Copeland Scroll Compressors for R290 Applications

ZB12KCU to ZB49KCU - Application Guidelines

About these guidelines

The purpose of these guidelines is to provide guidance in the application of Copeland scroll compressors in users' systems. They are intended to answer the questions raised while designing, assembling and operating a system with these products.

Besides the support they provide, the instructions listed herein are also critical for the proper and safe functioning of the compressors. The performance and reliability of the product may be impacted if the product is not used according to these guidelines or is misused.

These application guidelines cover stationary applications only. For mobile applications, please contact the Application Engineering department at Copeland as other considerations may apply.

Safety instructions

Copeland scroll compressors are manufactured according to the latest relevant European, UK and US safety standards. Particular emphasis has been placed on the user's safety.

ZB*KCU compressors are intended for installation in systems in accordance with the following directives and regulations:

  • Machinery Directive MD 2006/42/EC
  • Pressure Equipment Directive PED 2014/68/EU
  • Low Voltage Directive LVD 2014/35/EU
  • Supply of Machinery (Safety) Regulation 2016
  • Pressure Equipment (Safety) Regulation 2008
  • Electrical Equipment (Safety) Regulation 2016

They may be put to service only if they have been installed in systems according to instructions and conform to the corresponding provisions of legislation. For relevant standards please refer to the Manufacturer's Declaration, available at www.copeland.com/en-gb.

In order to keep the system compliant with the ATEX Directive 99/92/EC, all accessories to be fitted on the compressor, eg, oil level regulator, crankcase heater, discharge line thermostat, shall comply with the ATEX Directive 2014/34/EU Zone 2. If one of these accessories does not comply, the complete system will lose its compliance with the ATEX Directive 99/92/EC and therefore can be operated only in a non-flammable environment.

NOTE: Only dedicated compressors are allowed to be used with flammable refrigerants. Copeland marks all compressors that are qualified for flammable refrigerants with a sticker indicating the usage of such refrigerants. Systems using flammable refrigerants must be executed correctly while observing safety rules, as specified in corresponding safety standards such as, but not limited to EN 378. They must comply with any and all applicable legislation and regulations. Ensuring compliance remains the user's responsibility.

The Material Safety Datasheet (MSDS) of the refrigerant shall be considered – please check the document provided by the gas supplier.

These instructions shall be retained throughout the lifetime of the compressor. You are strongly advised to follow these safety instructions.

Icon explanation

  • ⚠️ WARNING: This icon indicates instructions to avoid personal injury and material damage.
  • High voltage: This icon indicates operations with a danger of electric shock.
  • ?❄️ Danger of burning or frostbite: This icon indicates operations with a danger of burning or frostbite.
  • ? Explosion hazard: This icon indicates operations with a danger of explosion.
  • ? Danger of explosive atmosphere: This icon indicates a risk of explosive atmosphere.
  • ? Fire hazard: This icon indicates a risk of flammable atmosphere.
  • CAUTION: This icon indicates instructions to avoid property damage & possible personal injury.
  • IMPORTANT: This icon indicates instructions to avoid malfunction of the compressor.
  • ℹ️ NOTE: This word indicates a recommendation for easier operation.

Product description

Compressor range

These application guidelines cover Copeland scroll compressor models ZB*KCU for medium-temperature refrigeration applications.

CompressorCooling capacity (kW)Motor
ZB12KCU2.82PFJN/TFDN
ZB17KCU3.93PFJN/TFDN
ZB20KCU4.99PFJN/TFDN
ZB25KCU5.73TFDN
ZB31KCU7.05TFDN
ZB37KCU8.41TFDN
ZB49KCU10.32TFDN

Evaporating temperature: -10 C; condensing temperature: 45 C; suction gas superheat: 10 K; liquid sub-cooling: 0 K; frequency: 50 Hz

Nomenclature

The model designation contains the following technical information about the compressors:

Diagram Description (Figure 1: Nomenclature): A diagram illustrating the compressor model designation breakdown. It shows fields for Compressor family (Z = Scroll), Nominal capacity (in kBTU/h at specified conditions), Refrigerant & Oil (U = R290 Refrigerant & POE Hatcol 4467), Bill of material number, Application range (Medium temperature), Model variation, and Motor version (PFJN = Single-phase motor, TFDN = Three-phase motor).

BOM variations

The BOM (bill of material) number at the end of the compressor designation indicates the different compressor layouts and details. ZB*KCU compressors are available in the following BOM versions:

BOMSuction & discharge connectionsT-BoxMounting partsFeatures
524Brazing stub tubesIP65For single compressor useSingle compressor
424WithoutTandem-ready

ZB*KCU compressors with BOM 524 and BOM 424 contain an IP65 terminal box, which complies with the ATEX Directive 94/9/EC part II 3G. The compressor label conforms to the ATEX Directive 2014/34/EU specifications and to the harmonized standard series EN 60079. The ATEX marking for applications in gas explosive atmosphere Zone 2 locations is as follows:

  • ATEX Directive 94/9/EC part: II 3G
  • Standard part (EN 60079-0, EN 60079-15): Ex nA IIA T2

Please refer to the Copeland price list for more details. The Declaration of Conformity is available from the manufacturer upon request.

Application range

Qualified refrigerant and oil

CompressorsZB*KCU
Qualified refrigerantR290
Qualified oil (factory charged)POE Hatcol 4467 (Ident Number 8410785)
Servicing oilPOE Hatcol 4467 (Ident Number 8410785)

Oil recharge values can be taken from the compressor nameplate or from Copeland Select software available at www.copeland.com/en-gb/tools-resources.

NOTE: R290 is classified as A3 flammable refrigerant.

Application limits

CAUTION Inadequate lubrication! Compressor breakdown! The superheat at the compressor suction inlet must always be sufficient to ensure that no refrigerant droplets enter the compressor. For a typical evaporator-expansion valve configuration a minimum stable superheat of at least 10 K is required.

For application envelopes and technical data, please refer to Copeland Select software available at www.copeland.com/en-gb/tools-resources.

PED category and maximum allowable pressures PS

The nameplate of the compressor contains information about the maximum allowable pressure PS, the minimum and maximum allowed temperatures TS, the internal free volumes and the fluid groups of the refrigerants qualified for the compressor model range. Values are given for both pressure ranges on low- and high-pressure sides.

CompressorPSTS max.Internal free volume (litres)
Low-pressure sideHigh-pressure sideLow-pressure sideLP sideHP side
ZB12KCU17 bar(g)28 bar(g)50 C4.10.5
ZB17KCU17 bar(g)28 bar(g)50 C4.20.5
ZB20KCU17 bar(g)28 bar(g)50 C4.30.5
ZB25KCU17 bar(g)28 bar(g)50 C6.40.6
ZB31KCU17 bar(g)28 bar(g)50 C6.40.6
ZB37KCU17 bar(g)28 bar(g)50 C6.40.6
ZB49KCU17 bar(g)28 bar(g)50 C6.40.6

The PED category is assigned according to the Pressure Equipment Directive PED 2014/68/EU. Requirements apply to the relevant pressure levels in the compressor when the product of "pressure relative to the environment" by "related internal free volume" (P x V) exceeds given limits. When calculating the PED category, the high- and low-pressure sides have to be calculated separately. The highest of the calculation results is considered.

The PED category also depends on the fluid group of the qualified refrigerants, also shown on the nameplate. A distinction is made between refrigerants of fluid group 1 (flammable) and fluid group 2 (non-flammable). The ZB*KCU compressors covered in these guidelines are operated with R290 which is classified as A3 refrigerant (fluid group 1).

Compressor rangeRefrigerantFluid groupPED category
ZB12KCU to ZB49KCUR2901II

Dimensions

Diagram Description (Figure 2: External dimensions - Front & top view): Two diagrams illustrating the external dimensions of the compressor from the front and top views, with various dimensions labeled A through O.

ModelBOMABCDEFGHJKLO
ZB12KCU524/424364.4338245173.569.6*165.8254.4253115.596.958.249
ZB17KCU387361264193.475.3*165.8254.4253115.596.958.249
ZB20KCU400.8375277206.175.3*165.8254.4253115.596.958.249
ZB25KCU ZB31KCU ZB37KCU ZB49KCU524/42444241029722379.6*185.5265.6254.4124.710362.144

NOTE: The connection in blue colour (dimension E) is an additional brazing connection for paralleling models (only on BOM version 424).

Installation

⚠️ WARNING High pressure! Injury to skin and eyes possible! Be careful when opening connections on a pressurized item.

Compressor handling

Transport and storage

⚠️ WARNING Risk of collapse! Personal injuries! Move compressors only with appropriate handling equipment according to weight. Keep in the upright position. Respect stacking loads according to Figure 3. Check the tilting stability and if needed take action to ensure the stability of the stacked loads. Keep the packaging dry at all times.

Respect the maximum number of identical packages which may be stacked on one another, where "n" is the limiting number:

  • Transport: n = 1
  • Storage: n = 2

Diagram Description (Figure 3: Maximum stacking loads for transport and storage): An illustration showing the maximum number of compressor packages that can be stacked for transport (n=1) and storage (n=2).

The compressor tilt angle should not exceed 30 during transport and handling. This will prevent oil from exiting through the suction stub. A tilt angle of maximum 45 is allowed for a very short time. Tilting the compressor more than 45 might affect its lubrication at start-up.

NOTE: The compressor is pre-charged with dry air to avoid any moisture contamination.

Positioning and securing

IMPORTANT Handling damage! Compressor malfunction! Only use the lifting eyes whenever the compressor requires positioning. Using discharge or suction connections for lifting may cause damage or leaks.

The compressor should be kept vertical during handling.

