CAPACITIES
  • 2.5-35 kW
  • 208-600V
  • 10 or 30
  • Thermostat Range: 50°-90° F
  • Air Volume: 550-3850 CFM
  • Air Throw Range: 13-75 feet
  • Class 1, Divisions 1 & 2, Groups C & D
  • Class II, Divisions 1 & 2, Groups F & G
  • Class 1, Zones 1 & 2, Groups IIB
  • Ignition Temperature Code T3C, 320° F
  • See Selection Chart for Options
JOB INFORMATION

JOB NAME:

LOCATION:

ARCHITECT:

ENGINEER:

CONTRACTOR:

SUBMITTED BY:

DATE:

HEATER SPECIFICATIONS
TAG/ITEMQTY.CATALOG NUMBERKWVOLTSØAMPSCFMAIR MOVEMENT THROWTEMP. RISE
ACCESSORIES AND CONTROLS
TAG/ITEMQTY.CATALOG NUMBERDESCRIPTION
APPROVALS

SUBMITTED BY:

DATE:

APPROVED BY:

DATE:

ARCHITECT'S AND ENGINEER'S SPECIFICATIONS*

Electric explosion proof unit heater(s) shall be supplied by QMark, a Marley Engineered Products® Brand, Bennettsville, SC, USA, and shall be of the KW rating, voltage and phase specified in the schedule. They shall be fan-forced type, certified to cCSAus, and approved for Class I, Divisions 1 and 2, Group C and D; Class II, Divisions 1 and 2, Groups E, F and G; Class I, Zones 1 and 2, Group IIB; Temperature Code T3C, 320°F (160°C).

SAFETY:

Unit heaters shall be outfitted with dual overtemperature production—both a manual and automatic reset thermal cutout.

HEAT EXCHANGER:

Efficient liquid-to-air design utilizes an all welded steel headers and finned tube construction with spiral wound aluminum fins. Industrial grade heating elements are immersed in a nontoxic, inhibited, propylene glycol heat transfer fluid that provides freeze protection down to -49°F (-45°C). The heat exchanger is hydrostatically tested at 350 psig. A pressure relief valve provides excess pressure protection and is set at 70 psig.

ENCLOSURE:

Heat exchanger and components to be enclosed in an industrial grade, corrosion-resistant cabinet fabricated from polyester powder-coated, 14 gauge steel. Adjustable outlet louvers to have minimum opening safety stops.

FAN MOTOR ASSEMBLY:

Unit heaters consist of an explosion-proof motor (60hz standard, 50hz optional) fitted with an aluminum fan blade. The motor has double shielded, permanently lubricated ball bearings and automatic reset line breaking thermal overload protection. Motors furnished on standard units operate at line voltage and are prewired to the control enclosure so separate field wiring to the motor is not required. The standard motor is rated for Class I, Groups C and D, Class II, Groups F and G. The minimum operating temperature is -14°F (-25°C) and the minimum storage temperature is -49°F (-45°C). Optional motor ratings available.

MOUNTING:

The heater shall be provided with an accessory mounting kit designed to bear the weight of heater assembly. Options include a ceiling mounting kit, wall mounting kit, or a pole mounting kit.

OPTIONAL BUILT-IN CONTROLS:

Units come standard with a controlling magnetic contactor and 24 Volt control circuit transformer housed in a NEMA 7, 9 cast aluminum enclosure. The following factory installed and prewired control options are available: adjustable built-in thermostat, disconnect switch with external handle, fan only switch, 120 Volt control circuit for special external thermostat circuit, “warning” pilot light (to indicate abnormal operation), “Heater On” pilot light.

*QMark reserves the right to change specifications without prior notice.

