• Use the solderless terminal with an insulation sleeve in which the M3 screw fits when wiring the instrument. • The terminal block of the JIR-301-M is designed to be wired from the upper side.


File Info : application/pdf, 4 Pages, 1.19MB

PDF preview unavailable. Download the PDF instead.

JIR31JE4
INSTRUCTION MANUAL


DIGITAL INDICATOR JIR-301-M

No. JIR31JE4

SHINKO TECHNOS CO., LTD.

Head office: 2-5-1, Senbahigashi, Minoo, Osaka, 562-0035, Japan

TEL: +81-72-727-6100 FAX: +81-72-727-7006 URL: https://shinko-technos.co.jp/e/ E-mail: overseas@shinko-technos.co.jp

2021.09

For detailed usage, refer to the Instruction Manual for the JIR-301-M. Please download the full Instruction Manual from the Shinko Technos website. https://shinko-technos.co.jp/e/ Support & Downloads Downloads Manuals

Thank you for purchasing our JIR-301-M, Digital Indicator. This manual contains instructions for the mounting, functions, operations and notes when operating the JIR-301-M. To ensure safe and correct use, thoroughly read and understand this manual before using this instrument. To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

Safety Precautions (Be sure to read these precautions before using
our products.) The safety precautions are classified into 2 categories: "Warning" and "Caution".
Warning: Procedures which may lead to dangerous conditions and cause death or serious injury, if not carried out properly.
Caution: Procedures which may lead to dangerous conditions and cause superficial to medium injury or physical damage or may degrade or damage the product, if not carried out properly.

· No large capacity electromagnetic switches or cables through which large current is flowing · No water, oil or chemicals or where the vapors of these substances can come into direct
contact with the unit · Please note that the ambient temperature of this unit ­ not the ambient temperature of the
control panel ­ must not exceed 50 (122 ) if mounted through the face of a control panel, otherwise the life of electronic components (especially electrolytic capacitors) may be shortened.
Wiring Precautions

Warning
· To prevent an electric shock or fire, only Shinko or other qualified service personnel may handle the inner assembly.
· To prevent an electric shock, fire or damage to the instrument, parts replacement may only be undertaken by Shinko or other qualified service personnel.
SAFETY PRECAUTIONS
· To ensure safe and correct use, thoroughly read and understand this manual before using this instrument.
· This instrument is intended to be used for industrial machinery, machine tools and measuring equipment. Verify correct usage after purpose-of-use consultation with our agency or main office. (Never use this instrument for medical purposes with which human lives are involved.)
· External protection devices such as protective equipment against excessive temperature rise, etc. must be installed, as malfunction of this product could result in serious damage to the system or injury to personnel. Proper periodic maintenance is also required.
· This instrument must be used under the conditions and environment described in this manual. Shinko Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring due to the instrument being used under conditions not otherwise stated in this manual.
Mounting Precautions
This instrument is intended to be used under the following environmental conditions (IEC61010-1)]: Overvoltage category , Pollution degree 2 Ensure the mounting location corresponds to the following conditions: · A minimum of dust, and an absence of corrosive gases · No flammable, explosive gases · No mechanical vibrations or shocks · No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
(No icing) · An ambient non-condensing humidity of 35 to 85 %RH

· Do not leave wire remnants in the instrument, as they could cause a fire or malfunction. · Use the solderless terminal with an insulation sleeve in which the M3 screw fits when wiring
the instrument. · The terminal block of the JIR-301-M is designed to be wired from the upper side. The lead wire must be inserted from the upper side of the terminal, and fastened by the terminal screw. · Tighten the terminal screw using the specified torque. If excessive force is applied to the screw when tightening, the terminal screw or case may be damaged.
(0.63 N·m of torque is recommended.) · Do not pull or bend the lead wire on the terminal side when wiring or after wiring, as it could
cause malfunction. · This instrument does not have a built-in power switch, circuit breaker and fuse. It is
necessary to install a power switch, circuit breaker and fuse near the instrument. (Recommended fuse: Time-lag fuse, rated voltage 250 V AC, rated current 2 A) · For the grounding wire, use a thick wire (1.25 - 2.0 mm2). · For a 24 V AC/DC power source, ensure polarity is correct when using direct current (DC). · Do not apply a commercial power source to the sensor which is connected to the input terminal nor allow the power source to come into contact with the sensor. · Use a thermocouple and compensating lead wire according to the sensor input specifications of this instrument. · Use the 3-wire RTD according to the sensor input specifications of this instrument. · When using a relay contact output type, externally use a relay according to the capacity of the load to protect the built-in relay contact. · When wiring, keep input wires (thermocouple, RTD, etc.) away from AC power sources or load wires.
Caution with Respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the manufacture of weapons of mass destruction (i.e. military applications, military equipment, etc.), please investigate the end users and the final use of this instrument. In the case of resale, ensure that this instrument is not illegally exported.