The discharge connection plug should be removed first before pulling the suction connection plug to allow the dry air pressure inside the compressor to escape. Pulling the plugs in this sequence prevents oil mist from coating the suction tube making brazing difficult. The copper-coated steel suction tube should be cleaned before brazing.

The plugs must be removed as late as possible before brazing so that the air humidity does not affect the oil characteristics.

For ZB*KCU compressors, as oil might spill out of the suction connection located low on the shell, the suction connection plug must be left in place until the compressor is set into the unit.

No object, eg, a swaging tool should be inserted deeper than 51 mm into the suction tube as it might damage the suction screen and motor.

Installation location

These compressors shall be installed in a non-hazardous atmosphere for normal operation. In the unlikely event of a circuit leakage, flammable refrigerant must not stagnate around the compressor and a flammable atmosphere may only remain for a short period.

Ensure the compressors are installed on a solid level base. For single compressor applications, the compressor tilt angle during operation should not exceed 15 to allow adequate lubrication. For multiple-compressor parallel configurations, the compressors must be positioned completely vertically on a totally horizontal surface or rail.

Mounting parts

The compressors are designed to be mounted on vibration absorber grommets. The grommets dampen the start-up surge of the compressor and minimise sound and vibration transmission to the compressor base during operation. The metal sleeve inside is a guide designed to hold the grommet in place. It is not designed as a load-bearing member, and application of excessive torque to the bolts can crush the sleeve. Its inner diameter is approximately 8.5 mm to fit, eg, an M8 screw. The mounting torque should be 13 1 Nm. It is critically important to avoid compressing the grommets.

If the compressors are mounted in tandem or used in parallel, then the hard mountings (bolt M9 5/16") are recommended. The mounting torque should be 27 1 Nm.

See Copeland spare parts catalogue at www.copeland.com/en-gb/tools-resources for references.

Diagram Description (Figure 4: Mounting parts): Images showing soft mounting parts for ZB12KCU to ZB49KCU compressors, including vibration absorber grommets and metal sleeves.

Brazing procedure

⚠️ WARNING Air/flammable refrigerant mixture! Creation of a potentially flammable atmosphere! Fire hazard! Remove all refrigerant before opening the system. When working on a refrigerant-filled system, make sure to follow the safety and working instructions given in Chapter 6 "Maintenance & repair".

⚠️ WARNING High temperature! Burning! Proceed with caution when brazing system components. Do not touch the compressor until it has cooled down. Ensure that other materials in the area of the compressor do not come into contact with it.

CAUTION Blockage! Compressor breakdown! Maintain a flow of oxygen-free nitrogen through the system at very low-pressure during brazing. Nitrogen displaces the air and prevents the formation of copper oxides in the system. If allowed to form, the copper oxide material can later be swept through the system and block screens such as those protecting capillary tubes, thermal expansion valves and accumulator oil return orifices.

Contamination or moisture! Bearing failure! Do not remove the connection plugs until the compressor is set into the unit. This minimises any entry of contaminants and moisture.

General brazing procedure

Copeland scroll compressors have copper-plated steel suction and discharge stub tubes. These stub tubes are far more robust and less prone to leaks than copper tubes. Make sure the brazing procedures are carried out in an appropriate manner taking into account the different thermal properties of steel and copper.

Diagram Description (Figure 5: Brazing areas): A diagram illustrating the three numbered areas (1, 2, 3) on a compressor stub tube where heat should be applied during brazing.

Refer to Figure 5 and procedure below for the brazing of the stub tube connections of a scroll compressor.

  • It is mandatory to flush oxygen-free nitrogen through the piping during the brazing process of systems using A3 flammable refrigerants.
  • The copper-coated steel tubes on scroll compressors can be brazed in approximately the same manner as any copper tube.

Recommended brazing materials: any Silfos material is recommended, preferably with a minimum of 5 % silver. However, 0 % silver is acceptable.

  • Be sure tube fitting inner and outer surfaces are clean prior to assembly.
  • Using a double-tipped torch, apply heat in area 1.
  • As the tube approaches brazing temperature, move the torch flame to area 2.
  • Heat area 2 until braze temperature is attained, moving the torch up and down and rotating around the tube as necessary to heat the tube evenly. Add braze material to the joint while moving the torch around the joint to flow braze material around the circumference.
  • After the braze material flows around the joint, move the torch to heat area 3. This will draw the braze material down into the joint. The time spent heating area 3 should be minimal.
  • As with any brazed joint, overheating may be detrimental to the final result.

NOTE: Since the discharge stub contains a check valve, care must be taken not to overheat it to prevent brazing material from flowing into it.

Brazing procedure for ZB*KCU compressors in parallel applications

⚠️ WARNING Air/flammable refrigerant mixture! Creation of a potentially flammable atmosphere! Fire hazard! Remove all refrigerant before opening the system. When working on a refrigerant-filled system, make sure to follow the safety and working instructions given in Chapter 6 "Maintenance & repair".

⚠️ WARNING High oil temperature! Risk of ignition and personal injuries! The high temperature generated during the brazing process can exceed the flash point of the oil and consequently lead to vapour/air mixture ignition. Make sure to always keep the oil temperature below its flash point. Never braze pipes with oil inside.

Only compressor models officially approved by Copeland in the qualified configuration may be used for parallel applications. For ZB*KCU compressors in parallel applications with passive oil management, additional precautions shall be taken before brazing the oil and gas equalization ports. The sequence shall be as follows:

First, install the compressors on the base frame and tilt the assembly so that oil will not be lost when opening the cap. The gas and oil equalization line assembly should be ready for brazing at this point. For new compressors, release the protective gas charge: the rubber plug from the discharge port of the compressor has to be removed first, then the rubber plug from the oil port.

Most probably the oil port will be coated with some oil. It is mandatory to clean out the oil before brazing. If the inner surface is contaminated with oil the brazing material will not adhere to the surface and the joint will fail, generating leakage. The oil should be carefully wiped out with industrial absorption paper. Industrial solvents on a clean cloth can be used too but only with great care. Note that emery cloth will not remove the oil.

It is possible that the oil cannot be completely cleaned out. In this case additional measures should be taken. For instance, if a connection is coated with flux then the residual oil will be removed when brazing thanks to the applied heat.

Pressure safety controls

Pressure protection devices to be used in ATEX Zone 2 locations must comply with the ATEX Directive requirements. Non ATEX-certified pressure protection devices shall NOT be used in ATEX Zone 2 locations.

ATEX-approved pressure protection devices are available from Alco Controls. Please refer to the dedicated "Product Guide for R290".

High-pressure protection

Applicable regulations and standards, for example EN 378-2, shall be followed to apply appropriate control and ensure that the pressure never exceeds the maximum limit.

High-pressure protection is required to stop the compressor operating outside the allowable pressure limits. The high-pressure control must be installed correctly, which means that no service valve is allowed between the compressor and the pressure protection.

The high-pressure cut-out setting shall be determined according to the applicable standard, the type of system, the refrigerant and the maximum allowable pressure PS.

Low-pressure protection

CAUTION Operation outside the application envelope! Compressor breakdown! A low-pressure protection shall be fitted in the suction line in order to stop the compressor when it operates outside the envelope limits. Do not bridge or bypass the low-pressure limiter.

Applicable regulations and standards shall be followed to apply appropriate control and ensure that the pressure is always above the required minimum limit.

Low-pressure protection is required to stop the compressor operating outside the allowable envelope limits. The low-pressure control must be installed correctly into the suction line, which means that no service valve is allowed between the compressor and the pressure protection.

The minimum cut-out setting shall be determined according to the refrigerant and the allowed operation envelope – see Select software at www.copeland.com/en-gb/tools-resources.

System protection for operation below atmospheric pressure

⚠️ WARNING Operation below atmospheric pressure! Fire hazard! During operation below atmospheric pressure, a flammable mixture can form inside the system. Ensure system tightness to prevent any ingress of air.

ZB*KCU compressors in R290 applications may be operated below atmospheric pressure only when installed in hermetically sealed systems. For non-hermetically systems, the pressure must always be above atmospheric pressure. The operating pressure must be limited as defined by the operation envelope – refer to the technical documentation.

When systems with ZB*KCU compressors operate below atmospheric pressure, special requirements for safety and tightness apply and the following precautions must be observed:

  • Check all the critical points on the system and piping connections; tightness has to be ensured also at very low pressure.
  • Minimum absolute working pressure: 0.5 bar.
  • The installation of mechanical high-pressure and low-pressure cut-outs is mandatory. For systems provided with a service shut-off valve on the discharge side of the compressor, only a mechanical pressure cut-out shall be used. Electronic pressure limiters, which could cause delayed sensor response, are not allowed.
  • The high- and low-pressure cut-outs must be installed correctly on the discharge and suction lines, which means that no service valve is allowed between the compressor and the pressure protection (refer to EN 378 or ISO 5149).
  • A discharge temperature control is mandatory to stop the compressor when the maximum discharge temperature is exceeded – see section 3.7 "Discharge gas temperature protection".
  • Additional warning notices shall be affixed to any system equipped with shut-off valves. The warnings must contain instructions to open the shut-off valves completely after each repair or maintenance work. The compressors may only be energized when the safety measures (high- and low-pressure cut-outs and discharge temperature cut-out) have been checked and verified to be operational.

NOTE: All of the above points must be fulfilled. If only one of them is not complied with, the compressor shall not be operated below atmospheric pressure.

Crankcase heater

⚠️ WARNING Ignition source in a potentially flammable atmosphere! Fire hazard! The crankcase heater, as specified by Copeland (see spare parts catalogue), is not an ignition source during normal operation in A3-refrigerant systems but could become one if not installed properly according to installation instructions. Ensure correct electrical and mechanical installation.

