User Guide for Elimko models including: E-48P Series, E-48P Series Universal Advanced Digital Controllers, Universal Advanced Digital Controllers, Advanced Digital Controllers, Digital Controllers, Controllers

İsimsiz-1

Murat ARAS

E48P Quick Start Guide

16 nov 2023 — 0. 1. * Only one of the analog output and RS-485 options can be coded. For example, only one of the options (X) and (Y) can be coded as 1.


File Info : application/pdf, 2 Pages, 1.54MB

PDF preview unavailable. Download the PDF instead.

E48P Quick Start Guide
KY-48P-1123-1

4. WARNINGS

Thermocouple / miliVolt 0-20 mA / 4-20 mA
Resistance Thermometer 2-Wire Transmitter Volt

200.0
200.0 R1
R2

E l i m k o

SET 48P

E-48P Series Universal Advanced Digital Controllers Quick Start Guide
Manufacturer / Technical Support Elimko Elektronik malat ve Kontrol Ltd. ti. 8. Cadde 21. Sokak No:16 Emek 06510 Ankara / TÜRKYE Telefon: + 90 312 212 64 50 Faks: + 90 312 212 41 43 www.elimko.com.tr · e-mail:elimko@elimko.com.tr

1. DESCRIPTION
E-48P Series universal process controllers are industrial devices at 48x48 mm IEC/TR 60668 dimensions designed using new generation microcontrollers with on/off, PID and other control forms, where inputs and outputs can be easily programmed by the user.
In E-48P Series controllers, the set value and measured value can be displayed from -1999 to 9999 on two 4-digit displays; general purpose inputs (T/C, R/T, mV, mA) can be programmed.

2. DIMENSIONS and PANEL CUT-OUT

44 mm 44 mm

48 mm
200.0
200.0 R1
R2

E l i m k o

SET 48P

48 mm

Elimko
Kontrol Edilmitir
2

TP

: E48

SKALA :

GR :

ÇIKI :

SER NO : 21/14798

Elimko
Tel: +90 3122126450 Fax: +90 3122124143
TÜRKYE

44 mm

44 mm

-0.0 45 x 45 mm
+0.5 10 mm min.

35 mm min.

Panel Cut-Out and Minimum Spacing

Relay and SSR Outputs Analog Inputs

3. CONNECTION DIAGRAM

RL1 13 RL2 14

01

06

SSR2

02 SSR1

07

03

08

Operating voltage suitable for the device type shall be applied.

04

09

AO1

05

11

12

10

RS 485

1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR (SSR1, SSR2).
Only one of analog output (AO1) and RS-485 can be selected.
Analog output (AO1) mA or 0-10 V DC can be selected.

Analog Input

06

06

07

07

08

08

09

09

10

10

06

06

07

07

08

08

09

09

10

10

06

07

08

09

V

10

E-48P controller is designed for panel mounting and should be used in an industrial environment.
 The package of E-48P controller conta ns; Controller, 2 p eces of mount ng clamps, User manual and Guarantee cert f cate.
 After open ng the package, please check the contents w th the above l st. If the del vered product s wrong type, any tem s m ss ng or there are v s ble defects, contact the vendor from wh ch you purchased the product.
 Before nstall ng and operat ng the controller, please read the user manual thoroughly.
 The nstallat on and conf gurat on of the controller must only be performed by a person qual f ed n nstrumentat on.
 Keep the un t away from flamable gases, that could cause explos on.
 Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked n water t ghtly squeezed to gently w pe the outer surface of the controller.
 It s not used n med cal appl cat ons.

EU DIRECTIVE COMPLIANCE
Low Voltage D rect ve EN 61010-1 EMC D rect ve EN 61326-1

K - Q TSE-ISO-EN
9000
TS EN ISO 9001 Quality Management System Certificate

5. TYPE CODING
E-48P Series Universal Advanced Controller

E-48P - W - X - Y - Z

Relay Outputs

None

0

1 relay (RL1)

1

2 relays (RL1, RL2)

2

Reserved

3

1 SSR (SSR1)

4

1 SSR (SSR1) + 1 relay (RL2)

5

Reserved

6

2 SSR (SSR1, SSR2)

7

Reserved

8

Analog Outputs *

0

None

1

0-20 / 4-20 mA (AO1)

2

0-10 V DC (AO1)

Communication

None

0

RS-485 **

1

Operating Voltage

85-265 V AC / 85-375 V DC

0

20-60 V AC / 20-60 V DC

1

* Only one of the analog output and RS-485 options can be coded. For example, only one of the options (X) and (Y) can be coded as 1.

