CoreSense™ Diagnostic Modules for Copeland Scroll™ Refrigeration Compressors

Bulletin AE8-1424
October 2017

Table of Contents

Safety Instructions

CoreSense™ Diagnostic modules for Copeland Scroll™ refrigeration compressors are manufactured according to the latest U.S. and European Safety Standards. Emphasis has been placed on the user's safety. Safety icons are explained below, and safety instructions applicable to the products in this bulletin are grouped on Page 3. These instructions should be retained throughout the lifetime of the compressor. Users are strongly advised to follow these safety instructions.

Safety Icon Explanation

Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons

Safety Statements

Introduction

The CoreSense™ Diagnostics module for Copeland Scroll™ refrigeration compressors (referred to as 'the CoreSense module' in this document) is a breakthrough innovation for monitoring and protecting the compressor, as well as alerting the contractor to refrigeration system faults. It can also perform digital unloading, liquid injection control, and detect the cause of system-related issues by monitoring the discharge line temperature and current.

A flashing LED indicator communicates the alert code and guides the service technician more quickly and accurately to the root cause of a problem. The CoreSense module is factory installed in the electrical box of all Copeland Scroll 7.5-15 HP ZB*K5 & ZF*K5 refrigeration compressors. Refer to bulletin AE4-1383 for further information on the 7.5-15 HP ZB*K5 & ZF*K5 scroll compressors. It is also offered as a panel mount for an aftermarket solution from Emerson Distribution Services for the (ZB*KC & ZF*K4/KV & ZS*K4) compressors. Refer to Table 5 for Copeland Scroll model number identification. The CoreSense modules offered on the different compressor families are not interchangeable due to different current operating ranges of the compressors.

CoreSense Diagnostics Module Overview

Current Signal Input

This connector is where the current transducer (CT) is plugged into the CoreSense module. In the documentation, this input is labeled 'Current'. For 7.5 -15 HP ZB*K5 & ZF*K5 models, the minimum compressor running current is 3 Amps, and for the (ZB*KC & ZF*K4/KV & ZS*K4) 2-7.5 HP compressors, it is 1 Amp. This input is used to tell the CoreSense module the running state of the compressor. Compressor protective alert codes, injection, and modulation control will only be active when the current transducer is plugged in and current is sensed through the CT.

1-5V Analog Input

1-5V analog input supplied from a separate device, controller, etc., for digital modulation. This would utilize the input labeled ‘DIG 1-5V’. A separate demand input is not required if this input is used. Digital modulation can also be performed via communication and would eliminate the need for a separate 1-5 V analog input.

Discharge Temperature Input

In the documentation, the discharge temperature thermistor input is labeled 'Temp'. CoreSense can utilize both discharge line temperature probes and top cap probes for various compressor applications. When the probe is plugged into the thermistor input, the CoreSense module identifies the probe type (line or top cap) based on pin locations. Refer to Tables 2 & 3 for specific probe part numbers.

RS485 Network Communication

Digital modulation commands are communicated via RS485 network communications to the CoreSense module. If controlling through network communications, 1-5V and demand inputs are not used for this configuration.

Unloading capacities for Copeland Scroll refrigeration compressors are as follows:

Figure 1: CoreSense Diagnostics Module showing connections for LEDs, Current, 1-5V Analog, Discharge Temp, Liquid Injection, Solenoid, and RS485 Network Comm's.

Liquid Injection Output

The CoreSense module can also provide liquid injection for Low Temp scroll compressors. This connector is a 12VDC output to a stepper motor that drives the EXV that is plumbed to the compressor. In the documentation, this output is labeled 'LIQUID INJ'.

Please note that the EXV for the compressor families are not interchangeable due to different orifice sizes:

Refer to Table 3 for EXV, stepper motor, and extension cable part numbers.

Solenoid Output

The solenoid output labeled 'SOL' on the CoreSense module can be used for either digital capacity control or liquid line solenoid. For digital compressors (ZFD/ZBD), Emerson recommends using this output for digital capacity control vs. liquid line solenoid. For digital low temperature compressors using liquid injection (ZFD*K5 or K4), use a current sense relay for the liquid line solenoid.

NOTE: Refer to Table 3 for kit details and extension cables for remote mount 4-7.5 HP models.

CoreSense Module LED Overview

The CoreSense module has four LEDs: green, yellow, red, and blue, that are on the face of the module. These LEDs will flash compressor codes or stay solid depending upon the code that is being annunciated by the CoreSense module.

