Instruction Manual for systemair models including: CLEVA Remote Control, CLEVA, Remote Control, Control, Remote

Remote Control Manual ENG

CLEVA Climatizadores · Systemair


File Info : application/pdf, 16 Pages, 3.42MB

PDF preview unavailable. Download the PDF instead.

202501eng remote-control
Technical documentation
Cleva remote control

Contents

1. Introduction

03

2. Specs

03

3. Design

03

3.1 Dimensions

04

3.2 Installation

04

4. Wiring

04

5. Main functions

05

6. Operation

07

6.1 Operation mode and ventilation screen

07

6.1.1 Occupied/ unoccupied/ temporary screen

08

6.1.2 Temperature screen

10

6.1.3 Alarms and maintenance notices screen

10

6.1.4 Clock screen

14

6.1.5 Hourly program configuration

14

7. Alarms

15

systemair 2

1. Introduction
This document aims to comprehensively describe the operation of CLEVA remote control.
Warning Installation, mounting and maintenance operations must be carried out by qualified, authorised and trained operators according to local regulations in each country.
Warning
· This remote control is an electronic device and must be discarded according to applying European Directives and not as domestic waste.
· Exclusively use the approved means. · Properly meet all applicable local regulations.
2. Specs
This remote control features: · Room temperature measurement. · Temperature, ventilation, DHW and control configuration buttons. · Backlit LCD screen displaying: room temperature, operation mode, scheduler, notifications, alarms and clock
configuration. · All 8 buttons allow a friendly use of the remote control. · 2-wire connection to the main board through KNX PL-Link (PL+/ PL-), allowing both communication and power
supply. No need for screened cable although it must run separated from the main power supply cable to avoid EMC issues. · Communication/ power supply cable max length between remote control and main board: 1000 m. · Cable type: 2-thread twisted. Cross section: 0.5 ­ 1.5 mm2.
3. Design
3.1 Dimensions

Case dimensions

Mounting dimensions

3.2 Mounting and installation
The remote control fits both wall or standard junction box mounting. In the second case, check out box dimensions to secure compatibility.

3 systemair

Main components: 1. Wall mounting gasket. 2. Base frame including:
· Holes for junction box mounting screwing. · Guiding channels for cables. 3. Remote control. 4. KNX bus connector between remote control and main board. Before mounting and installation of this remote control please beware of the following: · Recommended installation height: 1,50 m. · Avoid voids, close curtains, doors or heat sources. · Avoid direct sunbeams and air currents. · Properly seal wall mounting or junction box cable pipes to avoid wrong sensor readings. · Respect the local regulations concerning admitted room conditions. · Follow the instructions included in the supplied remote control box.

4. Wiring
The unit´s electrical drawing together with the remote control supplied instructions manual are necessary for proper wiring.
Use 2-wire, twisted cable with cross section between 0.5 and 1.5 mm2 (depending on cable length). No need for screened cable although .
No need for screened cable although it must run separated from the main power supply cable to avoid EMC issues.

Conector

Pin Description

+ KNX PL-Link (positive)

- KNX PL-Link (negative)

Warning
Cables are not interchangeable! The device is protected against wrong wiring but communication would be affected. Connection can be carried out to any (+)/(-) pin pairs.

systemair 4

5. Main functions

Element 5 systemair

Description Occupied mode (hourly program) / unoccupied / temporary. Temporary mode: ventilation boost. Operation modes: Comfort / ECO / Unoccupied / STOP. Operation mode: automatic/ manual. Manual mode. Ventilation screen. Temperature screen. Notifications/ alarms screen. Clock screen. Means that elements are available. System processing. On. Notifications/ alarms list. Alarm type 1 (major). Active alarm. Present alarm. Alarm type 1 (major). Inactive alarm. Unacknowledged alarm. It is necessary to acknowledge the alarm before reset it. Alarm type 1 (major). Active and confirmed alarm. Present alarm. Alarm type 1 (major). Inactive and confirmed alarm. Alarm not present. Reset possible.

Element

Description Alarm type 2 (maintenance, light). Active alarm. Present alarm. Alarm type 2 (maintenance, light). Active alarm. Deactivated alarm yet not confirmed. Alarm not present. Alarm type 2 (maintenance, light). Deactivated and confirmed alarm. Alarm not present. Reset possible. All alarm notifications confirmed. Alarm reset once confirmed. Confirm. Cancel. Back. Exit / next. Up / down. Add hourly program interval. Edit. Erase. 1= Monday, 2= Tuesday, 3= Wednesday, 4= Thursday, 5= Friday, 6= Saturday, 7= Sunday. Time. Hourly program set. Hourly program. Outdoor temperature. Room temperature. Comfort mode active through digital input. Remote control in manual mode. ECO mode active through digital input. Remote control in manual mode. Unoccupied mode active through digital input. Remote control in manual mode.
systemair 6

6. Operation
6.1 Operation mode/ ventilation screen
Once the remote control is switched on a welcome screen shows basic unit information, including software version and serial number. After 3s the main screen is shown as below:

Button 1/5 2/6 3/7
4 / 8

Description

Mode selection: occupied/ unoccupied/ temporary.