GUX SERIES 60 Hz Models & Specifications:

ITEM INFORMATION CATALOG NO.ELECTRICAL DATA VOLTS PHASE KWMOTOR HP RPMAIR FLOW FAN BLADE DIAMETER CFMFRAME SIZEAIR MOVEMENT THROWTEMP. RISE**SHIP WT.
GUX-233-FA-0036C208 1 171/4 172512" 650115"15°F130 lbs
GUX-233-FA-0036J240 1 151/4 172512" 650115"15°F130 lbs
GUX-233-FA-0036D208 3 101/4 172512" 650115"15°F130 lbs
GUX-233-FA-0036K240 3 91/4 172512" 650115"15°F130 lbs
GUX-233-FA-0036U480 3 51/4 172512" 650115"15°F130 lbs
GUX-233-FA-0036Z600 3 41/4 172512" 650115"15°F130 lbs
GUX-233-FA-0056C208 1 261/4 172512" 650115"25°F130 lbs
GUX-233-FA-0056J240 1 231/4 172512" 650115"25°F130 lbs
GUX-233-FA-0056D208 3 161/4 172512" 650115"25°F130 lbs
GUX-233-FA-0056K240 3 141/4 172512" 650115"25°F130 lbs
GUX-233-FA-0056U480 3 71/4 172512" 650115"25°F130 lbs
GUX-233-FA-0056Z600 3 61/4 172512" 650115"25°F130 lbs
GUX-233-FA-0086C208 1 381/4 172512" 850125"28°F130 lbs
GUX-233-FA-0086J240 1 341/4 172512" 850125"28°F130 lbs
GUX-233-FA-0086D208 3 231/4 172512" 850125"28°F130 lbs
GUX-233-FA-0086K240 3 201/4 172512" 850125"28°F130 lbs
GUX-233-FA-0086U480 3 101/4 172512" 850125"28°F130 lbs
GUX-233-FA-0086Z600 3 91/4 172512" 850125"28°F130 lbs
GUX-233-FA-0106J240 1 441/4 172512" 850125"38°F130 lbs
GUX-233-FA-0106D208 3 301/4 172512" 850125"38°F130 lbs
GUX-233-FA-0106K240 3 261/4 172512" 850125"38°F130 lbs
GUX-233-FA-0106U480 3 131/4 172512" 850125"38°F130 lbs
GUX-233-FA-0106Z600 3 111/4 172512" 850125"38°F130 lbs
GUX-233-FB-0156D208 3 441/4 172516" 1800245"27°F169 lbs
GUX-233-FB-0156K240 3 381/4 172516" 1800245"27°F169 lbs
GUX-233-FB-0156U480 3 191/4 172516" 1800245"27°F169 lbs
GUX-233-FB-0156Z600 3 161/4 172516" 1800245"27°F169 lbs
GUX-233-FB-0206U480 3 251/4 172516" 1800245"35°F169 lbs
GUX-233-FB-0206Z600 3 211/4 172516" 1800245"35°F169 lbs
GUX-233-FC-0256U480 3 311/2 172520" 3110365"26°F216 lbs
GUX-233-FC-0256Z600 3 251/2 172520" 3110365"26°F216 lbs
GUX-233-FC-0306U480 3 371/2 172520" 3850375"25°F216 lbs
GUX-233-FC-0306Z600 3 301/2 172520" 3850375"25°F216 lbs
GUX-233-FC-0356U480 3 431/2 172520" 3850375"29°F216 lbs
GUX-233-FC-0356Z600 3 351/2 172520" 3850375"29°F216 lbs

*Total Amps = Heating element and motor amps. **Approximate air temperature rise

GUX SERIES 50 Hz Models & Specifications:

