User Manual for Danfoss models including: NovoCon M Digital Actuator, NovoCon M, Digital Actuator, Actuator

NovoCon M actuator


File Info : application/pdf, 4 Pages, 2.04MB

PDF preview unavailable. Download the PDF instead.

AQ291838446552en-020504
Operating Guide
NovoCon® M

NovoCon® M / 73697030


A B
© Danfoss | 2024.03

NovoCon® M + AB-QM NovoCon
(DN 40/50)

NovoCon® M + AB-QM NovoCon
(DN 50)

NovoCon® M + AB-QM NovoCon
(DN 65-100)

DN 40 - 100

NO presetting!

100 %







 


Click

 

1b 1a 



Click

AQ291838446552en-010504 | 1

NovoCon® M





 



+24V

24V AC/DC

0V



A+

BACnet MS/TP or

B-

Modbus RTU

GND T3

Temperature sensor 3

R on R off

T2 T1 GND GND AO AI

Temperature sensor 1
Analog output

Temperature sensor 2
Analog input

GND is common for all signals



Optional step (connecting flow sensor)

NovoCon M
+24V 0V A+ B- GND T3
R on R off
T2 T1 GND GND AO AI

Sharky FS 473 flow sensor
Wire Description Blue Ground (-) White Volume pulse output (+)



NovoCon®M
003Z8540
Actuator for AB-QM DN40-100
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA

Power: 24VAC/DC, 50/60 HZ

Force: 550N. Stroke: 20 mm. Speed: 3-24s/mm

Consumption: 3.5VA running. Standby 0.9W

III

IP54/40, -10T55

E100 VX01X 281624 0030471

6430 Nordborg, Denmark MADE IN SLOVENIA

E100 VX01X 281624 0030471

Serial number and QR code can be removed from the NovoCon® M label and added to installation drawing.

E100 VX01X 281624 0030471

Device Object Instance Number

2 | © Danfoss | 2024.03

AQ291838446552en-010504

NovoCon® M



DIP Switch
12345678

R ON OFF

Dip switches for addressing and bus protocol selection are located under the lid of the actuator. Dip switches 1 to 7 are used to assign the MAC address manually. Default MAC address assignment method is Auto MAC addressing for BACnet MS/TP and DIP Switches for Modbus RTU. Dip switch 8 is used to select between BACnet MS/TP (OFF=Default) and Modbus RTU (ON). When the protocol is changed on DIP Switch 8, a power cycle is required. For termination of the last unit on the field bus, turn the DIP Switch R located between the connectors to ON.



Initial configuration

Application mode:
 MSV:9 / 32810 Digital control (default), Analog control



Select Valve Type MSV:3 / 32802 (default AB-QM NovoCon DN40)

   Select application MSV:10 / 32811 Heating (default) Cooling

Design Flow Rate AV:30 / 32796 Heating AV:31 / 32798 Cooling

Activate calibration MSV:0 / 33284 state 2 or use manual calibration

NovoCon® M

AQ291838446552en-010504

© Danfoss | 2024.03 | 3

NovoCon® M



Click

 ~ 60°

 










Safety Note
To avoid injury and damage to persons and devices, it is absolutely necessary these instructions are carefully read and observed prior to assembly and commissioning. Necessary assembly, start-up, and maintenance work must be performed only by qualified, trained and authorised personnel. Switch off the power line before wiring the actuator.

Safety Note
If the NovoCon® M network is supplied with two or more AC power boosters, caution must be observed when disconnecting one of the transformers from the high voltage power line. As the NovoCons are connected in a daisy chain, there may be high voltage on the primary side of the disconnected power supply. Disconnect always both the primary and secondary side of the transformer.
Firmware update
We recommend to validate the firmware version before installation. The latest firmware can be downloaded at www.novocon.com by selecting the tab: Support files.