⚠️ CAUTION High temperature! Overheating and burnout! Compressor damage! Follow assembly instructions. If installed incorrectly, the heater can reach temperatures over 150 C. In this case, turn off the heater and do not touch the surface. Keep wiring cables away from the heating elements. Never apply power to the crankcase heater in free air, before the crankcase heater is installed on the compressor or when it is not in complete contact with the compressor shell.

IMPORTANT Oil dilution! Bearing malfunction! Turn the crankcase heater on 12 hours before starting the compressor.

A crankcase heater is used to prevent refrigerant from migrating into the shell during standstill periods. The installation of a crankcase heater is required when the system charge exceeds the charge limits indicated in Table 7. This requirement is independent from system type and configuration.

Compressor modelRefrigerant charge limitCrankcase heater
PositionHeight
ZB12KCU & ZB17KCU1.4 kg5 – 12 mm
ZB20KCU1.5 kg
ZB25KCU to ZB49KCU1.6 kg9.5 – 41 mm

The initial start-up in the field is a very critical period for any compressor because all load-bearing surfaces are new and require a short break-in period to carry high loads under adverse conditions. The crankcase heater must be turned on a minimum of 12 hours prior to starting the compressor. This will prevent oil dilution and bearing stress on initial start-up. The crankcase heater must remain energized during compressor off cycles.

Caution: Crankcase heaters must be properly grounded!

NOTE: Because of the continuous possibility of circuit leakage, only a crankcase heater proven as non-source of ignition can be used. Copeland has qualified crankcase heaters for individual compressor ranges and applications with flammable refrigerants. These crankcase heaters are verified as non-sources of ignition if properly installed. Please refer to the Copeland spare parts catalogue available at www.copeland.com/en-gb/tools-resources to select the appropriate crankcase heater model.

For installation, the manufacturer/installer shall follow the recommendations mentioned below.

Assembly instructions
  • Choose the appropriate model according to compressor size and required wattage.
  • Check the compressor application guidelines for crankcase heater connection and operation.
  • Position the crankcase heater between the lower cover and the lower bearing weld projection (Fig. 6).
  • Fit the heater horizontally around the crankcase, ensuring that it is in close contact with the compressor housing along the entire length.
  • Avoid having the heating portion of the heater in contact with any weld projection (Fig. 7 & 8).
  • Avoid having the assembly heater inclined (Fig. 9).
  • Close the lock and tighten the screw, torque: 2 - 3 Nm.

The excess clamp bracket may be trimmed. Sharp edges must not come into contact with wires.

The presence of the heater shall be made evident by the posting of caution signs or markings at appropriate locations.

Diagram Description (Figures 6-9): Illustrations showing correct (Figure 6) and incorrect (Figures 7, 8, 9) installation positions for the crankcase heater.

Discharge gas temperature protection

CAUTION Inadequate lubrication! Scroll set damage! All ZB*KCU compressors must be equipped with an external discharge gas temperature protection.

A good system control shall prevent the system from operating outside the published operating envelope and acceptable superheat range, whatever the climatic conditions and the capacity demand. However, under some extreme operating conditions (such as loss of charge or improper control operation), the internal discharge gas temperature reached can cause compressor damage. In order to ensure positive compressor protection, discharge gas temperature protection is required for any application with Copeland compressors.

The maximum discharge gas temperature is 135 C for models ZB12KCU to ZB20KCU and 130 C for models ZB25KCU to ZB49KCU.

Discharge gas temperature protection is the "fall-back" for failure of the system control. It is essential that proper control of both the evaporating and condensing pressures and the superheat is maintained and has the ability to cope with all likely conditions and high loads. Reliance on protectors will cause inadequate system performance and short cycling.

NOTE: The maximum discharge gas temperatures indicated in this chapter are valid for safe operation within the approved application envelope. The discharge line thermostat has the function of a compressor protection device; it is not designed to control the operating envelope. For compressor envelope control, an additional control device or regulation must be used.

Excessive discharge gas temperatures

A few of the possible consequences of excessive discharge gas temperatures are listed below:

  • Since the oil circulates in the system with the refrigerant, it is subjected to high discharge gas temperatures. If the discharge gas temperature becomes too high, the so-called "cooking" effect will occur (heating of oil under exclusion of air). Carbon deposits can form at points of high temperature, for example on the valves, oil channels, oil filters, etc. The oil lubricity will be reduced and a progressive wear process will occur which will prematurely damage the compressor.
  • The stability of the refrigerant can also be affected, particularly if traces of contaminant are present.

The problems described above frequently occur simultaneously, particularly since the chemical reaction speed approximately doubles with every 10 C temperature rise. This directly leads to chemical reactions of the oil with the refrigerant and the compounds extracted from sealants and insulation material. As a consequence, contaminants of various types, among them acids, will form inside the system.

Discharge line thermostat

ZB*KCU compressors have no internal discharge gas temperature protection. Therefore, an external discharge line thermostat must be installed.

Copeland can supply an ATEX discharge line thermostat which can be used with A3 refrigerants. It can also be used in an ATEX zone 2 or non-ATEX environment. This thermostat is marked with a special ATEX label – see Figure 10.

Diagram Description (Figure 10: ATEX discharge line thermostat and ATEX label): Images showing the ATEX discharge line thermostat and its associated ATEX compliance label.

Technical data of the discharge line thermostatZB*KCU
Compressor rangeZB*KCU
Voltage120-240 VAC
Maximum amperage5 A / 240 V
Operating temperaturesOpen 134 C ( 4 K)
Close 106 C ( 8 K)
Wire insulation maximum temperature150 C
Clips for tube 12.7 mm (1/2")

To be ATEX-compliant, the cable ends of the thermostat must be connected with suitable cable glands and electrical enclosure to achieve a minimum protection degree of IP54 according to IEC 60079-15, clause 6.3. When connecting the cable ends, a creepage distance of minimum 4 mm and a clearance distance of 2.5 mm between the conductive parts at different potentials must be maintained. Maximal voltage and amps values for the thermostat and a protection against electrical shock must be respected during the installation.

Additionally, the ATEX compliance requires a protection of the thermostat body against mechanical damage, according to IEC 60079-0, clause 26.4.2, table 13. There is no need for an additional housing around the thermostat body. Protection against mechanical damage to the thermostat can be achieved with an overall cover or box placed around the compressor or refrigerant system.

To ensure proper functioning and to avoid false readings, the discharge line thermostat must be installed and insulated according to the procedure and recommendations hereunder.

Assembly of the discharge line thermostat
  • Install the discharge line thermostat on the discharge tube 120 mm from top cap.
  • Snap the retainer clip over the tube and onto the thermostat.
  • The thermostat should be placed on the discharge tube so that its body is in upward position on a horizontal tube installation. Ensure that the thermostat is not tilted.
  • The wire must not be in contact with the top cap of the compressor or the discharge tube. Care should be taken to route wires so that they do not come into contact with sharp objects.
  • To avoid any impact on tripping temperature by the ambient, the discharge line thermostat must be insulated.
  • Wrap thermal insulation around the pipe left and right of the thermostat and secure it with plastic straps.
  • Wrap a second layer of insulation around the first one and around the thermostat and secure it with plastic straps.

Internal pressure relief valve

There is an internal pressure relief valve on ZB*KCU compressors. It opens at a differential pressure of 28 bar 3 bar between high- and low-pressure sides. A high-pressure protection must be provided by the system manufacturer/installer for each system and according to EN 378-2.

The IPR valve is a safety device, not an HP switch. It is not designed for repeated operation and there is no guarantee that it will reset correctly if it does have repeated operation

Discharge check valve

ZB*KCU compressors contain an internal check valve on the discharge connection. The discharge check valve prevents the high-pressure discharge gas from flowing rapidly back through the compressor after shutdown.

NOTE: This check valve cannot be used with recycling pumpdown because it is not entirely leak-proof.

Filter screens

CAUTION Screen blocking! Compressor breakdown! Use filter screens with at least 0.6 mm openings.

The use of filter screens finer than 30 x 30 mesh (0.6 mm openings) anywhere in the system should be avoided with these compressors. Field experience has shown that finer mesh screens used to protect thermal expansion valves, capillary tubes or accumulators can become temporarily or permanently plugged with normal system debris and block the flow of either oil or refrigerant to the compressor. Such blockage can result in compressor failure.

Mufflers

Gas flow through scroll compressors is continuous with relatively low pulsation. External mufflers may not be required on Copeland scroll compressors. Due to system variability, individual tests should be conducted by the system manufacturer to verify acceptable levels of sound and vibration.

If adequate attenuation is not achieved, use a muffler with a larger cross-sectional area to inlet area ratio. A ratio of 20:1 to 30:1 is recommended. A hollow shell muffler will work quite well. Locate the muffler at minimum 15 to maximum 45 cm from the compressor for the most effective operation. The farther the muffler is placed from the compressor within these ranges, the more effective. Choose a muffler with a length of 10 to 15 cm.

Sound shell

At this time, no sound shell attenuation for ZB*KCU compressors is available from Copeland. If a sound shell is needed, particular attention shall be paid to its non-electrostatic properties – see EN 60079-0, clause 7.4.

Insulation material

Insulation material is commonly used in a system to insulate the suction line, suction accumulator, expansion valve bulb or discharge line thermostat. When choosing the insulation material for R290 applications, particular attention shall be paid to its non-electrostatic properties, as it could be a potential ignition source.

Sound and vibration

⚠️ WARNING Vibrations! Creation of a flammable atmosphere! Carefully check the system for vibrations.

Vibrations during compressor operation can cause cracks which could lead to refrigerant leakage. This situation must be avoided by the system manufacturer/installer. To this end, the pipework must be carefully designed when connecting a scroll compressor to a system.