The CoreSense module can shut down the compressor if an abnormal condition is detected. This is performed by opening the M1-M2 relay on the CoreSense, which is wired in series with the compressor contactor coil. For a list of protective alerts and features, see Figure 11.

There are different categories of flashing codes that the CoreSense Module can annunciate: (Green) normal operation, (Yellow) tripped condition, (Red) lockout, and (Blue) demand error codes and unloading status.

The CoreSense module will trip the compressor 'OFF' when any of the following severe alert conditions (Codes 1, 2, 4, 6, 7 or 9) are detected. Refer to Table 2 for Fault Code Identification. Alert code 7, reverse phase detection, is the only severe alert code that defaults to a lockout and cannot be configured. A trip condition is when the CoreSense pilot circuit relay interrupts the contactor, which results in stopping the compressor motor. A trip condition will automatically allow the compressor to run once the trip condition is satisfied and a protective off time has elapsed.

A lockout event results in the CoreSense module shutting down the compressor and not allowing it to restart until the situation is corrected and the module is manually reset. A manual reset is done by cycling power to the module. Other codes can be configured to lockout, including high discharge temperature, locked rotor, and phase loss. See Error! Reference source not found. for more information on the default number of consecutive trips before a lockout. These default values can be configured through the E2 or PCIF.

Error! Reference source not found. indicates how to read the LED codes. If an alert code is present, the CoreSense module will continue to annunciate the code until the condition is cleared or module power is cycled.

For an explanation of each code and troubleshooting tips, refer to Table 2 at the end of this document.

CoreSense Diagnostics Part Number & Compressor Applications

There are two different CoreSense module part numbers for refrigeration scroll compressors: p/n 543-0209-00 for the ZB*K5 & ZF*K5 and p/n 543-0223-00 for the ZB*KC & ZF*K4/KV & ZB*KC & ZS*K4 compressor families. This is due to the difference in the compressor operating current ranges. It is important to select the correct part number per the compressor family to avoid nuisance trips.

NOTE: In low current applications, it is applicable for both modules to loop the power leads through the current sensor twice. This will double the current value the CoreSense module reads and eliminate the low current nuisance trip.

Product Specifications

Maximum continuous contactor coil current is 2A with a max inrush current of 20A. The CoreSense module connections are 1¼ in male terminals.

CoreSense Module Mounting

Figure 2: Panel Mount CoreSense Module

Figure 3: Terminal Box Mount CoreSense Diagnostics

Network DIP Switch Configuration

Figure 4 shows the two DIP switch panels. The brown DIP switch panel has 10 positions and is located near the center of the CoreSense module. The blue DIP switch panel has 6 positions and is in the upper left corner of the CoreSense module.

Figure 4: CoreSense Diagnostics DIP Switches showing Node Addresses, Baud Rate, Parity, Control Network Mode, Termination, and Positions 1-10.

Figure 5: CoreSense Diagnostics DIP Switches.

Figure 6: Brown 10 Position.

Switches 1-5

Switches 1 through 5 are used for setting the node address for each CoreSense module. The CoreSense module uses a binary addressing for switches 1-5. The unique combination of these switches will define the node address 1-31. Use Table 1 as a reference to setting node addresses.

Switch 6

CoreSense Diagnostics Modbus® communication baud rate setting is configurable to either 19200 or 9600 through DIP switch 6 on the 10 position dip switch.

The baud rate for each of the CoreSense devices should be set to match the rack controller. To determine the baud rate in the E2, follow these steps:

Switch 7

CoreSense Diagnostics Modbus® communication parity is user configurable (even or no parity) through DIP switch number 7.

The parity setting must match the parity setting of the rack controller.

Switch 8

Switch 8 is used to set the module to be in network mode or standalone.

Network mode will generate a communications error if the rack controller fails to communicate with the device. For standalone mode, no communications are expected, so the communication error is blocked. The CoreSense Diagnostics module can communicate with a rack controller using Modbus® protocol. The communication cable is wired from the rack controller to the first compressor. Additional compressors are wired in a daisy chained configuration. A shielded, twisted pair cable such as Belden #8761 (22AWG) should be used for the communication wiring. Passing the communications wire through the grommet in the plastic housing will help reduce abrasion to the wiring. Appropriate strain relief is recommended.

