Danfoss CDS303/803 Quick Troubleshooting Guide

Service Guide

Intent of the Document

This document aims to provide a simplified troubleshooting process for Danfoss CDS303 and CDS803 drives, focusing on alarms displayed on the LCP (Local Control Panel). This is intended to reduce the number of drives returned as 'No Fault Found' by guiding users through common alarm resolutions.

Troubleshooting Steps

  1. Connect the LCP display to the drive.
  2. Power OFF and then power ON the drive. Allow the unit to attempt compressor startup.
  3. Check the alarms displayed on the drive and in the alarm history via the 'Alarm log'. Record these alarms carefully (or take a picture) for communication with Danfoss support.

CDS303 Alarm Log

The CDS303 drive displays alarm information directly on its screen. The 'Alarm log' button on the LCP provides access to this history.

Example alarms shown on the CDS303 display include:

CDS803 Alarm Log (Parameter 15-30 Alarm Log: Error Code)

To access the alarm log on the CDS803, navigate using the LCP as follows:

The drive can display up to 10 fault logs. Log '[0]' is the most recent, and '[9]' is the oldest.

Troubleshooting Flowcharts

Check Alarm #

#13: Over current

#18: Start failure

#49: Speed limit

If any of these alarms are present, it may indicate a Compressor failure.

Action: Replace the compressor and return it for inspection if under warranty.

Check Alarm #

#30: Motor phase U missing

#31: Motor phase V missing

#32: Motor phase W missing

These alarms suggest it is most probably neither a drive nor a compressor failure.

Action: Check the motor cable and reset the alarm.

Check Alarm #

#14: Earth (ground) fault

#A45: Earth (ground) fault

Action:

  • Power OFF the unit.
  • Disconnect the power cable at the compressor electrical box.
  • Perform an insulation resistance test on the compressor using a 500V 'megger' tester.

If resistance < 500 kΩ: Replace the compressor and return it for inspection if under warranty.

If resistance > 500 kΩ: Replace the drive and return it for inspection if under warranty.

Check Alarm #

#68: Safe stop activated by HP (High Pressure) switch trip

Action: Reset the high-pressure switch and reset the drive.

Check Alarm #

#36: Mains failure

Indicates power shortage while the compressor was running.

Action: Check the unit's main power supply. Investigate if other units connected to the same power supply are causing voltage drops during startup.

Check Alarm #

#38: Internal fault

Action: Check the code number associated with this alarm and refer to the Operating Instructions.

Power OFF and then power ON the drive. If the alarm remains, the drive may need to be returned for inspection if under warranty.

Others

Action: Return the drive for inspection.

Notes

  1. If the drive is not equipped with a display, the ordering code numbers are 120Z0581 for CDS803 and 120Z0326 for CDS303. LCP kits for remote mounting are 120Z0617 for CDS803 and 175Z0929 for CDS303.
  2. For further details regarding each alarm, refer to the Operating Instructions.
Models: CDS303 803 Dc Drive, CDS303, 803 Dc Drive, Drive

File Info : application/pdf, 6 Pages, 1.67MB

PDF preview unavailable. Download the PDF instead.

Service Guide CDS303,803 (Руководство по обслуживанию)

References

Adobe PDF library 15.00

Related Documents

Preview Danfoss CDS303/803 Quick Troubleshooting Guide
A quick troubleshooting guide for Danfoss CDS303/803 drives, focusing on common alarms and their solutions to minimize unnecessary returns.
Preview VACON® NXP DCGuard™ Application Guide - Danfoss
Comprehensive application guide for the VACON® NXP DCGuard™ system, detailing configuration, control, parameters, and troubleshooting for advanced AC drive functions.
Preview Danfoss VZH088-117-170 Compressor: Installation, Operation, and Maintenance Guide
Comprehensive guide for Danfoss VZH series variable speed scroll compressors (VZH088, VZH117, VZH170), covering installation, safety, electrical connections, operation, maintenance, and warranty information.
Preview VACON® 3000 Drive Kit Operating Guide
This guide provides essential information for the safe installation and commissioning of the VACON® 3000 Drive Kit. It covers product overview, mechanical and electrical installation, control connections, commissioning procedures, maintenance, and fault tracing for qualified personnel.
Preview VLT HVAC Basic Drive FC 101 Selection Guide
A comprehensive selection guide for the Danfoss VLT HVAC Basic Drive FC 101, detailing its features, technical specifications, and applications for HVAC systems. This guide covers energy savings, CO2 emission reduction, and performance optimization for fans, pumps, and compressors.
Preview VLT® Compressor Drive CDS 803 Operating Guide
This operating guide provides essential information for the safe installation, commissioning, and operation of the VLT® Compressor Drive CDS 803. It covers safety precautions, mechanical and electrical installation, programming, troubleshooting, and technical specifications for this Danfoss drive.
Preview VLT HVAC Basic Drive FC 101 Selection Guide - Danfoss
Explore the VLT HVAC Basic Drive FC 101 from Danfoss, a compact and competitive solution for standard HVAC applications, offering energy savings, advanced features, and robust performance for fans, pumps, and compressors.
Preview Danfoss VLT® DriveMotor FCP 106: Selection Guide for Space-Saving Efficiency
Explore the Danfoss VLT® DriveMotor FCP 106, a versatile and efficient solution for variable speed motor control. This selection guide highlights its space-saving design, flexible installation options, premium efficiency features, and cost-saving benefits for industrial applications like pumps, fans, and conveyors. Learn about its built-in DC choke, smart logic controller, automatic motor adaptation, and robust IP66/Type 4X enclosure.