Diagram Description (Figure 11: Example of suction tube design): An illustration showing an example of a flexible suction tube design intended to accommodate compressor movement and minimize vibration transmission.

A scroll compressor makes both a rocking and twisting motion and enough flexibility must be provided in the pipework to allow starting, stopping and steady state running of the compressor without transmitting excessive stress into any line attached to the unit. In a split system, the most important goal is to ensure minimal vibration in all directions to avoid transmitting vibrations to the structure to which the lines are fastened.

Under some conditions, the Copeland scroll has a normal starting rotational motion that can transmit a transient noise along the lines. This may be particularly pronounced in compressors using a three-phase motor due to their inherently higher starting torque. This phenomenon, like the one described previously, can easily be avoided by using standard line isolation techniques.

The sound level of a system is the result of design, quality and application. Scroll compressors sound power levels generally increase with the compressor model capacity and the condition pressure ratio.

Compressor oil return, oil balancing, refrigerant floodback and oil dilution tests

CAUTION Inadequate lubrication! Bearing and moving parts destruction! Ensure adequate oil return from the system into the compressor at any time. No liquid refrigerant return to the compressor. Liquid refrigerant dilutes the oil, could wash the oil off the bearings and moving parts and could lead to overheating and compressor failure.

The system piping must be carefully designed to ensure sufficient refrigerant gas velocity, so that oil returns to the compressor at all times and conditions. Individual piping diameter calculation depends on the refrigerant properties, pressure level, mass flow, and density.

For other system components such as suction accumulators, the extra amount of oil which will be required in the system must be checked with the suppliers of these components. If needed, the system should be pre-charged accordingly including the additional oil quantity.

Once a new system design is set and assembled, a functional test is required. The functional test includes a qualification for the general system oil return, a refrigerant floodback test and an oil dilution test. Systems with multiple compressors (two, three, or more) require additional oil balancing qualification between the parallel compressors.

A sample compressor equipped with an external oil sight tube can be ordered from Copeland for lab testing.

Records of the evaporating temperature and the bottom shell temperature shall be taken with a high sampling rate during the entire oil return or oil balance testing and under all tested conditions. The liquid level in the sight tube has to be observed and recorded too. Testing conditions shall include defrost and varying loads. If the system is reversible, the tests should be conducted in both operation modes.

System engineers should review the system design and operation to identify the critical conditions and to check oil return, oil balancing, liquid floodback and oil dilution. For discussion of individual test results and system behaviour, eg, with regard to oil dilution, please contact the Application Engineering department. Typically, the following situations should be considered:

  • In single compressor systems: to check oil return, testing conditions shall be at minimum mass flow and minimum density of suction gas in continuous and frequent start/stop cycling.
  • In multiple compressor systems: to check oil return and oil balancing in the tandem or trio, testing conditions shall be at the corner points of the system application envelope in continuous and frequent start/stop cycling.
  • In all systems: to test liquid floodback and oil dilution, all possible transient operation conditions in the system should be checked, eg, compressor frequent start/stop, compressor start after long off time with migration, defrost, switching between the operation modes in reversible systems, load changes, fans or pumps cycling at low load and more. To evaluate the risk of liquid floodback and oil dilution, please refer to the chart in Figure 12.

Diagram Description (Figure 12: Oil dilution chart): A graph plotting Evaporating Temperature (te) against the difference between bottom shell temperature (tb) and evaporating temperature (tb-te). It shows a "Safe Area" and an "Unsafe Area" (Too much refrigerant dilution). A small diagram indicates the oil temperature sensor position.

The bottom shell temperature together with the evaporating temperature gives an indication whether liquid refrigerant is returning or diluted in the compressor oil sump. The compressor sump temperature must remain in the (green) safe area, as shown in the chart in Figure 12. In case of operation in the (red) unsafe area, adjustments are required in order to modify the system design, refrigerant charge or superheat setting of the expansion device(s). The bottom shell temperature should be measured accurately. The thermo-probe must be properly insulated and positioned on the opposite side of the sight glass or at an angle of 90 clockwise from the suction inlet with view on the top.

Suction line accumulators

Due to Copeland scroll's inherent ability to handle liquid refrigerant, for example in flooded start and defrost cycle operation, an accumulator is not required in most systems.

To determine if a suction line accumulator is required, the system designer must check this with an appropriate test scenario. See section 3.15 "Compressor oil return, oil balancing, refrigerant floodback and oil dilution tests".

If an accumulator is used, the oil-return orifice should be from 1 to 1.4 mm in diameter for all ZB*KCU models depending on compressor size and compressor floodback results. To protect this small orifice from plugging with system debris a large-area protective screen no finer than 30 x 30 mesh (0.6 mm openings) is required. Tests have shown that a small screen with a fine mesh can easily become plugged causing oil starvation to the compressor bearings. The size of the accumulator depends upon the operating range of the system and the amount of sub-cooling and subsequent head pressure allowed by the refrigerant control. For the correct selection and size of the suction line accumulator, refer to the manufacturer's specifications.

Electrical connection

General recommendations

⚠️ WARNING Conductor cables! Electrical shock hazard! Shut off power supply before undertaking any task on electrical equipment.

⚠️ WARNING Ignition source in a potentially flammable atmosphere! Fire hazard! The electrical connection of the scroll compressor is not an ignition source during normal operation in a flammable refrigerant system but could become one if not installed properly according to installation instructions. Ensure correct mechanical and electrical installation. System capacitors may remain charged for several minutes after shutdown. Before starting to work on the electrical installation make sure sparking is not possible. Continuously check if the ambient atmosphere is non-flammable when working on the electrical installation.

⚠️ WARNING Run capacitors! Sparking in a potentially explosive atmosphere! Explosion hazard! Single-phase compressors must be electrically connected to a run capacitor. Run capacitors have a potential ignition source and do not comply with ATEX requirements. The installation is only allowed in a non-explosive atmosphere, eg, an enclosure for ATEX 94/9/CE Zone 2 according to the relevant standard EN 60079.

The compressor terminal box has a wiring diagram on the inside of its cover. Before connecting the compressor, ensure the supply voltage, the phases and the frequency match the nameplate data.

For safety reasons, Copeland recommends that the electrical installation be executed in compliance with standard EN 60204-1 and/or other standards and regulations of application when dealing with A3 flammable refrigerants.

When installing ZB*KCU compressors in a system, the following measures must be taken:

  • To ensure the wires are properly terminated, the correct terminal and clamping tool for the selected wire size must be used.
  • The ground wiring must conform to local regulations and codes of practice (only the supplied parts must be used).
  • The grounding screws must be torqued as per Table 10 in section 4.3 "Terminal box".
  • A cable strain-relief device must be added.
  • The cable and wires must be protected against sharp edges.

Electrical installation

Recommended wiring diagrams are shown in Figures 14 & 15 next pages.

NOTE: A contactor K2 has to be used for the safety chain to comply with EN 60335 and EN 60204-1.

NOTE: It is mandatory to install a residual current device (RCD) in any electrical system associated with ZB*KCU compressors and flammable refrigerants such as R290. The purpose of the RCD is to detect current leaks to the ground in case of electrical issues, for example with the terminal connection pins or other electrical accessories.

Diagram Description (Figure 13: Residual current device (RCD)): An icon representing a Residual Current Device (RCD).

Diagram Description (Figure 14: Single-phase wiring diagram): A schematic diagram illustrating the power and control circuits for single-phase compressors (PF*) with internal motor protection, including motor terminal connections and a legend for components.

CompressorRun capacitorIdent nr.Part nr.
ZB12KCU-PFJN45 F / 370 V8414743914-0009-02
ZB17KCU-PFJN50 F / 370 V8414754914-0009-03
ZB20KCU-PFJN60 F / 370 V8414765914-0009-04

Diagram Description (Figure 15: Three-phase wiring diagram): A schematic diagram illustrating the power and control circuits for three-phase compressors (TF*) with internal motor protection, including motor terminal connections and a legend for components.

NOTE: For the selection of Copeland qualified run capacitors, please refer to the Copeland spare parts catalogue available at www.copeland.com/en-gb/tools-resources.

Terminal box

⚠️ WARNING Ignition source in a potentially flammable atmosphere! Fire hazard! Particular attention must be paid in A3-refrigerant systems as any work on the energized terminals in the compressor terminal box could create an ignition. Do not touch the energized terminals with a tool or cable when the compressor is energized. Compressors operating with flammable refrigerants shall use only the qualified terminal box supplied with the compressor.

CAUTION Mechanical stress or shock! Overheating! Terminal Fusite damage and leakage! Mechanical stress and shocks to the Fusite must be avoided as they could damage the glass and/or ceramic. This might result in hermeticity failure or loss of terminal performance. Precautions are required to prevent striking or bending of pins. Bent or damaged pins may result in loss of hermeticity and/or terminal performance. Ensure correct connection of cables to the compressor terminal Fusite to avoid local overheating of Fusite pins which might lead to refrigerant leaks.

Cable glands have an influence on the protection class of the terminal box. Copeland strongly recommends using appropriate cable glands according to EN 50262 in order to reach the rated protection class. An example of correct electrical installation is shown in Figure 17 below.

ZB*KCU compressors with BOM 524 (single compressor) and 424 (tandem-ready compressor) are supplied with an IP65 metal terminal box, which is ATEX-compliant and can be used in an ATEX Zone 2 environment, in accordance with ATEX Directive 94/9/EC part II 3G.

The maximum thickness of cable connectors for the terminal block shall be 1 mm for all models – see Figure 16.