** When E-48P Series controllers are ordered with communication, the E-IB-11 USB-RS485 converter can be used for PC connection. There are various control and monitoring software provided by Elimko.

6. TECHNICAL SPECIFICATIONS

Parameter

Description

Control Type

On/Off, PID, Heat/Cool, Floating and Feedback Control of Valves

Operating Voltage

20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC

Relays / SSR

2 pieces SPST - NO 250 V AC 5A relays or 24 V DC 25 mA (SSR) drives

Dimensions (mm)

48 (Lenght) x 48 (Height) x 100 (Width)

Panel Cut-Out (mm)

45 (Lenght) x 45 (Height)

Analog Output

1 x 0..20 / 4..20 mA or 0..10 V DC optional

Analog Input

Universal (Note 1),

Communication (RS-485) Available (RS-485)

Digital Input

None

Valve Feedback

None

Transmitter Supply

Available

Weight

115 g

Power Consumption Max. 7 W (10 VA)

Operating Temperature - 10 °C ... 55 °C

Storage Temperature - 25 °C ... 65 °C

Memory

Maks. 100.000 write

Protection Class

IP-65 Front Panel, IP-20 Rear Case

Notes:

(1) Universal Input :

Thermocouple

: B, E, J, K, L, N, R, S, T, U

Resistance Thermometer : Pt-100

Current

: 0-20 mA, 4-20 mA (Linear)

Voltage

: 0-50 mV, 0-1 V, 0.2- 1 V (Linear),

0-10 V DC, must be specified in the order.

Resolution

: 16 bit

Accuracy

: Thermocouple, Max. ±1.0 °C (Conversion and CJC error)

Resistance Thermometer, Max. ±0.5 °C

(Conversion and wire resistance compensation)

Linear Input, Max. % 0.1

ALARM SETTINGS
ACNF

CONTROL SET SETTINGS
SETP

INPUT SETTINGS
gcnf

7. PARAMETER TABLE
Description INP1 Analog Input 1 Type
DP Decimal Point SCLO Analog Input 1 Linear Scale Lower Value SCHI Analog Input 1 Linear Scale Upper Value UNIT Temperature Unit OFST Analog Input 1 Offset Value FLTR Analog Input 1 Filter SNBR Analog Input 1 Sensor Broken Behaviour ADRS Modbus Adress BAUD Modbus Baud Rate [4.8, 9.6, 19.2, 38.4 kbaud] PRTY Modbus Parity [None, ODD, Even]
SPSR Control Set Point Source SPLL Control Set Point Lower Limit SPHL Control Set Point Upper Limit SPRR Control Set Point Ramping Rate S-1 1. Step Set Value T-1 1. Step Time S-2 2. Step Set Value T-2 2. Step Time S-3 3. Step Set Value T-3 3. Step Time
A1TP Alarm 1 Type A1SP Alarm 1 Set Point A1HY Alarm 1 Hysteresis A1LT Alarm 1 Lock A2TP Alarm 2 Type A2SP Alarm 2 Set Point A2HY Alarm 2 Hysteresis A2LT Alarm 2 Lock

Min Maks Unit

Table 1

0

3

-199.9 999.9 EU

-199.9 999.9 EU *C *F

-100.0 100.0 EU 1 15 s
LO HI

1 127 4.8 38.4

Table 2 -199.9 SPHL EU SPLL 999.9 EU
OFF 60.0 EU/min SPLL SPHL EU
OFF 999.9 min SPLL SPHL EU
OFF 999.9 min SPLL SPHL EU
OFF 999.9 min
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB

OUTPUTS
OCNF

CTYP CFRM CPRD MNPR TRTM DBND OLL OHL OMR PONC TRLL TRHL RL1D RL2D AO1D AO1R

Control Type Control Form [DIR, REV] Control Period Manual Mode Selection Floating Control Valve Travel Time Dead Band Control Output Lower Limit Control Output Upper Limit Control Output Manual Reset PID Power On Behaviour Retransmission Scale Lower Value Retransmission Scale Upper Value
Relay 1 Function Relay 2 Function Analog Output 1 Function Analog Output 1 Type