ITEM INFORMATION CATALOG NO.ELECTRICAL DATA VOLTS PHASE KWMOTOR HP RPMAIR FLOW FAN BLADE DIAMETER CFMFRAME SIZEAIR MOVEMENT THROWTEMP. RISE**SHIP WT.
GUX-233-FA-0036E220 1 141/4 143812" 550113"14°F130 lbs
GUX-233-FA-0036F220 3 91/4 143812" 550113"14°F130 lbs
GUX-233-FA-0036G380 3 61/4 143812" 550113"14°F130 lbs
GUX-233-FA-0036H400 3 61/4 143812" 550113"14°F130 lbs
GUX-233-FA-0036I415 3 51/4 143812" 550113"14°F130 lbs
GUX-233-FA-0056E220 1 211/4 143812" 550113"24°F130 lbs
GUX-233-FA-0056F220 3 131/4 143812" 550113"24°F130 lbs
GUX-233-FA-0056G380 3 91/4 143812" 550113"24°F130 lbs
GUX-233-FA-0056H400 3 81/4 143812" 550113"24°F130 lbs
GUX-233-FA-0056I415 3 71/4 143812" 550113"24°F130 lbs
GUX-233-FA-0076E220 1 311/4 143812" 700122"28°F130 lbs
GUX-233-FA-0076F220 3 191/4 143812" 700122"28°F130 lbs
GUX-233-FA-0076G380 3 121/4 143812" 700122"28°F130 lbs
GUX-233-FA-0076H400 3 111/4 143812" 700122"28°F130 lbs
GUX-233-FA-0076I415 3 101/4 143812" 700122"28°F130 lbs
GUX-233-FA-0096E220 1 401/4 143812" 700122"38°F130 lbs
GUX-233-FA-0096F220 3 241/4 143812" 700122"38°F130 lbs
GUX-233-FA-0096G380 3 151/4 143812" 700122"38°F130 lbs
GUX-233-FA-0096H400 3 131/4 143812" 700122"38°F130 lbs
GUX-233-FA-0096I415 3 131/4 143812" 700122"38°F130 lbs
GUX-233-FB-0136F220 3 351/4 143816" 1500239"26°F169 lbs
GUX-233-FB-0136G380 3 211/4 143816" 1500239"26°F169 lbs
GUX-233-FB-0136H400 3 191/4 143816" 1500239"26°F169 lbs
GUX-233-FB-0136I415 3 181/4 143816" 1500239"26°F169 lbs
GUX-233-FB-0176F220 3 461/4 143816" 1500239"35°F169 lbs
GUX-233-FB-0176G380 3 281/4 143816" 1500239"35°F169 lbs
GUX-233-FB-0176H400 3 251/4 143816" 1500239"35°F169 lbs
GUX-233-FB-0176I415 3 241/4 143816" 1500239"35°F169 lbs
GUX-233-FC-0216G380 3 331/2 143820" 2600357"26°F216 lbs
GUX-233-FC-0216H400 3 321/2 143820" 2600357"26°F216 lbs
GUX-233-FC-0216I415 3 311/2 143820" 2600357"26°F216 lbs
GUX-233-FC-0256G380 3 391/2 143820" 2600357"30°F216 lbs
GUX-233-FC-0256H400 3 371/2 143820" 2600357"30°F216 lbs
GUX-233-FC-0256I415 3 361/2 143820" 2600357"30°F216 lbs

*Total Amps = Heating element and motor amps. **Approximate air temperature rise

Factory Built-in Options:

CATALOG NO.OPTIONDESCRIPTION
DDisconnect SwitchFactory installed on the unit heater above the control enclosure. This is an inexpensive and positive way to meet NEC/CEC requirements for a disconnecting means within sight of the heater.
EGroup E (Metal Dust) ConstructionClass II, Group E (Metal Dust) Construction Temperature Code T3C, 320° F (160°C).
K"Warning" Pilot LightIndicates when the thermal cutouts have tripped and the unit heater needs servicing. Not available with combination V & L.
L"Heater On" Pilot LightIndicates when the electric heating elements are energized. Not available with combination V & K
MManual Reset Thermal Cutout with Backup ContactorA pilot duty manual reset thermal cutout with a backup contactor is provided for independent secondary overtemperature protection. Cannot be installed with S, S1 or V.
SAuto/Fan Selector SwitchA two-position switch wired to the control circuit for auto (automatic heat) and fan only control. Cannot be installed with M, V or S1.
S1Built-In Controls to Remote Auto/Fan Selector SwitchA two-position switch wired to the control circuit for auto (automatic heat) and fan only control. Cannot be installed with M, V or S1.
TAdjustable ThermostatFactory installed and prewired to the control enclosure. Thermostat is adjustable from 50° to 90° F (10° to 32°C).
T1Adjustable Thermostat for Wet LocationsFactory installed and prewired to the control enclosure. Thermostat is adjustable from 40° to 80° F (5° to 25°C). Can be specified for all constructions.
V120 Volt Control CircuitCan be provided when required for special external thermostat circuit. Cannot be installed with S, S1, M or the combination of both K & L together.