Diagram Description (Figure 16: Maximum thickness of cable connectors): An illustration showing the maximum allowable thickness for cable connectors in the terminal block.

Diagram Description (Figure 17: IP65 T-Box with terminal block for ring terminal connectors): A photograph showing the IP65 terminal box with a cable gland and terminal block.

The first two nuts already installed on the Peko bolts shall not be removed, as they will ensure good tightness of the terminal box assembly. Make sure to assemble the ground connection of the Peko bolt with a torque of 4 - 4.4 Nm and the ground connection between the cover and the body of the terminal box with a torque of 1.8 - 2 Nm.

Assemble the cable gland M25 with a torque of 9.8 - 10 Nm. The cable gland is designed for cable diameters of 10 to 17 mm – see Figure 18 & Table 10. The degree of protection (IP) will be safeguarded only if sealing and cable glands are properly assembled. Only run the compressor with permanently wired cables. The system manufacturer/installer shall provide the required strain relief.

Finally, close the cover of the terminal box applying a torque of 1.8 - 2 Nm. The degree of protection (IP) will be safeguarded only if the cover is properly assembled.

Diagram Description (Figure 18: T-Box with T block and T-Box cover): Diagrams showing the terminal block (T-block) and the terminal box cover.

ItemSymbolTorqueDiameter
Grounding nut4 - 4.4 Nm
Cable gland9.8 – 10 NmCable 10 - 17 mm
Grounding screw1.8 – 2 Nm
Connection screws1.4 – 1.7 Nm

Motor insulation

The motor insulation material is class "B" (TF*) within maximum allowable operating temperatures according to IEC 34-1 or DIN 57530.

Motor protection

In addition to the internal motor protection, fuses must be installed before the compressor. The selection of fuses has to be made according to EN 60269-1 or EN 60204-1 and compressor maximum operating current (MOC). Not installing fuses before the compressor or selecting inappropriate fuses may result in compressor failure.

Conventional inherent internal line break motor protection is provided for the complete range of ZB*KCU compressors.

High-potential testing

⚠️ WARNING High-potential testing in a flammable atmosphere! Fire hazard! Make sure the atmosphere is non-flammable before performing high-potential testing. Make sure the electrical connections are properly made. Perform the high-potential test only after passing system strength and tightness tests according to EN 378.

⚠️ WARNING Conductor cables! Electrical shock hazard! Shut off power supply before high-potential testing.

CAUTION Internal arcing! Motor destruction! Do not perform high-voltage or insulation tests if the compressor housing is under vacuum.

Copeland subjects all scroll compressors to a high-voltage test after final assembly. Each motor phase winding is tested according to EN 60034-1 at a differential voltage of 1000 V plus twice the nominal voltage.

Since high-voltage tests lead to premature ageing of the winding insulation, further additional tests of that nature are not recommended. However, if it has to be done for any reason, it shall not be made with the compressor charged with refrigerant. Conduct the test with a lower voltage, as described above. Disconnect all electronic devices, eg, motor protection module, fan speed control, etc. prior to testing.

Special attention should be paid when performing a high-potential test and reading the Megohm resistance on R290 compressors, as such tests can induce an electrical arc and cause a fire hazard.

For the same reason, compressors removed from a system with R290 refrigerant will need to have the oil drained and a nitrogen purge introduced to flush any remaining refrigerant from the compressor prior to high-potential testing and Megohm resistance reading.

Start-up & operation

⚠️ WARNING Diesel effect! System explosion! The mixture of air and oil at high temperature can lead to an explosion. Avoid operating with air.

⚠️ WARNING Air/flammable refrigerant mixture! Creation of a flammable atmosphere! Make sure the atmosphere is non-flammable before starting the system. Ensure that the system contains only refrigerant.

IMPORTANT Oil dilution! Bearing malfunction! It is important to ensure that new compressors are not subjected to liquid abuse. It is mandatory to have a crankcase heater installed if the refrigerant charge exceeds a defined value – see Table 7. Turn the crankcase heater on 12 hours before starting the compressor.

Strength-pressure test

⚠️ WARNING High pressure! Personal injuries! Consider personal safety requirements and refer to test pressures prior to test.

CAUTION System contamination! Bearing malfunction! Use only dry nitrogen for pressure testing. DO NOT USE other industrial gases.

Compressor strength-pressure test

The compressor has been strength-pressure tested in the Copeland factory. Therefore, it is not necessary for the system manufacturer/installer to strength-pressure test the compressor again.

Scroll compressors are divided into two pressure zones. The compressor high-side and low-side maximum allowable pressures PS have to be respected at all times.

System strength-pressure test

A strength-pressure test of individual sections of the entire system is permitted. Once the compressor is isolated, the rest of the system can be tested with the required pressure values.

The strength-pressure test can also be conducted with the compressor connected, but in that case the two pressure zones of the scroll compressor need to be respected:

  • System high-pressure section:
    • Define the system high-side PS ≤ compressor high-side PS.
    • Isolate the high- and low-pressure sections of the system by closing valves, solenoid valves, expansion valves or by other means.
    • Use the internal check valve of the compressor on the discharge side or add an external check valve. To protect the compressor internal check valve, observe a maximum pressure delta of ≤ 40 bar between the high-pressure side and the low-pressure side.
    • Activate the check valve with a fast pressure increase. Once the check valve is activated, the pressure increase can be slowed down.
    • At this stage the system test pressure of 1.1 x system high-side PS can be applied for a short time.
    • During the system test, make sure the pressure inside the compressor does not exceed the maximum PS value, which corresponds to the compressor low-pressure PS.
  • System low-pressure section:
    • Define the system low-side PS ≤ compressor low-side PS.
    • The system test pressure of 1.1 x system low-side PS can be applied for a short time.

Compressor tightness test

⚠️ WARNING High pressure! Personal injuries! Consider personal safety requirements and refer to test pressures prior to test.

CAUTION System contamination! Bearing malfunction! Use only dry inert gases (for example nitrogen) for leak testing. DO NOT USE other industrial gases.

The compressor has been leak-pressure tested in the Copeland factory.

All compressors get a factory holding charge of dry air (about 1 to 2.5 bar, relative pressure). The presence of an intact holding charge serves as a proof of quality against penetrating moisture.

When removing plugs from the compressor, the plugs may pop out due to pressure and oil can spurt.

Any later modification to compressor connections can have an impact on the compressor tightness. Always leak-pressure test the compressor after opening or modifying the connections.

Never add refrigerant to the test gas (as leak indicator).

System evacuation

Before the installation is put into commission, it has to be evacuated with a vacuum pump. The vacuum pump and all tools have to be approved for A3 refrigerant/air mixture. The installation should be evacuated down to an absolute pressure of 2.7 mbar in accordance with EN 378-4. Proper evacuation reduces residual moisture to 50 ppm. During the initial procedure, suction and discharge shut-off valves on the compressor remain closed. The installation of adequately sized access valves at the furthest point from the compressor on the suction and liquid lines is advisable. The pressure must be measured using a vacuum pressure gauge on the access valves and not on the vacuum pump; this serves to avoid incorrect measurements resulting from the pressure gradient along the connecting lines to the pump.

Evacuating the system only on the suction side of a scroll compressor can occasionally result in a temporary no-start condition for the compressor. The reason for this is that the floating seal could axially seal with the scroll set, with the higher pressure on the floating seal. Consequently, until the pressures equalise, the floating seal and scroll set can be held tightly together.

The highest demands are placed on the leak-proof design of the installation and on the leak testing methods – please refer to EN 378.

When working on systems filled with refrigerant, it may be necessary to repeat the evacuation process several times. Refrigerant may have dissolved in the refrigerant oil and will only gradually condense out.

Preliminary checks – Pre-starting

⚡️ WARNING Air/R290 refrigerant mixture in a potentially flammable or explosive atmosphere! Fire and explosion hazard! Whenever starting up a system charged with R290 refrigerant, eg, after filling, repair, or maintenance, make sure not to start and operate accidentally in a flammable or explosive atmosphere.

Discuss details of the installation with the installer. If possible, obtain drawings, wiring diagrams, etc. It is ideal to use a check list but always check the following:

  • no explosive atmosphere or flammable gas in the ambient;
  • suitable ventilation according to room volume and refrigerant charge;
  • visual check of the electrics, wiring, fuses etc;
  • visual check of the plant for leaks, loose fittings such as TXV bulbs etc;
  • compressor oil level;
  • calibration of HP & LP switches and any pressure-actuated valves;
  • check setting and operation of all safety features and protection devices;
  • all valves in the correct running position;
  • pressure and compound gauges fitted;
  • correctly charged with refrigerant;
  • compressor electrical isolator location & position.

Charging procedure

⚡️ WARNING Air/R290 refrigerant mixture in a potentially flammable or explosive atmosphere! Fire and explosion hazard! Only use filling equipment designed and approved for use and operation with R290 refrigerant. Make sure all connections are tight to avoid leakage. Make sure to fill with pure R290 refrigerant.

CAUTION Low suction pressure operation! Compressor damage! Do not operate with a restricted suction. Do not operate with the low-pressure limiter bridged. Do not operate compressor at pressures that are not allowed by the operating envelope. Allowing the suction pressure to drop below the envelope limit for more than a few seconds may overheat scrolls and cause early drive bearing and moving parts damage.

Prior to charging or re-charging, the refrigerant system must be leak- and pressure-tested with appropriate purging gas.

Ensure that the system is grounded prior to charging with refrigerant.

The system shall be liquid-charged through the liquid-receiver shut-off valve or through a valve in the liquid line. The use of a filter-dryer in the charging line is highly recommended. Systems shall be liquid-charged on both the high and low sides simultaneously to ensure a positive refrigerant pressure is present in the compressor before it runs. The majority of the charge shall be placed in the high side of the system to prevent bearing washout during first-time start on the assembly line.