AT PID PB-1 PB-2 ITH ITC DTH DTC HYS

PID Auto Tune PID Parameter Type Proportional Band + Proportional Band Integral Time + Integral Time Derivative Time + Derivative Time Hysteresis

SCOD DPRL APRL FCST

Security Code Parameter Access Level Parameter Setting Level Factory Settings [OFF, LOAD, SAVE, DFLT]

Table 4

DIR REV

1 250 s

DSB ENB

10 2500 s

0.1 25.0 %

0.0 OHL %

OLL 100.0 %

OLL OHL %

0

4

-199.9 TRHL EU

TRLL 999.9 EU

Table 5

Table 5

Table 6

Table 7.1 ve Table 7.2

OFF ON
STD ADV
0.1 999.9 EU 0.1 999.9 EU OFF 9999 s OFF 9999 s OFF 2500 s OFF 2500 s 0.0 999.9 EU

0 9999

0

9

0

9

PID SETTINGS
tUNE

SECURITY
PRTC

8. ACCESSING PARAMETERS

STEP 1:

STEP 2:

Security Code Configuration

Entry Page Selection

(Default: 10) and Entry

STEP 3: Parameter Selection and Configuration

Process Screen
199.8
200.0

Selected Page

 

 SCOD
0

 PAGE
GCNF

  Parameters . . .







Adjustment

Enter

Return

Menu Access


9. APPLICATION EXAMPLES
1) Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High AO1: 4-20 mA PID Control Output inp1 a1tp a1sp a2tp a2sp ctyp rl1D rl2D ao1D ao1r pt lo 50.0 hi 55.0 sco al-1 al-2 co-1 4-20
2) Input: TC Type J, Relay1: On-Off Control Output, Relay2 / Alarm2: 350 °C High inp1 a2tp a2sp ctyp rl1D rl2D
j hi 350.0 sco Do-1 al-2
3) Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes), Relay1: PID Control Output, AO1: Retransmission Output (4-20 mA, 0-1200 °C)
inp1 spsr s-1 t-1 s-2 t-2 ctyp trll trhl rl1D rl2D ao1D ao1r k prfl 400 10.0 400 60.0 sco 0 1200 co-1 al-2 pvtr 4-20

Table 1. Input Type Options b Type B Thermocouple e Type E Thermocouple j Type J Thermocouple k Type K Thermocouple l Type L Thermocouple n Type N Thermocouple r Type R Thermocouple s Type S Thermocouple t Type T Thermocouple u Type U Thermocouple pt Pt-100
0-20 0-20 mA 4-20 4-20 mA 0-50 0-50 mV 0.0-1 0-1 V 0.2-1 0.2-1 V 0-10 0-10 V (*) 2-10 2-10 V (*) (*) Custom specified volt input
Table 2. Control Set Options int Internal adjustment with
keys prfl With Profile Control
Table 3. Alarm Options off Off lo Low Alarm hi High Alarm loD Low Deviation hiD High Deviation lob Band Alarm (In) hib Band Alarm (Out)

Table 4. Control Type Options off No Control sco Single (Heat) Dco Double (Heat/Cool) bnD Floating Control of Valve
Tablo 5. Relay Output Options co-1 PID + (Heating) co-2 PID - (Cooling) Do-1 On-Off + (Heating) Do-2 On-Off - (Cooling) al-1 Alarm 1 al-2 Alarm 2 al-3 Alarm 3 al-4 Alarm 4
Table 6. Analog Output Options co-1 PID + (Heating) co-2 PID - (Cooling) pvtr Process Value sptr Control Set Value
Table 7.1. Analog Output Range 0-20 0-20 mA 20-0 20-0 mA 4-20 4-20 mA 20-4 20-4 mA
Table 7.2. Analog Output Range 0-10 0-10 V 10-0 10-0 V 2-10 2-10 V 10-2 10-2 V

For detailed information, you can access the comprehensive user manual of the device under the heading "User Manuals" at www.elimko.com.tr. You can also use the QR Code on the front for this.
Elimko Elektronik malat ve Kontrol Ticaret Ltd. ti. Ankara Sanayi Odasi 2. Organize Sanayi Bölgesi Alci OSB Mahallesi 2001. Cad. No:14 Temelli 06909 Ankara / TURKYE
Tel: +90 312 212 64 50 (Pbx) · Fax: +90 312 212 41 43 · E-mail: elimko@elimko.com.tr · www.elimko.com.tr



References

Corel PDF Engine Version 16.1.0.843 CorelDRAW X6