Note: Both pilot lights (K & L) are not available with 120V option (V). Only one pilot light can be ordered with 120V control heaters.

Standard Mounting Kits:

CATALOG NO.DESCRIPTION
1022451Ceiling Mounting Kit
1022454Wall Mounting Kit
1022457Pole Mounting Kit

Note: One kit required per heater. Work with all frame sizes

Accessory Remote Thermostats:

CATALOG NO.SWITCH TYPETYPERATINGTEMP RANGEDESCRIPTION
1007002BimetalSPDT125-277V, 22A50°-90°F (10°-32°C)Class 1 Div. 1, Groups C & D. Class II, Div. 1, Groups E, F, & G
QX-1024754Bulb and Capillary with Internal Set Point AdjustmentSPDT120-240V, 25A 277V, 22A40°-120°F (5°-49°C)Corrosion-Resistant Class 1, Div. 1, Groups B, C, & D. Class II, Div. 1, Groups E, F & G
QX-1025396SPST120-240V, 25A 277V, 22A40°-120°F (5°-49°C)Class I, Div. 1, Groups C & D. Class II, Div. 1, Groups E, F, & G. Class III. IP66, Type 4
1036506BimetalSPDT480V, 15A40°-80°F (5°-25°C)Class I, Div. 1, Groups C & D. Class II, Div. 1, Groups E, F, & G. Class III. NEMA 4X

Remote Fan Switch:

CATALOG NO.SWITCH TYPERATINGHUBSDESCRIPTION
10017442-Position120/277V, 30A(2) 3/4" NPT HubsClass I, Div. 1, Groups C & D. Class II, Div. 1, Groups E, F, & G. Class III
10310422-Position110V, 6A(2) 3/4" NPT HubsClass I, Div. 1, Groups C & D. Class II, Div. 1, Groups E, F, & G. Class III. NEMA 4X

Dimensions and Clearances:

Side View

A diagram showing the side view of the unit heater with dimensions labeled X, MH, and clearance indicators.

Front View

A diagram showing the front view of the unit heater with dimensions labeled Y, Z, and clearance indicators.

SIZEXYZMHMW
122 1/2"19 3/8"16 1/16"11 1/16"9"
222 1/2"23 3/8"20 3/16"15 1/16"7"
322 3/4"27 3/8"24 3/16"19 1/16"5"

Ceiling Mounting Kit

A diagram illustrating the ceiling mounting configuration with a unit heater suspended from the ceiling, showing clearances.

Wall Mounting Kit

A diagram illustrating the wall mounting configuration with a unit heater attached to a wall, showing clearances.

Pole Mounting Kit

A diagram illustrating the pole mounting configuration with a unit heater attached to a pole, showing clearances.

How to Order

Example: GUX-233-F-A-010-6-U-DKS-00

  • Brand: GUX
  • Series: 233 = Unit Heater, Explosion Proof
  • Agency Approval: F = cCSAus Approval (standard), N = No Approval
  • Cabinet Size: A = Size 1, 12" Fan, 0-10 kW, B = Size 2, 16" Fan, 10.1-20 KW, C = Size 3, 20" Fan, 20.1-35 KW
  • kW*: 003, 005, 008, 010, 015, 020, 025, 030, 035
  • Temperature Rating: 6 = T3C Temperature Rating
  • Voltage & Phase:
    • Standard Offering-60Hz: C = 208V/1, D = 208V/3, J = 240V/1, K = 240V/3, U = 480V/3, Z = 600V/3.
    • Additional/Special Offering-60Hz: A = 115/1, B = 120/1, E = 220/1, F = 220/3, G = 230/1, H = 230/3, I = 347/1, N = 277/1. O** = Special, Q = 440/3, S = 460/3, X = 575/3.
    • Standard Offering-50Hz***: E = 220/1, F = 220/3, G = 380/3, H = 400/3, I = 415/3.
  • *Round up to the nearest whole kW
  • **For custom requests, contact Marley sales representative for assistance and additional detail
  • ***Option Code "H" indicates 50 Hz Heater
  • Contact Marley Sales Representative for additional configuration details
  • Product Serial Code**: Factory Install Options: D = Disconnect Switch, E = Group E (Metal Dust) Construction, K = "Warning" Pilot Light, L = "Heater On" Pilot Light, M = Manual Reset Thermal Cutout with Backup Contactor, S = Auto/Fan Selector Switch, S1 = Built-In Controls for Remote Auto/Fan Selector Switch, T = Adjustable Thermostat, T1 = Adjustable Thermostat for Wet Locations, V = 120 Volt Control Circuit, W = Wet Location Construction Features - IP55