Extreme care shall be taken not to overfill the system with refrigerant.

NOTE: The system manufacturer/installer must respect the charge limitations according to valid standards, such as EN 378.

Run-in time

Scroll compressors exhibit a slight decrease in input power during the initial running period. Published performance ratings are based on calorimeter testing which is carried out after run-in. Therefore, users should be aware that before the performance specified by EN 12900 is achieved the compressor needs to be run in. Recommended run-in times for ZB*KCU compressors to attain the published performance are 16 hours at the standard conditions.

Initial start-up

CAUTION High discharge pressure operation! Compressor damage! Do not use compressor to test opening setpoint of high-pressure cut-out. Internal parts are susceptible to damage before they have had several hours of normal running in.

Liquid and high-pressure loads could be detrimental to new bearings. It is therefore important to ensure that new compressors are not subjected to liquid abuse and high-pressure run tests. It is not good practice to use the compressor to test the high-pressure switch function on the production line. The switch function can be tested with nitrogen prior to installation and the wiring can be checked by disconnecting the high-pressure switch during the run test.

Rotation direction

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single-phase compressors since they will always start and run in the proper direction. Three-phase compressors will rotate in either direction depending upon the phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, it is important to include notices and instructions in appropriate locations on the equipment to ensure proper rotation direction when the system is installed and operated.

Observing that suction pressure drops and discharge pressure rises when the compressor is energized allows verification of proper rotation direction. There is no negative impact on durability caused by operating three-phase Copeland scroll compressors in the reverse direction for a short period of time (under one hour) but oil may be lost. Oil loss can be prevented during reverse rotation if the tubing is routed at least 15 cm above the compressor. After several minutes of operation in reverse, the compressor protection system will trip due to high motor temperature. The operator will notice a lack of cooling. However, if allowed to repeatedly restart and run in reverse without correcting the situation, the compressor will be permanently damaged.

All three-phase scroll compressors are identically wired internally. Therefore, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the identified compressor terminals will ensure proper rotation direction.

Start-up and shut-off sound

During the very brief start-up, a clicking sound resulting from the initial contacting of the spirals is audible; this sound is normal. Due to the design of the Copeland scroll compressors, the internal compression components always start unloaded even if system pressures are not balanced. In addition, since internal compressor pressures are always balanced at start-up, low voltage starting characteristics are excellent for Copeland scroll compressors.

Scroll compressors incorporate a device that minimizes reverse rotation. The residual momentary reversal of the scrolls at shut-off will cause a clicking sound, but it is entirely normal too and it has no effect on compressor durability.

Deep vacuum operation

CAUTION Vacuum operation! Compressor damage! Copeland scroll compressors in refrigeration or air-conditioning applications should never be used to evacuate a system. Operating scroll compressors in deep vacuum could damage internal motor parts and lead to unacceptable high temperatures in the compressor housing.

For operation below atmospheric pressure with flammable refrigerants, see section 3.5 "System protection for operation below atmospheric pressure".

Pumpdown cycle

⚠️ WARNING Operation below atmospheric pressure! Fire hazard! During operation of A3-refrigerant systems below atmospheric pressure, a flammable mixture can form inside the system. Ensure system tightness to prevent any ingress of air.

CAUTION Vacuum operation! Compressor damage! Compressor operation outside the operating envelope is not allowed.

A pumpdown cycle to control refrigerant migration may have to be used for several reasons, for example when the compressor is located outdoors without any housing so that cold air blowing over the compressor makes the crankcase heater ineffective.

If a pumpdown cycle is used, a separate external check valve must be added. The scroll discharge check valve is designed to stop extended reverse rotation and prevent high-pressure gas from leaking rapidly into the low side after shut-off. The check valve might in some cases leak, causing the scroll compressor to recycle more frequently. Repeated short cycling of this nature can result in a low oil situation and consequent damage to the compressor. The hysteresis of the lowpressure control differential has to be reviewed since a relatively large volume of gas will re-expand from the high side of the compressor into the low side after shutdown.

For pressure control setting, never set the low-pressure limiter to shut off outside of the operating envelope. To prevent the compressor from running into problems during such faults as loss of charge or partial blockage, the low-pressure limiter shall not be set lower than the minimum suction pressure allowed by the operating envelope.

NOTE: Refer to section 3.5 "System protection for operation below atmospheric pressure" for further information.

Shell temperature

During normal operation, the discharge gas as well as the compressor top shell and discharge line can reach temperatures up to the maximum discharge gas temperature of 130/135 C – see section 3.7 "Discharge gas temperature protection".

In a failure mode, the discharge gas temperatures can get even higher. Ensure that wiring or other materials that could be damaged by these temperatures do not touch the shell.

Minimum run time

Copeland recommends a maximum of 10 starts per hour. There is no minimum off time because scroll compressors start unloaded, even if the system has unbalanced pressures. The most critical consideration is the minimum run time required to return oil to the compressor after start-up. To establish the minimum run time, a sample compressor equipped with an external oil sight glass is available from Copeland. The minimum on time becomes the time required for oil lost during compressor start-up to return to the compressor sump and to restore a minimal oil level that will ensure oil pick-up through the crankshaft. Cycling the compressor for a shorter period than this, for instance to maintain very tight temperature control, will result in progressive loss of oil and damage to the compressor.

Supply frequency and voltage

There is no general release of standard Copeland scroll compressors for use with variable speed AC drives. A number of considerations must be taken into account when applying scroll compressors with variable speed, including system design, inverter selection, and operating envelopes at various conditions. Only frequencies from 50 to 60 Hz are acceptable.

The third letter of the motor code indicates which frequency and voltage must be applied – see section 2.2 "Nomenclature".

For example, motor code TFDN:

  • T = Three-phase motor
  • F = Internal motor protection
  • D = Voltage and frequency range
  • N = Without UL approval
50 Hz60 HzCode
220-240 V / 1 ph-Z
220-240 V / 1 ph265 V / 1 phJ
380-420 V / 3 ph-M
380-420 V / 3 ph460 V / 3 phD

Oil level

There is no oil sight glass on ZB*KCU compressors to ensure maximum hermeticity.

Some systems may contain higher than normal refrigerant charges. Systems with large coils, low ambient condenser flooding, or systems with multiple heat exchangers are some of the configurations that may require additional lubricant.

BOM version 424 contains a stub tube connection 7/8" (22.2 mm) for paralleling on the compressor housing at oil level height.

If an oil regulator is used the oil level should be set within the top half of the oil regulator sight glass.

During the system development phase, adequate oil return from the system to the compressor should be evaluated and qualified. For this purpose, a sample compressor for lab testing, equipped with an external oil sight tube, is available from Copeland. The sample compressors can be used for oil return check in single or tandem applications. Oil return check test recommendations for paralleling are available on request. See also section 3.16 "Compressor oil return, oil balancing, refrigerant floodback and oil dilution tests".

Diagram Description (Figure 19: Sample compressor with external oil sight tube): A photograph of a Copeland compressor equipped with an external oil sight tube for testing oil return.

Maintenance & repair

⚠️ WARNING Conductor cables! Electrical shock hazard! Follow the lockout/tag out procedure and the national regulations before carrying out any maintenance or service work on the system. Use compressor with grounded system only. Screwed electrical connections must be used in all applications. Refer to original equipment wiring diagrams. Electrical connections must be made by qualified electrical personnel.

⚡️ WARNING Ignition source in a potentially flammable or explosive atmosphere! Fire and explosion hazard! When opening the system, the atmosphere could be explosive. All the electrical components that are a source of ignition must always be switched off during service and maintenance. Ensure that the surface temperatures of the components never exceed the limits set by the applicable safety standard, eg, EN 378-2.

Air/flammable refrigerant mixture! Fire and explosion hazard! Remove all the refrigerant before opening the system. Make sure to remove refrigerant completely from all components such as heat exchangers, refrigerant accumulators, etc. Flush the system and the components with inert gas before undertaking any work and before brazing.

⚡️ WARNING Open flame in a potentially flammable or explosive atmosphere! Fire and explosion hazard! The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of a potentially toxic or flammable atmosphere. Ensure that the leak detection equipment is suitable for all applicable refrigerants. Personnel performing work on a refrigeration system that involves exposing the pipework shall avoid using any ignition source in a way that could lead to a fire or explosion hazard. All sources of ignition shall be kept sufficiently far from the site of installation, repair, removal or disposal during the entire time when refrigerant could be released into the surrounding space. Open flames and smoking are strictly forbidden at all times.

During service make sure that:

  • the area is well ventilated;
  • the materials and equipment used are suitable for use under flammable conditions;
  • only non-sparking tools are used;
  • antistatic gloves and clothes are used;
  • build-up of electrostatic charges is avoided;
  • no unshielded or naked flame is used;

If parts of the refrigeration system are charged with flammable refrigerant, make sure that all the valves are tightly closed and that the open pipes after the valves are free of refrigerant and oil.

A risk analysis to evaluate all possible risks shall be carried out by the service technician before any repair work.

Qualification of workers

Personnel working on the maintenance, repair and decommissioning of the system shall be adequately trained. Any work procedure affecting safety shall only be executed by qualified and trained personnel in compliance with national or other equivalent certification systems.

Examples of such work procedures are breaking into the refrigerating circuit, opening sealed components, opening ventilated enclosures, etc...

Preparation and work procedure

A work procedure shall be provided in the preparation stage. All personnel working at the site, whether maintenance or other, shall be instructed on the nature of the work being carried out.

