QG0073 ASW015-030K-TH EN 540-300767-00 V01 1224
1 General Information
This quick installation guide should be read together with the user manual. In case of doubt and uncertainties, the content in the user manual takes precedence over the content in this guide.
The contents of this guide may be updated or revised due to on-going product development and continuous improvement. The information in this guide is subject to change without notice. The latest version of this document and the user manual for installation, commissioning, configuration and decommissioning are to be found in PDF format at www.solplanet.net.

2 Safety

2.1 Intended use
The product is a transformerless hybrid inverter with four MPP trackers and one or two battery inputs that feeds the direct current of the PV array into the connected battery or converts it to grid-compliant three-phase current and then feeds it into onsite loads and the utility grid.

The product has a backup function that can continue to supply selected circuits with power from the battery or PV array in the event of a grid fault.

The product is intended for indoor and outdoor applications.

The product must only be connected with PV modules of protection class II (in accordance with IEC 61730, application class A).

The product is not equipped with an integrated transformer and therefore has no galvanic isolation. The product must not be operated with PV modules which require functional grounding of either the positive or negative PV conductors. This can cause the product to be irreparably damaged. The product may be operated with PV modules with frames that require protective earthing.

All components must remain within their permitted operating ranges and their installation requirements at all times.

Use the product only in accordance with the information provided in this guide, the user manual and with the locally applicable standards and directives. Any other application may cause personal injury or damage to property.

ASW015-030K-TH_EN_V01

1

The product must only be operated in connection with an intrinsically safe lithium-ion battery approved by Solplanet. The entire battery voltage range must be completely within the permissible input voltage range of the product. The latest version of the Solplanet battery compatibility list can be found in PDF format at www.solplanet.net.
The product must only be used in countries for which it is approved by Solplanet and the grid operator.
The type label must be permanently attached to the product and must be in a legible condition.
This document does not replace any regional, state, provincial, federal or national laws, regulations or standards that apply to the installation, electrical safety and use of the product.
2.2 Important safety instructions
The product has been designed and tested strictly according to the international safety requirements. As with all electrical or electronical devices, there are residual risks despite careful construction. To prevent personal injury and property damage and to ensure long-term operation of the product, read this section carefully and observe all safety information at all times.
DANGER
Danger to life due to high voltages of the PV array or the battery
The DC cables connected to the battery, or the PV array may be live. Touching the DC conductors or associated live components can cause lethal electric shocks. Disconnecting the DC connectors from the product under load, an electric arc may expose the user to electric shock and burns. · Do not touch non-insulated cable ends. · Do not touch the DC conductors without isolating all sources of energy. · Do not touch any live components of the product. · Do not open the product. · Observe all safety information of the battery manufacturer. · All work on the product must only be carried out by qualified personnel who
have read and fully understood all safety information contained in this document and the user manual.

2

ASW015-030K-TH_EN_V01

· Disconnect the product from all voltage and energy sources and ensure it cannot be reconnected before working on the product.
· Wear suitable personal protective equipment for all work on the product.
DANGER
Danger to life due to electric shock when touching live components in backup mode
Regardless of the AC breaker and the PV switch of the inverter being switched off or disconnected, the parts of the system may still be live when the battery is providing power during backup mode. · Do not open the product. · Disconnect the product from all voltage and energy sources and ensure it
can not be reconnected before working on the product.
DANGER
Danger to life due to fire or explosion when batteries are fully discharged
A fire may occur due to incorrect charging of fully discharged batteries. This can result in death or serious injury. · Ensure the battery is not fully discharged before commissioning the system. · Contact the battery manufacturer before proceeding if the battery is fully
discharged.

DANGER
Danger to life due to burns caused by electric arcs through short-circuit currents
Short-circuit currents in the battery can cause heat accumulation and electric arcs if the battery is short circuited or wrongly installed. Heat accumulation and electric arcs may result in lethal injuries due to burns.
· Disconnect the battery from all voltages sources prior to performing any work on the battery.
· Only use properly insulated tools to prevent accidental electric shock or short circuits during installation.
· Observe all safety information of the battery manufacturer.