About Marley Engineered Products

No matter the industry or application, Marley Engineered Products has a robust portfolio of innovative, reliable, high-performance comfort heating and ventilation solutions for all your heating needs. For more information or assistance on your next project, contact Technical Services at 800-642-4328.

Models: GUX-233-FA-0036C, GUX-233-FA-0036J, GUX-233-FA-0036D, GUX-233-FA-0036K, GUX-233-FA-0036U, GUX-233-FA-0036Z, GUX-233-FA-0056C, GUX-233-FA-0056J, GUX-233-FA-0056D, GUX-233-FA-0056K, GUX-233-FA-0056U, GUX-233-FA-0056Z, GUX-233-FA-0086C, GUX-233-FA-0086J, GUX-233-FA-0086D, GUX-233-FA-0086K, GUX Series Explosion Proof Unit Heater, GUX Series, Explosion Proof Unit Heater, Proof Unit Heater, Unit Heater, Heater

File Info : application/pdf, 7 Pages, 441.17KB

PDF preview unavailable. Download the PDF instead.

MEP GUX-HEP-Q Submittal 2025-07-web

References

Adobe InDesign 19.2 (Macintosh) Adobe PDF Library 17.0

Related Documents

Preview QMark GUX Series Explosion-Proof Unit Heater Specifications and Features
Detailed specifications, features, and technical data for the QMark GUX Series Explosion-Proof Unit Heater, designed for harsh environments. Includes electrical data, motor specifications, airflow details, and available options.
Preview QMark Explosion-Proof Series Convection Heater: Specifications and Features
Comprehensive product information for QMark's Explosion-Proof Series Convection Heaters, detailing specifications, applications, electrical packages, and construction for hazardous environments.
Preview CU900 Series Cabinet Unit Heater - QMark Unit Heaters
Detailed specifications, features, and optional accessories for the QMark CU900 Series Cabinet Unit Heater, designed for various commercial and institutional spaces.
Preview QTS Series Toe Space Fan-Forced Heater | QMark Product Specifications
Detailed product information for the QTS Series Toe Space Fan-Forced Heater by QMark. Learn about its features, ideal applications, technical specifications, available models, and dimensions for efficient floor-level heating.
Preview QMARK IUH Series Industrial Unit Heater: Specifications and Features
Detailed product information for the QMARK IUH Series Industrial Unit Heater, including technical specifications, model numbers, features, and installation dimensions. Ideal for industrial and commercial spaces.
Preview QMARK Explosion-Proof Convector: Specifications and Applications
Detailed submittal sheet and specifications for QMARK Explosion-Proof Convectors, designed for hazardous locations (Class I, II, Divisions/Zones) with various kW ratings, voltages, and control options.
Preview QMark SSAR Architectural SmartSeries Programmable Wall Heater Submittal Sheet
Submittal sheet for the QMark SSAR Architectural SmartSeries Programmable Wall Heater, detailing capacities, electrical data, dimensions, and optional accessories.
Preview QMark CWH3000 Series Commercial Fan-Forced Large Wall Heater Submittal Sheet
Submittal sheet for the QMark CWH3000 Series Commercial Fan-Forced Large Wall Heater, detailing specifications, capacities, electrical data, and optional accessories.