If any work is to be conducted on the refrigeration systems or any associated parts, appropriate fire extinguishing equipment shall be provided. Dry powder or CO2 fire extinguishers are considered appropriate. Verify that appropriate fire extinguishing equipment is available near the work area.

Prior to starting to work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized.

Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapour being present while the work is being performed.

Avoid working on systems filled with flammable refrigerant in a confined space.

Disassembling system components

The recommendations below shall be observed when disassembling system components:

  1. Recover refrigerant and evacuate system using an A3-dedicated recovery unit and vacuum pump. All the refrigerant shall be recovered to avoid significant release. Ensure that the outlet of the vacuum pump is not close to any potential ignition source and that ventilation is available.
  2. Flush system with inert gas (dry nitrogen). Compressed air or oxygen shall not be used for purging refrigerant systems.
  3. For A3-refrigerant systems, the procedure of evacuation and flushing with oxygen-free nitrogen may need to be repeated until no refrigerant is present in the system. When the final nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
  4. Disassemble components with a cutting tool.
  5. Drain, recover and dispose of compressor oil as appropriate.

Diagram Description (Figure 20: Tube connecting areas): A diagram showing areas 1, 2, and 3 on compressor tube connections, relevant for disconnection and reconnection.

To disconnect:
  • Using a pipe cutting tool, cut off the suction and discharge lines in such a manner that the new compressor can easily be re-connected into the system.
  • Heat joint areas 2 and 3 slowly and uniformly until the braze material softens and the tube end can be pulled out from the fitting.
To reconnect:
  • Recommended brazing material: Silfos with minimum 5 % silver or silver braze used on other compressors.
  • Due to the different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used.

NOTE: Since the discharge stub contains a check valve, care must be taken not to overheat it to prevent brazing material from flowing into it.

Exchanging the refrigerant

⚡️ WARNING Air/R290 mixture in a potentially flammable or explosive atmosphere! Fire and explosion hazard! Avoid air/R290 mixture in the refrigeration system in any case. Make sure that the system is filled with pure R290 refrigerant. In the event that the refrigerant needs replacing, the charge should be recovered using A3-qualified refrigerant recovery unit and recycling bottles.

CAUTION Low suction pressure operation! Compressor damage! Do not operate compressor with a restricted suction or with the low-pressure limiter bridged. Do not operate at pressures that are not allowed by the operating envelope. Allowing the suction pressure to drop below the envelope limit for more than a few seconds may overheat scrolls and cause early drive bearing and moving parts damage.

For qualified refrigerant and oil, see section 2.4.1.

Replacing a compressor

CAUTION Inadequate lubrication! Bearing destruction! For systems with a refrigerant accumulator, exchange the accumulator after replacing a compressor with a burned-out motor. The accumulator oil return orifice or screen may be plugged with debris or may become plugged. This will result in starvation of oil to the new compressor and a second failure. Remove refrigerant and oil completely from the replaced compressor.

Compressor replacement

When replacing an A3-refrigerant compressor, the oil must be drained out of the compressor and the compressor should be flushed with dry nitrogen. DO NOT close the stubs with plugs.

In case of motor burnout, most of the contaminated oil will be removed with the compressor. The rest of the oil is cleaned through the use of suction and liquid line filter-dryers. A 100 % activated alumina filter-dryer is recommended for the suction line. It must be removed after 72 hours.

It is highly recommended that the suction accumulator be replaced if the system contains one. This is because the accumulator oil return orifice or screen may be plugged with debris or may become plugged shortly after a compressor failure. This will result in starvation of oil to the replacement compressor and a second failure.

When a single compressor or tandem is exchanged in the field, it is possible that a large portion of the oil remains in the system. While this may not affect the reliability of the replacement compressor, the extra oil will add to rotor drag and increase power usage.

Start-up of a new or replacement compressor

Rapid charging only on the suction side of a scroll-equipped system can occasionally result in a temporary no-start condition for the compressor. The reason for this is that, if the flanks of the scrolls happen to be in a sealed position, rapid pressurisation of the low side without opposing high-side pressure can cause the scrolls to seal axially. As a result, until the pressures eventually equalise, the scrolls can be held tightly together preventing rotation. The best way to avoid this situation is to charge on both the high and low sides simultaneously at a rate which does not result in axial loading of the scrolls.

A minimum suction pressure specified in the published operating envelope must be maintained during charging. Allowing the suction pressure to drop below that value may overheat the scrolls and cause early drive bearing and moving parts damage.

Never install a system in the field and leave it unattended when it has no charge, a holding charge, or with the service valves closed without securely electrically locking out the system. This will prevent unauthorised personnel from accidentally operating the system and potentially ruining the compressor by operating with no refrigerant. Do not start the compressor while the system is in a deep vacuum. Internal arcing may occur when a scroll compressor is started in a vacuum causing burnout of the internal lead connections.

Compressor return procedure

For A3-refrigerant systems, if a compressor has to be returned to the manufacturer for analysis, both the refrigerant and the oil must be thoroughly removed before shipment. All compressor connections must remain open and warning stickers for flammable refrigerant must be placed on the shipping box.

The recommendations and procedure below shall be followed:

  • During the entire working procedure continuously check if the ambient atmosphere is flammable. If a flammable atmosphere is detected, immediately cut off the power supply and ventilate the working space.
  • Resume working after the atmosphere is no longer dangerous.

Recover the refrigerant from the system using a suitable recovery unit. During this action, the compressor crankcase heater could be energized – immediately de-energize in case a flammable or explosive atmosphere is detected.

  • Recover to 2,7 mbar absolute pressure or lower. For best results and to recover also the refrigerant solved in the oil, run the recovery unit two or three times as necessary.
  • Flush the whole system with oxygen-free dry nitrogen.
  • Open the system with a cutting tool and flush the entire system with dry nitrogen again.
  • Disassemble the compressor with a cutting tool. Drain and recover compressor oil properly. Flush the compressor with dry nitrogen for a few minutes.
  • The compressor should be returned free of oil and with connections open – do not close connections with plugs.
  • Collect and secure the oil properly. Provide information about the quantity of oil drained from the compressor and its colour. Ideally, send a good picture.
  • Dispose of the oil according to local rules and regulations.
  • Use a proper cardboard box package when preparing the compressor for shipment. Place warning icons on each side and on the top of the box. Mention the following message on the box: "Warning! Flammable A3 refrigerant compressor for analysis".
  • The compressor must be kept in the upright position – mark the box accordingly.
  • If more than one compressor have to be returned, each compressor must be packed individually.

NOTE: Check with the transport company that all the requirements applying to such shipments are complied with.

Lubrication and oil removal

⚡️ WARNING Air/R290 flammable refrigerant mixture in a flammable or explosive atmosphere! Fire and explosion hazard! Use suitable recovery unit and recycling bottles also for oil disposal as R290 refrigerant may still be dissolved in the oil.

CAUTION Chemical reaction! Compressor destruction! Do not mix up ester oils with mineral oil and/or alkyl benzene.

The compressor is supplied with an initial oil charge. The standard oil for use with ZB*KCU compressors and R290 refrigerant is a polyolester (POE) lubricant Hatcol 4467. See nameplate for original oil charge shown in litres. A field recharge is from 0.05 to 0.1 litre less.

One disadvantage of POE is that it is far more hygroscopic than mineral oil – see Figure 21. Only brief exposure to ambient air is needed for POE to absorb sufficient moisture to make it unacceptable for use in a refrigeration system. Since POE holds moisture more readily than mineral oil it is more difficult to remove it through the use of vacuum.

Diagram Description (Figure 21: Absorption of moisture in ester oil): A graph comparing the absorption of moisture in ester oil (POE) versus mineral oil in ppm by weight at 25°C and 50% relative humidity over time (h= hours).

The oil contained in Copeland compressors has a low moisture content, which however may rise during the system assembling process. Therefore, it is recommended to install a properly sized filter-dryer in all POE systems to maintain the moisture level in the oil to less than 50 ppm. If POE oil is charged into a system, it is recommended that its moisture content be no higher than 50 ppm.

If the moisture content of the oil in a system reaches unacceptably high levels, corrosion and copper plating may occur. The system should be evacuated down to 2.7 mbar in accordance with EN 378–4. If there is uncertainty as to the moisture content in the system, an oil sample should be taken and tested. Sight glass/moisture indicators currently available can be used with R290 refrigerant and lubricant. However, they will only show the moisture content of the refrigerant. The actual moisture level in the oil is likely to be higher than indicated by the sight glass. This is due to the high hygroscopicity of POE oil. To determine the actual moisture content of the lubricant, samples have to be taken from the system and analysed.

Oil additives

Although Copeland cannot comment on any specific product, from our own testing and past experience, we do not recommend the use of any additives to reduce compressor bearing losses or for any other purpose. Furthermore, the long-term chemical stability of any additive in the presence of refrigerant, low and high temperatures, and materials commonly found in refrigeration systems is complex and difficult to evaluate without rigorously controlled chemical laboratory testing. The use of additives without adequate testing may result in malfunction or premature failure of components in the system and, in specific cases, in voiding the warranty on the component.

Troubleshooting

⚠️ WARNING Electrical cables! Electrical shock hazard! Before attempting any electrical troubleshooting, make sure all grounds are connected and secure and there is ground continuity throughout the compressor system. Also ensure the compressor system is correctly grounded to the power supply. If you are not a qualified service person familiar with electrical troubleshooting techniques, DO NOT PROCEED until a qualified service person is available.

Most in-warranty electrical failures are a result of mechanical problems (particles in the oil, liquid refrigerant in the oil, etc.) and most mechanical problems are a result of system problems. Unless the reason for the failure is found, replacing the compressor will probably lead to another compressor failure.

