cables, electronic light dimmers, electronic ballasts and starters for fluorescent lamps etc... 6.3. Lock power on Feature For hands free operation a lock power on feature is incorporated on the press to test button. Set LOCK button to lock test voltage, Pressing it again will switch it off.
8

7. LOW RESISTANCE (CONTINUITY) MEASUREMENTS 1. Set the range switch to 200 Position 2. Connect the red test lead to the V  terminal and black to the COM terminal. 3. Connect the tips of the test leads to both ends of the circuit under test read resistance in  on the LCD. 4. When the impedance on circuit is below approximately 40. It will indicate by a continuous beeper.
8. AC/DC VOLTAGE MEASUREMENTS 1. Set the range switch to ACV or DCV position 2. Connect red test lead to "V " terminal and black test lead to terminal "COM". 3. Connect test prods of test leads IN PARALLEL to the circuit being measured. 4. Read the voltage value on LCD.
9. POWER TOOLS AND SMALL APPLIANCES This test would also apply to other similar equipment that has a line cord. For double insulated power tools, the megohmmeter lead shown connected to the housing would be connected to some metal part lf the tool (e.g. chuck,blade). Note: The switch of the device must be in the "ON" position and the main power should be disconnected.

MOTORS

AC-Disconnect the motor from the line by disconnecting the wires at the

motor terminals or by opening the main switch. If the main switch is used

and the motor also has a starter then the starter must be held, by some

means, in the "ON" position. In the latter case, the measured resistance

will include the resistance of the motor, wire and all other components

between the motor and the main switch. If a weakness is in dicated, the

motor and other components should be checked individually. If the motor is

disconnected at the motor terminals, connect one megohmmeter lead to

the grounded motor housing and the other lead to One of the motor leads.

DC-Disconnect the motor from the line. To test the brush rigging, field coils

and armature connect one megohmmeter lead to the grounded motor

housing and the other lead to the brush on the commutator. If the

resistance measurement indicates a weakness, raise the brushes off the

commutator and separately test the armature, field coils and brush rigging

by connecting one megohmmeter lead to each of them individually, leaving

the other connected to the grounded motor housing. The above also

applies to DC Generators.

9

CABLES Disconnect the cable from the line. Also disconnect opposite end to avoid errors due to leakage from other equipment. Check each conductor to ground and /or lead sheath by connecting one megohmmeter lead to a ground and /or lead sheather and the other megohmmeter lead to each of the conductors in turn. Check insulation resistance between conductors by connecting megohmmeter leads to conductors in pairs.
10

11