· Occupied mode : The unit will assume the temperature/ airflow set points corresponding to the hourly program set.

· Unoccupied mode : The unit will assume the temperature/ airflow set points corresponding to the unoccupied function .

· Temporary mode : allows fan boost for limited time only.

Mode selection: automatic

/manual

· Automatic mode: no function. · Manual mode: allow to select temperature and airflow set points for comfort ,
ECO , unoccupied and unit stop .

Allow access to: · Ventilation · Temperature · Notifications/alarms · Clock

6.1.1 Occupied/ unoccupied/ temporary modes

Buttons 1 and 5 allow to switch among the following modes:

· Occupied mode . The unit will assume the temperature/ airflow set points corresponding to the hourly

program set only if the unit is running in

mode. Temperature set points can be selected through the

remote control. Airflow set points are factory-fixed to avoid any damage to the unit. Go to hourly program

screen to it set up.

· Unoccupied mode .The unit will assume the temperature/ airflow set points corresponding to the unoccupied function . The unit will run this mode unless the user changes it.

7 systemair

Button 1/5 2/3/4/5/6/7/8

Description Mode selection: occupied/ unoccupied/ temporary. · Occupied mode : The unit will assume the temperature/ airflow set points
corresponding to the hourly program set. · Unoccupied mode : The unit will assume the temperature/ airflow set points
corresponding to the unoccupied function. · Temporary mode : Allows fan boost for limited time only.
No function.

· Temporary mode operation mode.

: Allow fan max speed for up to 30 min. After up to 30 min the unit will go back the former

Button
1/5
2/6 3/7 4 / 8

Description Mode selection: occupied/ unoccupied/ temporary. · Occupied mode : The unit will assume the temperature/ airflow set points
corresponding to the hourly program set. · Unoccupied mode : The unit will assume the temperature/ airflow set points
corresponding to the unoccupied function . · Temporary mode : allows fan boost for limited time only.
No function.
Allows BOOST mode for up to 30 min (max fan speed).
Allow access to: · Ventilation . · Temperature . · Notifications/alarms . · Clock

·

mode. The unit will run in automatic mode according to the hourly program set

· Manual mode . This screen allows to select the different temperature/ airflow set points together with the temperature setting for each of them.

systemair 8

Button 1/5 2/6 3/7
4/8

Description

Mode selection: occupied/ unoccupied/ temporary. · Occupied mode : The unit will assume the temperature/ airflow set points
corresponding to the hourly program set. · Unoccupied mode : The unit will assume the temperature/ airflow set points
corresponding to the unoccupied function . · Temporary mode : allows fan boost for limited time only.

Mode selection: automatic

/ manual

This screen allows to select the different temperature/ airflow set points together with the temperature setting for each of them. · Comfort . · ECO . · Unoccupied . · Stop .

Allow access to: · Ventilation · Temperature · Notifications/alarms · Clock

6.1.2 Temperature screen
Allows to modify the set point for every operation mode: comfort, ECO and unoccupied.

Button 1/5 2/6 3/7 4/8
9 systemair

Description Mode selection: occupied/ unoccupied/ temporary. · Occupied mode : The unit will assume the temperature/ airflow set points
corresponding to the hourly program set. · Unoccupied mode : The unit will assume the temperature/ airflow set points
corresponding to the unoccupied function . · Temporary mode : allows fan boost for limited time only.
No function.
Temperature set up.
Allow access to: · Ventilation · Temperature · Notifications/alarms · Clock

6.1.3 Alarm notifications and maintenance notifications screen
Press 4 & 8 in the default screen to access the notification one. If no pending notifications/ alarms, the next screen is shown:
Alarm notification If an alarm is displayed , for example 1236, the following information is shown. The screen will blink until the alarm is acknowledged.
Press any button to access the following screen: Note represents the notification type: type 1 - alarm. If a new alarm happens, the former one is overwritten. The screen will keep on showing notification type 1
Press buttons 3 & 7 to access the next screen to permit alarm confirmation (it consists of a confirmation to the system that the alarm has been only acknowledged):
systemair 10

Press button 5 to request the system a batch confirmation of all alarms. While the system response comes the display shows:

The next screens pops up automatically upon all alarms confirmation.Through confirmation but remain active (root cause not solved).

the system shows alarms user

Once upon an alarm root cause is solved, the display will show . Then a reset can be performed. When confirmed and deactivated alarms , press button 7 to go to the notification reset screen. In the reset screen , press 3 or 7 to switch between notifications/ alarms and reset screens.

Alarms will be deleted after reset and the screen will set back to notifications.