Specifications

Power

100-240 V AC 50/60 Hz Allowable fluctuation range: 85 to 264 V AC

supply

24 V AC/DC 50/60 Hz Allowable fluctuation range: 20 to 28 V AC/DC

Power

100-240 V AC:Approx.8 VA (When max. options ordered: Approx.10 VA)

consumption 24 V AC: Approx.6 VA (When maximum options ordered: Approx. 9 VA)

24 V DC: Approx.4 W (When maximum options ordered: Approx. 7 W)

Ambient temperature 0 to 50 (32 to 122 )

Ambient humidity

35 to 85 %RH (Non-condensing)

Indication

Thermocouple: Within 0.2% of each input span 1 digit, However,

accuracy

R, S input, 0 to 200 (32 to 392 ): Within 6 (12 )

B input, 0 to 300 (32 to 572 ): Accuracy is not guaranteed.

K, J, E, T, N input, Less than 0 (32 ): Within 0.4% of input span

1 digit

RTD: Within 0.1% of each input span 1 digit, or within 1 (2 )

whichever is greater

Direct current, DC voltage input: Within 0.2% of input span 1 digit

Input sampling period 125 ms

Weight

Approx. 300 g

Accessories Screw type mounting brackets: 1 set

Instruction manual excerpt: 1 copy

Unit label: 1 label

Terminal cover: 1 piece (when the TC option is ordered)

A1 output

Relay contact 1a: Control capacity: 3 A 250 V AC (resistive load)

A2 output

Electrical life: 100,000 cycles

A3 output

External dimensions (Scale: mm)

Transmission output 1
Alarm output 4 (A4 option) Insulated power output (P24 option) Insulated power output (P5 option) Power for 2-wire transmitter (DSB option) Transmission output 2 (T2 option)

Resolution:

12000

Direct current: 4 to 20 mA DC (Load resistance: Max. 550 )

Response time: 400 ms+ Input sampling period (0%90%)

Relay contact 1a: Control capacity: 3 A 250 V AC(resistive load)

Electrical life: 100,000 cycles

Output voltage: 24 3 V DC (when load current is 30 mA)

Ripple voltage: Within 200 mV DC (when load current is 30 mA)

Max load current: 30 mA DC

Output voltage: 5 0.5 V DC (when load current is 30 mA)

Ripple voltage: Within 200 mV DC (when load current is 30 mA)

Max load current: 30 mA DC

Output voltage: 24 3 V DC (when load current is 30 mA)

Ripple voltage: Within 200 mV DC (when load current is 30 mA)

Max load current: 30 mA DC

Resolution:

12000

Output accuracy: Within 0.3% of transmission output span

Response time: 400 ms + Input sampling period (0%90%)

Direct current: 4 to 20 mA DC (Load resistance: Max. 550 )

0 to 20 mA DC (Load resistance: Max. 550 )

DC voltage:

0 to 1 V DC (Load resistance: Minimum 100 k )

0 to 5 V DC (Load resistance: Minimum 500 k )

1 to 5 V DC (Load resistance: Minimum 500 k )

0 to 10 V DC (Load resistance: Minimum 1 M )

Gasket

Terminal cover

44.5

4 8

2(* )

96 106.2

11.5

98.5

104.5(*)

(*) When terminal cover is used

Panel Cutout (Scale: mm)

92

0.8 0

0.5 0

45

130

Caution
If vertical close mounting is used for the instrument, IP66 specification (Dripproof/Dust-proof) may be compromised, and all warranties will be invalidated.
Vertical close mounting n: Number of mounted units

n×48-300.5

92

0.8 0

Mounting of the Unit

Caution

As the case of the JIR-301-M is made of resin, do not use excessive force while tightening screws, or the mounting brackets or case could be damaged. 0.12 N·m of torque is recommended.