If the compressor fails to start and run properly, it is important that the compressor be tested to determine its condition. It is possible that electrical components may be defective, the protector may be open, or a safety device may have tripped. Here is a list of the most common compressor problems encountered in the field.

ConditionCauseCorrective action
The scroll compressor does not run, instead a buzz sound can be heardWired incorrectlyCheck the power supply on the compressor terminals if there is voltage measured. Trace the wiring diagram to see where the circuit is interrupted.
Low supply voltageIf the voltage falls below 90 % of the nameplate voltage, the motor may develop insufficient torque. Make sure the compressor is supplied with rated nominal voltage.
Shorted or grounded motor windingsCheck the motor for ground by means of a continuity check between the terminals. If grounded replace compressor.
Internal compressor mechanical damage
  • Refrigerant migration: When the compressor is switched off for a long period refrigerant can condense in the crankcase. If the compressor body is colder than the evaporator, refrigerant will move from the evaporator to the compressor crankcase. Refrigerant migration normally occurs when the compressor is installed in a cold area. A crankcase heater and/or a pumpdown cycle provide good protection against refrigerant migration.
  • Acid formation: Acid forms in the presence of moisture, oxygen, metal, salts, metal oxides and/or high discharge temperatures. The chemical reactions are accelerated at higher temperatures. Oil and acid react with each other. Acid formation leads to damage of the moving parts and in extreme cases to motor burnout. Several different test methods can be used to test for acid formation. If acid is present a complete oil change (including the oil in the oil separator) will help. A suction filter which removes acid should also be fitted. Check filter-dryer condition.
The scroll compressor does not run, no buzz sound can be heardCompressor motor protector openCheck if there is continuity on the compressor external protector. If the compressor is warm, it may require considerable time to cool down.
Defective system control componentsCheck if the pressure control or thermostat works properly or if the controls are open.
Power circuit openCheck the fuse for a tripped circuit breaker or for an open disconnected switch.
Burned motor windingIf motor burned is due to undersized contactors, this is observed when the contacts welded together. Complete motor burnout on all three phases despite the presence of a functioning protection system can be the result. For sizing information please consult the contactor data sheet. If the application of the compressor is changed the contactor sizing should be rechecked. Check for unbalanced voltage.
The scroll compressor trips on motor protectionHigh discharge pressure / suction pressure
  • For high discharge pressure:
    • Check for system leaks. With system leaks at the lowpressure side, air as non-condensable gas could enter the system and create high pressure.
    • Check the system design. Make sure the discharge line is correctly sized: undersized discharge line can increase discharge pressure. This is also true for an undersized condenser. Correct the component selection as needed.
    • Check the fan motor, make sure it is running properly in the right direction. Check the condenser: if dirt has been accumulated it will clog the airflow; clean as necessary. High discharge pressure is also caused by an overcharged system and high ambient temperature surrounding the condenser.
  • For high suction pressure, check the "evaporator superheat" first to diagnose the problem:
    • High superheat at the evaporator outlet: this is likely in case of excessive pressure-drop in the liquid line or too much vertical lift on the pipe work.
    • Low superheat at the evaporator outlet is usually the consequence of oversized selection of the expansion valve or incorrect bulb sensor mounting. The valve may freeze up in the open position due to accumulation of debris in the system. For a system with very short refrigeration lines an accumulator is recommended.
Compressor operating outside the design limitsCheck the compressor suction and discharge pressures while it is running. Make sure they are within the operating envelope limits.
Defective motor protectorIf all operating conditions are normal, the voltage supply at the compressor terminals is balanced and within limits, the compressor crankcase temperature is within normal limits, and the amperage drawn is within the specified range, the motor protector may be defective.
Excessive discharge temperatureToo high compressor superheatMake sure the compressor operates within the acceptable superheat range published by Copeland.
The scroll compressor runs continuouslyExcessive cooling / heating load or inadequate insulationCheck the load design; make sure that proper insulation is applied. Correct as necessary.
Control circuit inoperativeCheck the thermostat, measure the temperature of the room and compare with the thermostat; replace or re-calibrate the thermostat. Check the LP control switch and replace it if it is found defective.
Oil trap due to incorrect piping layout / sizingCheck the piping layout design. Installations of pipe being routed over or around obstacles can inadvertently create unwanted traps for the oil return. As much as possible the refrigerant line should travel a direct and straight course between the evaporator and compressor. It should also be remembered that the entire system will be coated in oil to some extent. Oil viscosity changes with temperature. More oil stays in the system than was originally expected. Make sure the line is correctly sized.
Compressor lubrication problemOil pump out due to high cycling rateA high cycling rate will pump oil into the system and lead to lubrication failure. Oil leaves the compressor at start-up and the short running time is insufficient to return the oil to the compressor via the suction side. Try to limit the number of cycles to maximum 10 per hour.
Low gas velocitySystem gas velocity changes depending on temperature and load (capacity control). In low load conditions gas velocity may not be high enough to return oil to the compressor. Fit a fan cycling control system.
Low discharge pressureLow ambient temperature
Low suction pressureRefrigerant underchargeCheck the system for leaks. Observe sight glass for bubbles if fitted. Add refrigerant until the sight glass is clear. If no sight glass is fitted, check the evaporator superheat and fill in with refrigerant.
System design load too smallIf the compressor is running in a tandem or in parallel, modulate the running process.
Inadequate refrigerant going to the evaporatorLower normal discharge pressure values can lead to insufficient refrigerant flow to the system. This can also be verified by checking the evaporator outlet superheat, if it is found unusually high. Check the selection of the expansion valve (likely undersized).
Noise during shut-offAnti-reverse deviceThis does not have any effect on the durability of the compressor, no action is necessary.

Dismantling & disposal

Removing oil and refrigerant:

  • Do not disperse in the environment.
  • Use the correct equipment and method of removal.
  • Dispose of oil and refrigerant in compliance with national legislation and regulations.

Dispose of compressor in compliance with national legislation and regulations.

References

Application Guidelines and Technical Information:

Please visit www.copeland.com/en-gb for free download of Application Guidelines and Technical Information.

Performance and technical data:

The latest version of Copeland Select software with performance data and technical data is available from the webpage www.copeland.com/en-gb/tools-resources/copeland-select-software.

Spare parts and accessories:

An online version of the Copeland spare parts & accessories catalogue is available from the webpage www.copeland.com/en-gb/tools-resources.

Appendix 1: Tightening torques

ConnectionTorque (Nm)
Mounting bolts 5/16", M927 max
Mounting bolts M8 (grommet for single operation)13 1
Mounting bolts M8 (hard mounting parts for parallel operation)27 1
Crankcase heater2 - 3
Terminal block screw2.8
Ground screw2.3
IP65 box ground screw (Peko bolt)4 - 4.4
IP65 ground screw cover / T-box1.8 - 2
IP65 cable gland M259.8 - 10
IP65 T-box cover screws1.8 - 2

DISCLAIMER

  1. The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability.
  2. Copeland Europe GmbH and/or its affiliates (collectively "Copeland"), as applicable, reserve the right to modify the design or specifications of such products at any time without notice.
  3. Copeland does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Copeland product remains solely with the purchaser or end user.
  4. Copeland does not assume responsibility for possible typographic errors contained in this publication.

PDF preview unavailable. Download the PDF instead.

AGL Ref ST ZBKCU EN Rev02 FULL Adobe Acrobat Pro (64-bit) 23.1.20174 Adobe Acrobat Pro (64-bit) 23.1.20174

Related Documents

Preview Copeland™ Scroll Compressors for R290 Applications: ZB12KCU to ZB49KCU Application Guidelines
Comprehensive application guidelines for Emerson's Copeland™ Scroll Compressors (ZB12KCU to ZB49KCU) designed for R290 refrigerant applications. Covers installation, operation, safety, and maintenance.
Preview Copeland™ Scroll Compressors for R290 Applications: Application Guidelines
Comprehensive application guidelines for Copeland™ Scroll Compressors (ZH04KCU to ZH16KCU) designed for R290 refrigerant systems. Covers safety, installation, operation, and maintenance for HVACR professionals.
Preview Copeland Scroll Compressors ZR24KRE-ZR190KRE Application Guidelines
Emerson's Copeland Scroll™ compressors (ZR24KRE to ZR190KRE) application guidelines detail installation, operation, safety, and troubleshooting for comfort, precision, and process cooling. Essential for system designers and technicians.
Preview Copeland Scroll Compressors for R290 Applications: Application Guidelines
Comprehensive application guidelines for Copeland Scroll Compressors (ZH04KCU to ZH16KCU) designed for R290 refrigerant systems. Covers installation, safety, operation, maintenance, and troubleshooting.
Preview Copeland™ Scroll Digital Compressors for Refrigeration Applications: Application Guidelines
This document provides comprehensive application guidelines for Copeland™ Scroll Digital Compressors (YBD17K1E to YBD36K1E) used in refrigeration applications. It covers product description, installation, electrical connection, start-up and operation, maintenance, repair, and safety instructions, including specific considerations for A2L refrigerants.
Preview Copeland Scroll Compressor Model Designation Guide
A technical guide to understanding and deciphering Copeland scroll compressor model numbers, covering motor types, capacity, voltage, and application ranges.
Preview Copeland™ Compressors with CoreSense™ Technology
Explore Copeland™ compressors featuring CoreSense™ technology for enhanced protection, diagnostics, and efficiency in air conditioning and refrigeration applications. Learn about CoreSense Diagnostics, Protection, and PerformanceAlert for various compressor types.
Preview Copeland Scroll Compressor Field Guide
A comprehensive reference guide for Emerson's Copeland Scroll compressors, detailing mobile app features, refrigerants, oils, product families, nomenclature, and manufacturing information for HVACR professionals.