11 systemair

Maintenance notifications
For notifications shown in the next screen

no pop-up screens are available. To check notifications, press 4 or 8 as
Note 2 shows the notification type: type 2 - maintenance. If a new
notification happens, the former one is overwritten. The screen will keep on showing notification type 2.

Upon confirmed notifications, press button 7 to access the next screen:

Press button 5 to request the system a batch confirmation of all notifications as long as they are properly managed. Whilst system response comes the display shows:

The next screens pops up automatically upon all alarms confirmation.

systemair 12

Maintenance notifications will be deleted after proper maintenance works execution. The main board will send confirmation to the remote control once the maintenance works have concluded.
6.1.4 Clock screen
Allows time and date set up.

Button 1/2/3/6/7 5
4/8

Description
No function.
Allows time and date set up.+
Allow access to: · Ventilation · Temperature · Notifications/alarms · Clock

6.1.5 Hourly program configuration

Hourly program permits set up of up to 15 different time intervals per day, for each 7 days of the week.

Three different set points can be selected for each interval: comfort , ECO modes has to be previously set up in the temperature set up screen.

and unoccupied . Each of these

In the main screen, press button 2 for 2 s to access the hourly program screen:

13 systemair

Button 1 2 / 6 3 / 4 / 5 / 7 8

Description Save chages. Day of the week. No function. Hourly program editing for the specific day of the week.

In the former screen, press button 8 to access the hourly program screen:

Button 1 2 / 4 / 6 3 / 7 5 8

Description Save chages. No function. Access to time intervals within a specific day of the week. New time interval. Edit time interval.

7. Alarms

Alarm codes breakdown below:

Alarm code 1000...1999 2000...2999

Alarm source Hardware. Software (application).

3000...3999

Communication.

9000...9999

Others.

Code 1001 1003 1004 1005

Description Temperature sensor failure.

Unit status Stop

Extract air temperature sensor failure. On

Outdoor air temperature sensor failure.

Stop

Anti-freeze air temperature sensor failure (heating coil)

Stop

Comments
The unit stops. Check electric connection and sensor status.
The unit is controlled through the extract air sensor. Check electric connection and sensor status.
The unit stops. Check electric connection and sensor status.
The unit stops. Anti-freeze alarm. Check electric connection and sensor status.

systemair 14

Code 1012 1013 1014 1017 1020 1032
1033
1034
1035 1041 2001 2005 2007 2010 2020 3011 3101

Description

Unit status

Room air temperature sensor failure. On

Indoor aire quality (IAQ) sensor failure. On

Extract indoor air quality (IAQ) sensor failure.

On

Room aire humidity sensor failure.

On

Clogged filters.

On

Supply air pressure sensor failure. Constant pressure control.

On

Extract air pressure sensor failure. Constant pressure control.

On

Supply air pressure sensor failure. Constant airflow control.

On

Extract air pressure sensor failure. Constant airflow control.

On

Anti-freeze air temperature sensor failure (combined coil).

Stop

Fire Alarm.

Stop

Supply air temperature exceeds limit values.

On

Anti-freeze warning (heating coil).

Stop

Overheating (heating coil).

Stop

Combined coil, frost warning.

Stop

Pressure sensor Modbus communication failure.

On

Room sensor KNX PL-Link communication failure.

On

Comments
The unit is controlled through the extract air sensor. Check electric connection and sensor status.
IAQ management is cancelled. Check electric connection and sensor status.
IAQ management is cancelled. Check electric connection and sensor status.
Humidity management is cancelled. Check electric connection and sensor status.
The unit keeps running. Replace filters.
Control switches to extract air pressure sensor. If both sensors fail a linear speed control is set. Check electric connections and sensor status.
Control switches to supply air pressure sensor. If both sensors fail the fans speed will be operation mode selected ones. Check electric connections and sensor status.
Control switches to extract air pressure sensor. If both sensors fail the fans speed will be operation mode selected ones. Check electric connections and sensor status.
Control switches to supply air pressure sensor. If both sensors fail a linear speed control is set. Check electric connections and sensor status.
The unit stops. Hot water valve opened. Check electrical connections and sensor status.
The unit stops because the fire alarm digital input is open.
Check the read value is correct and the sensor status.
The unit stops. Hot water valve opened. Check electrical connections and sensor status.
The unit stops. Temperature excedes limit values. Check the read value is correct and the sensor status.
The unit stops. Hot water valve opened. Check electrical connections and sensor status.
Fans speed will be operation mode selected ones.
Check connections and sensor status.

15 systemair

Systemair España · · February 20215· V2

Systemair España Calle Montecarlo 14 Fuenlabrada, Madrid 28942 Tel. +34 916 00 29 00 info@systemair.es
www.systemair.com



References

Adobe PDF Library 17.0 Adobe InDesign 20.1 (Windows)