Schneider Electric Q4L3350 Circuit Breaker

Product Data Sheet

Specifications

Product or Component Type: Circuit breaker

Trip Unit Technology: Thermal-magnetic

Complementary

Line Rated Current: 350 A

Number of Poles: 3P

Breaking capacity code: Q4

Mounting Mode: Unit mount

Magnetic Hold Current: 1750 A

Magnetic Tripping Current: 3500 A

Electrical connection: Lugs, load; Lugs, line

Terminal identifier: AL400LA

Tightening torque: 371.7 lbf.in (42 N.m) 0.08...0.5 in² (50...300 mm²) (AWG 1...600 kcmil); 371.7 lbf.in (42 N.m) 0.08...0.2 in² (50...120 mm²) (AWG 1...250 kcmil)

Height: 11 in (279.4 mm)

Width: 6 in (152.4 mm)

Depth: 5.84 in (148.34 mm)

Environment

Certifications: UL Listed, IEC, CSA

Ordering and shipping details

Category: US10DE200933

Discount Schedule: 0DE2

GTIN: 785901649274

Returnability: Yes

Country of origin: MX

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 9.20 in (23.368 cm)

Package 1 Width: 11.30 in (28.702 cm)

Package 1 Length: 17.70 in (44.958 cm)

Package 1 Weight: 16.510 lb(US) (7.489 kg)

Contractual warranty

Warranty: 18 months

Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via its ongoing "Use Better, Use Longer, Use Again" campaign to extend product lifetimes and recyclability.

Materials and Substances

Packaging made with recycled cardboard: Yes

Packaging without single use plastic: Yes

EU RoHS Directive: Compliant with Exemptions

SCIP Number: 45160aaa-1457-439f-bca7-7bd5246ac23e

REACH Regulation: REACH Declaration

California proposition 65: WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Halogen content performance: Halogen free plastic parts product

PVC free: Yes

Repack and remanufacture

Circularity Profile: No need of specific recycling operations

Take-back: No

Technical Illustration

Dimensions

Electrical Clearance: 1.58 in

Wire Bending Space: 4.27 in (top), 3.73 in (bottom)

Wire bending space is based upon the maximum wire size of the terminal, and NEC article 430-10. Wire bending space for the bottom is the same as the top wire bending space.

Overall Height: 11.00 in

Overall Width: 6.00 in

Overall Depth: 5.84 in

PDF preview unavailable. Download the PDF instead.

Generatepdf.aspx?salesorgid=78&dist=849&lang=42&form=no&documenttype=plain&productid=Q4L3350 cairo 1.15.12 (http://cairographics.org)

Related Documents

Preview Schneider Electric Q4L3400 Circuit Breaker Product Data Sheet
Technical specifications and environmental data for the Schneider Electric Q4L3400 circuit breaker, a 400A, 3-pole, 240VAC, 25kA thermal-magnetic breaker with lug connections.
Preview Schneider Electric LAL36350 Circuit Breaker Product Data Sheet
Product data sheet for the Schneider Electric LAL36350 circuit breaker, featuring specifications, dimensions, environmental data, and ordering information for this 350A, 3-pole, 600VAC thermal-magnetic breaker.
Preview Schneider Electric LAL36300 Circuit Breaker Product Data Sheet
Product data sheet for Schneider Electric LAL36300 circuit breaker. Details include specifications, ratings, dimensions, environmental data, and ordering information for this 300A, 3-pole, 600VAC, 22kA, 250VDC, 10kA thermal-magnetic circuit breaker.
Preview Schneider Electric SLA Circuit Breaker 250A 3 Pole Specifications
Detailed product data sheet for the Schneider Electric SLA circuit breaker, including specifications, complementary features, environmental data, and ordering information. Features a 250A rating, 3 poles, 480VAC, 35kA, 250VDC, thermal-magnetic trip unit, and unit mount.
Preview Schneider Electric HOM250GFICP Homeline 50A 2-Pole Mini Circuit Breaker Datasheet
Detailed product data sheet for the Schneider Electric HOM250GFICP Homeline series miniature circuit breaker. Specifications include 50A current rating, 2 poles, 120/240VAC voltage, 10kA AIR interrupting capacity, Class A ground fault protection, UL listing, and HACR rating. Includes dimensions, environmental data, shipping details, and sustainability information.
Preview Schneider Electric PowerPact 4 Circuit Breaker Datasheet PP41603X
Detailed technical specifications for the Schneider Electric PowerPact 4 molded case circuit breaker, model PP41603X. This datasheet covers its thermal-magnetic trip unit, 160A rating, 36kA breaking capacity, and complementary features.
Preview Schneider Electric EZ9F16132 Easy9 Miniature Circuit Breaker Datasheet
Technical specifications and characteristics for the Schneider Electric EZ9F16132 Easy9 miniature circuit breaker, including electrical ratings, dimensions, environmental data, and certifications.
Preview Schneider Electric TeSys Deca GV2ME14A Motor Circuit Breaker Data Sheet
Detailed specifications for the Schneider Electric TeSys Deca GV2ME14A motor circuit breaker, including its thermal-magnetic protection, snap-in terminals, push button operation, and environmental data.