ASW015-030K-TH_EN_V01

3

DANGER
Danger to life due to electric shock when touching live system components in case of a ground fault
If a ground fault occurs, parts of the system may still be live. Touching live parts and cables may result in death or lethal injuries due to electric shock. · Disconnect the product from voltage and energy sources and ensure it
cannot be reconnected before working on the device. · Handle PV module cables only by its insulation. · Do not touch any parts of the substructure or frame of the PV array. · Do not connect PV strings with ground faults to the product.
WARNING
Danger to life due to risk of fatal electric shock from measuring device damage caused by overvoltage
Overvoltage can damage a measuring device and result in voltage being present in the enclosure of the measuring device. Touching the live enclosure of the measuring device results in death or lethal injuries due to electric shock. · Only use measuring devices with a measurement span equal to or higher
than the voltage rating of the product.

CAUTION
Risk of burns due to high temperature.
Some parts of the enclosure can become hot during operation. · During operation, do not touch any parts other than the enclosure lid of the
product.

CAUTION

Risk of injury due to weight of product.
Injuries may result if the product is incorrectly handled or dropped while being transported or mounted.
· Transport and lift the product carefully. Take the weight of the product into account.
· Wear suitable personal protective equipment for all work on the product.

4

ASW015-030K-TH_EN_V01

2.3 Symbols on the label
Beware of a danger zone This symbol indicates that the product must be additionally grounded if additional grounding or equipotential bonding is required at the installation site.
Beware of high voltage and operating current The inverter operates at high voltage and current. Work on the inverter must only be carried out by skilled and authorized electricians.
Beware of hot surfaces The inverter can become hot during operation. Avoid contact during operation.
WEEE designation Do not dispose of the product together with the household waste but in accordance with the disposal regulations for electronic waste applicable in the country of installation.
CE marking The product complies with the requirements of the applicable EU directives.
Certification mark The product has been tested by TÜV and received the quality certification mark.
RCM (Regulatory Compliance Mark) The product complies with the requirements of the applicable Australian standards.
Capacitor discharge Danger to life due to high voltages in the inverter. Do not touch live parts for 5 minutes after disconnection from the power sources.
Observe the documentation Observe all documentation supplied with the product.

ASW015-030K-TH_EN_V01

5

3 System Wiring Diagram

6

ASW015-030K-TH_EN_V01

ASW015-030K-TH_EN_V01

7

The wiring of a basic application as an example for grid connected systems without special requirements is shown below:
The wiring of smart meter:
The wiring of CT(Optional):

8

ASW015-030K-TH_EN_V01

Breaker No. ASW015K-TH ASW020K-TH

1

63 A/1000 V DC Breaker

2

/

/

ASW025K-TH ASW29.9K-TH ASW030K-TH 63 A/1000 V DC Breaker

3

4

63 A/400 V 80 A/400 V AC AC Breaker Breaker

5

100 A/400 V AC Breaker

6

Dependent on the normal loads which should be checked by an installer

4 EU Declaration of Conformity
Within the scope of the EU directives · Radio Equipment Directive 2014/53/EU
(L 153/62-106. May 22. 2014) (RED) · Restriction of the use of certain hazardous substances 2011/65/EU
(L 174/88, June 8, 2011) and 2015/863/EU (L 137/10, March 31,2015) (RoHS)

AISWEI Technology Co., Ltd. confirms herewith that the products described in this document are in compliance with the fundamental requirements and other relevant provisions of the above mentioned directives. The entire EU Declaration of Conformity can be found at www.solplanet.net.

ASW015-030K-TH_EN_V01

9

5 Overview

ASW015-020K-TH (left)
Object
A B1/2 C1/2
D E F
G
H I

ASW025-030K-TH (right)
Description
DC-Switch Battery Connector Ports
PV Input Ai-Dongle Port Ventilation valve port Communication Ports Diesel Generator Connector Port (Reserved) EPS Load Connector Port AC Connector Port Additional Grounding Screw

10

ASW015-030K-TH_EN_V01

6 Scope of Delivery

B

C

D

E

A

F

G

H

I

A

J

K

L

Object A B C D
E

Description Inverter
Mounting Bracket Mounting Bracket Template
AC Connector Diesel Generator Connector
(Reserved) EPS Load Connector