Mounting of the Unit Mount the instrument vertically to the flat, rigid panel to ensure it adheres to the Drip-proof/Dust-proof specification (IP66). If vertical close mounting is used for the instrument, IP66 specification (Drip-proof/Dust-proof) may be compromised, and all warranties will be invalidated. Mountable panel thickness: 1 to 8 mm (1) Insert the instrument from the front side of the control panel. (2) Attach the mounting brackets by the slots on the right and left sides of the case, and secure the instrument in place with the screws. 0.12 N·m of torque is recommended.

Name and Functions
PV Display SV Display HOLD indicator TX/RX indicator A1-A4 value indicators

UP key FAST key

Display, Indicator Name
PV Display SV Display HOLD indicator TX/RX indicator A1 value indicator A2 value indicator A3 value indicator A4 value indicator A1 action indicator A2 action indicator A3 action indicator A4 action indicator Key
Name UP key
FAST key DOWN key MODE key

A1-A4 action indicators DOWN key MODE key
Description Indicates PV (process variable) or characters in the setting mode with the red LED. Indicates A1/A2/A3/A4 value or the set value in the setting mode with the green LED. When PV is held (HOLD, Peak HOLD, Bottom HOLD), the yellow LED lights. The yellow LED lights during Serial communication (C5 option) TX (transmitting) output. When A1 value is indicated on the SV Display, the green LED lights. When A2 value is indicated on the SV Display, the green LED lights. When A3 value is indicated on the SV Display, the green LED lights. When A4 value is indicated on the SV Display, the green LED lights. (A4 option) When A1 output is ON, the red LED lights. Flashes during A1 output HOLD. When A2 output is ON, the red LED lights. Flashes during A2 output HOLD. When A3 output is ON, the red LED lights. Flashes during A3 output HOLD. When A4 output is ON, the red LED lights. Flashes during A4 output HOLD. (A4 option)
Description Increases the numeric value. If High/Low limit range alarm is selected in [A4 type], and if the SV Display indicates A4 value, the SV Display indicates A4 high limit value while the UP key is pressed. Makes the set value change faster while holding down the UP/DOWN key and FAST key together. Decreases the numeric value. Selects the setting mode, and registers the set value.

Terminal Arrangement
Warning
· Turn the power supply to the instrument off before wiring or checking. Working on or touching the terminal with the power switched on may result in severe injury or death due to electrical shock.
· Tighten the terminal screw using the specified torque. 0.63 N·m of torque is recommended.

Selection Item Set value lock Unlock Lock 1 Lock 2 Lock 3 Communication protocol Shinko protocol MODBUS ASCII mode MODBUS RTU mode Shinko protocol (Block read available) MODBUS ASCII mode (Block read available) MODBUS RTU mode (Block read available) Communication speed 2400 bps 4800 bps 9600 bps 19200 bps 38400 bps Parity No parity Even Odd Stop bit 1 bit 2 bits Input type K -200 to 1370 K -200.0 to 400.0 J -200 to 1000 R 0 to 1760 S 0 to 1760 B 0 to 1820 E -200 to 800

Terminal Code GND PWR
TRANSMIT OUTPUT1 A1 A2 A3 EVENT INPUT TC RTD DC
P24 P5 RS-485 TRANSMIT OUTPUT2 A4 A 24V

Description Ground Power supply voltage 100 to 240 V AC or 24 V AC/DC For a 24 V AC/DC power source, ensure polarity is correct when using direct current (DC). Transmission output 1 A1 output A2 output A3 output Event input Thermocouple input RTD input Direct current input, DC voltage input For direct current input (Externally mounted shunt resistor), connect a 50 shunt resistor between input terminals. Insulated power output 24 V (P24 option) Insulated power output 5 V (P5 option) Serial communication (RS-485)(C5 option) Transmission output 2 (T2 option) A4 output (A4 option) Direct current input (DSB option) Power for 2-wire transmitter (DSB option)

