Installation Guide for TEKVOX models including: Quam System 15-8 2 Feet Tile Replacement Loudspeaker, 2 Feet Tile Replacement Loudspeaker, Tile Replacement Loudspeaker, Replacement Loudspeaker, Loudspeaker

QUAM-SYSTEM158-InstallationInstructions

Installation Instructions

31 mag 2024 — INSTALLATION INSTRUCTIONS. 1. Cut ceiling tile as required: 2' x 2' tile – No cutting required. 2' x 4' tile – Cut tile in half on 4' side.1 pagina

System 15/8 Ceiling Tile Speaker Installation Instructions

| TEKVOX


File Info : application/pdf, 1 Pages, 296.63KB

PDF preview unavailable. Download the PDF instead.

SYSTEM-15-8-Installation-Instructions
2 'X 2' TI L E RE P LACE ME NT LOUDSP EA KE R

SYSTEM 15/8

Installation Instructions

APPLICATION

Intended Use: Program Material: Installation:

Mass notification and emergency communications Signal tones and voice Fits into a 2' x 2' or 2' x 4' ceiling tile grid

INSTALLATION INSTRUCTIONS
1. Cut ceiling tile as required: 2' x 2' tile ­ No cutting required. 2' x 4' tile ­ Cut tile in half on 4' side.
2. Required only if using conduit clamp fitting other than what is provided with product.
a. Loosen, but do not remove screws on cover plate; slide plate to large keyhole position and lift plate from assembly.
b. Remove cable/conduit clamp fitting from cover plate; Install UL Listed metallic enclosure entry fitting for plenum cable or flex whip.
c. Feed supply cable through whip to speaker wires. Make connections per wiring diagram; Use appropriate connectors to meet any required codes.
d. Replace cover plate and tighten cover plate screws. When cover plate is secured, all connections/splices must be inside of the enclosure.
3. Make the necessary field wiring connections.

4. Place assembly onto ceiling grid, install 24" T-bar trim piece where required (not supplied).
TIE-OFF TAB 4X
IMPORTANT: · AHJ/ local codes may require tie-off to structure. Bend up
tie-off tabs as shown above and install as directed. · AHJ/ local codes may require tie-down to grid.
Recommended fasteners (not supplied): Erico/Caddy part ATA4i and 14"- 20 x 2" bolt, or equivalent. Attach to T-bar as directed with threaded hole over the edge of speaker assembly. Thread bolt through hole until snug against back of speaker assembly.

5. Place remaining ceiling tile into grid opening as required.

a. Connect the positive (red) wire from the SYSTEM 15/8 to the positive lead from the field wiring.
b. Connect the negative (black) wire from the SYSTEM 15/8 to the negative lead from the field wiring. All connections/splices must be inside of the enclosure.
c. Tighten screws on cable clamp.
IMPORTANT: · Verify all code requirements with local AHJ before selecting
connection method. · Using code compliant connectors for all field wiring.