F

DC Connector(pair, positive & negative)

G

Battery Connector(pair, positive & negative)

H

Ai-Dongle

I

External CT

J

Smart MeterCTs included

K

Fastener Package

L

Communication Terminal

Package

M

Document package

ASW015-030K-TH_EN_V01

Quantity 1 1 1 1
1
ASW015-020K-TH ASW025-030K-TH ASW015-020K-TH ASW025-030K-TH
1 3(optional)
1 1
1
1

M
4 8 1 2
11

7 Solplanet App
7.1 Brief introduction
The Solplanet App is an Android and iOS App which is used to set up and commission the inverter and connect it to the Solplanet cloud.
7.2 Download and install
Scan the following QR code which directs to the Google Playstore or Apple App Store, download and install the Solplanet App according to the prompt information.

12

ASW015-030K-TH_EN_V01

8 Mounting Environment

ASW015-030K-TH_EN_V01

13

9 Dimensions

Unit:mm

10 Mounting













14

ASW015-030K-TH_EN_V01

11 Secondary Protective Grounding











12 AC Connection











ASW015-030K-TH_EN_V01

15







16

ASW015-030K-TH_EN_V01

13 EPS Load / Diesel Generator Connection





 



ASW015-030K-TH_EN_V01

17









· The connector has to be tightened and sealed properly regardless if there is no load or diesel generator connected.

18

ASW015-030K-TH_EN_V01

14 PV Connection











15 Battery Connection











ASW015-030K-TH_EN_V01

19





16 Communication Setup
16.1 Communication interfaces

Object Description Terminal 1

PIN definition

2

3

4

5

6

7

8

/

Parallel
(Reserved)

RS485A RS485B

RS485A RS485B

CANBH CANBL

COM1/2

X

X

_PARA _PARA

_SYNC _SYNC

_PARA _PARA



Third_RS485 COM3 RS485A RS485B GND

X

X

X

X

X



SOUTH_485

COM4

RS485A RS485B GND

X

(Reserved)

/

Ethernet

COM5/6

TX+

TX-

RX+

X

X

X

X

X

RX-

X

X GND



BMS1

COM7

X

GND

X

CANH

CANL

X

X

X



BMS2

COM8

X

GND

X

CANH

CANL

X

X

X

20

ASW015-030K-TH_EN_V01

Object
A/E
B C D F G/K H/I J L


Description
DRM0/DI*4
North_485
(Reserved)
CT
(Optional)
ON/OFF Meter
NS-protection
External output_12V AI-HUB_DI
(Reserved)
DO2/DO1
(Reserved)

Terminal
6pin 4pin 6pin 2pin 4pin 2pin 2pin

1

2

DRMS Device

Com LOAD/0 or GND

REF GEN/0

\

GND

Current Transformer L1

Black

Red

GND

DI

\

GND

NS-protection (network and system
protection) Device

Negative Positive

GND

Selv_12V

PIN definition

3

4

5

6

Ripple Control Receiver Device

DI_1

DI_2

DI_3

DI_4

RS485B RS485A

Current Transformer L2

Black

Red

\

RS485B RS485A

\

Current Transformer L3

Black

Red

\

\

\

\

\

\

2pin

GND

DI

\

\

Multifunctional Relay

4pin

DO2

DO1

\

A

B

A

B



ASW015-030K-TH_EN_V01

21











22

ASW015-030K-TH_EN_V01

16.1.1


Ripple control connection









16.1.2


NS protection connection

ASW015-030K-TH_EN_V01

23









· Indicative only, please refer to the NS protection device user manual for correct wiring.

16.1.3


Smart meter connection

24

ASW015-030K-TH_EN_V01







 

ASW015-030K-TH_EN_V01

25

16.1.4


BMS Connection



16.1.5


Current Transformer connection (optional)

26

ASW015-030K-TH_EN_V01









ASW015-030K-TH_EN_V01

27

16.2 Ai-Dongle connection

















28

ASW015-030K-TH_EN_V01

17 Contact
Please contact our Service Department if you have any technical questions about our products. · The following information is needed to provide necessary assistance: · Inverter model · Inverter serial number · Photovoltaic module model · Photovoltaic modules quantity and string arrangement connected to each