T -200.0 to 400.0 N -200 to 1300 PL- 0 to 1390 C(W/Re5-26) 0 to 2315 Pt100 -200.0 to 850.0 JPt100 -200.0 to 500.0 Pt100 -200 to 850 JPt100 -200 to 500 K -320 to 2500 K -200.0 to 750.0 J -320 to 1800 R 0 to 3200 S 0 to 3200 B 0 to 3300 E -320 to 1500 T -200.0 to 750.0 N -320 to 2300 PL- 0 to 2500 C(W/Re5-26) 0 to 4200 Pt100 -200.0 to 1000.0 JPt100 -200.0 to 900.0 Pt100 -300 to 1500 JPt100 -300 to 900 4 to 20 mA DC -2000 to 10000 (Externally mounted 50 shunt resistor) 0 to 20 mA DC -2000 to 10000 (Externally mounted 50 shunt resistor) 0 to 1 V DC -2000 to 10000 0 to 5 V DC -2000 to 10000 1 to 5 V DC -2000 to 10000 0 to 10 V DC -2000 to 10000 4 to 20 mA DC -2000 to 10000 (Built-in 50 shunt resistor) 0 to 20 mA DC -2000 to 10000 (Built-in 50 shunt resistor) Decimal point place

No decimal point 1 digit after decimal point 2 digits after decimal point 3 digits after decimal point A1/A2/A3/A4 type No alarm action High limit alarm Low limit alarm High limit with standby alarm Low limit with standby alarm H/L limit range alarm(A3, A4 only) A1/A2/A3/A4 Energized/De-energized Energized De-energized Event input function HOLD Peak HOLD Bottom HOLD Alarm HOLD 1 Alarm HOLD 2 A1/A2/A3/A4 HOLD function Disabled Enabled Square root function Disabled Enabled A1/A2/A3/A4 output ON/OFF Output OFF Output ON

Key Operation Flowchart

Power ON

PV/SV Display Mode

PV

A1 value is

A1 value displayed.

+

PV

A2 value is

A2 value displayed.

+

PV

A3 value is

A3 value displayed.

+

PV

A4 value is

A4 value displayed.

+

[About setting item]

A1 value

· Upper left: PV Display: Indicates the setting item characters. · Lower left: SV Display: Indicates the factory default. Right side: Setting item

·

: Available only when option is ordered.

· If Serial communication (RS-485)[C5 option] is ordered, [Event input function] will not be available.

[About key operation]

·

+

: Press the

and

key (in that order) together. The unit will move to the next setting

item, illustrated by an arrow.

·

: Press the

key. The unit will move to Alarm setting mode.

·

+

(3 sec): Press the

and

key (in that order) together for approx. 3 seconds. The unit will

move to Auxilary function setting mode 1.

·

++

(3 sec): Press the ,

and

keys (in that order) together for approx. 3 seconds.

The unit will move to Auxiliary function setting mode 2.

·

+

(5 sec): Press the

and

keys (in that order) together for approx. 5 seconds. The unit will

move to Maintenance mode.

Alarm setting mode A1 value

+

+

(3 sec)

Auxiliary function setting mode 2

Input type

+

(5 sec)

Maintenance mode

A1 output

ON/OFF

A2 value

Scaling high limit

A2 hysteresis

A2 output ON/OFF

A3 value

Scaling low limit

A3 hysteresis

A3 output ON/OFF

A4 value

Decimal point place

A4 hysteresis

A4 output ON/OFF

A4 high limit value

PV filter time constant

A1 delay time

Trans. output 1 manual output

+

(3 sec)

Auxiliary function setting mode 1

Set value lock

Sensor correction coefficient
Sensor correction
Communication protocol
Instrument number
Communication speed
Parity

A1 type
A2 type
A3 type
A4 type
A1 Energized/ De-energized A2 Energized/ De-energized A3 Energized/ De-energized A4 Energized/ De-energized

A2 delay time
A3 delay time
A4 delay time
Transmission output 1 high limit Transmission output 1 low limit Transmission output 2 high limit Transmission output 2 low limit Event input function

Trans. output 2 manual output
Abbreviations: Trans.: Transmission
A2 HOLD function A3 HOLD function A4 HOLD function Square root function

Stop bit

A1 hysteresis

A1 HOLD function

Low level cutoff



References

Adobe PDF Library 21.7.123