Modules using a communications network must be commissioned as part of the E2 rack controller setup. The commissioning process uploads compressor asset information (model and serial number) into the rack controller for future reference. Once the commissioning process is completed, the controller will supervise and communicate with the module unless the node is deleted. Refer to AE1383 section titled Modbus® Communication to CoreSense Diagnostics for K5 Compressors or an E2 manual for more details on commissioning scroll compressors with an Emerson Retail Solutions E2 rack controller.

NOTE: For digital capacity using an E2 controller, an enhanced suction group must be enabled.

More information: The E2 jumpers on the Network Interface Board should be set for 'terminated'.

NOTE: The RS485 is polarity sensitive. + wires must connect to other + terminals, and - wires must connect to other - terminals. The shield wire is connected to the center terminal, or 0 volt position.

Figure 7: CoreSense Modbus Connections

Switch 9

Switch 9 is NOT used.

Switch 10

The last compressor in the daisy chain must be 'terminated' by setting DIP switch 10 to the 'on' position. For all other compressors, switch 10 should remain in the 'off' position.

Compressor DIP Switch Configuration

Figure 8: Blue 6 Position

Switch 1

Switch 1 is used to enable liquid injection EXV control. The 'on' position enables the EXV control via the CoreSense module.

Switch 2

Switch 2 is used to enable digital capacity control. The 'on' position enables digital capacity control via the CoreSense Module.

ZB*KC & ZF*K4/KVE & ZB*K5: 10 -100 % Capacity for 4-7.5 HP compressors & Medium Temp 7-15HP K5 compressors

ZF*K5: 30 -100% Capacity for Low Temp 7-15 HP K5 compressors

Switch 3

Switch 3 is used for failsafe mode. The 'ON' position will allow the compressor to run at full load if communications between the CoreSense module and the rack controller is lost. If in the 'off' position, the compressor turns off if communication is lost between the two devices.

Switch 4

Switch 4 affects standard Modbus®. For applications using IPRO™™ or XWeb™™ (Dixell) 'non-standard Modbus®', turn switch 4 'on'. For standard Copeland ™™ Modbus, the DIP switch orientation doesn't matter. For all other standard Modbus®, DIP switch 4 should be in the 'off' position.

CoreSense TM Diagnostics Modbus communication stop bits is user configurable to either be 1 or 2 stop bit. DIP switch number 4 on the main DIP switch board is used to configure stop bit.

Switch 5

Switch 5 is used to return module to factory defaults. By resetting the module, all configurations and module history will be erased. To reset, switch 5 must transition from 'off' to 'on' within 5 seconds of module power up.

Switch 6

Switch 6 is used to enable/disable lockouts. The 'on' position will enable lockouts for the following codes: high discharge temperature, missing phase, and locked rotor. Reverse phase is automatically a lockout and cannot be configured. If this switch is 'on', each of these lockouts can be individually configured to a specific number of trips before a lockout. This is done over communications or via the PCIF Software (available at Emerson.com/OPI).

CoreSense Diagnostics Wiring

Current Transducer (P/N 543-0159-00)

Figure 10: Current Transducer Diagram

A current transducer (CT) is used in conjunction with the CoreSense module to detect the running state of the compressor. The compressor power wires T1, T2, and T3 must be routed from the contactor through the CT L1, L2, and L3, respectively, to detect the running state of the compressor. It is important that the compressor power wires are routed in respect to the markings on the current transducer. For 7-15 HP K5 compressors, the CT is mounted in the terminal box. For 4-7.5 HP applications, the CT is mounted in the panel near the CoreSense module. An extension cable is available for 4-7.5 HP applications if needed.

NOTE: Only the compressor lead wires should be placed through the CT module. If the compressor lead wires do not match the L1, L2, and L3 Current Transducer holes, the compressor current measurement will be incorrect.

110-230VAC CoreSense Module Power Wiring

The CoreSense module requires 110-230VAC power between the L1 and L2 terminals on the module. The module should remain powered through all states of compressor on/off operation. Refer to wiring schematic examples shown in the following section.

Module Wiring Diagrams

There are 3 basic applications that require specific wiring schematics and DIP switch configurations:

  1. Fixed Capacity using the Demand Input (Figure 11)
  2. Digital Compressors using Analog Input for the modulation (Figure 12)
  3. Digital or Non-Digital compressors using control via communications (Figure 13)

It should be noted that CoreSense modules with p/n 543-0209-00 and 543-0223-00 have a normally open M1-M2 relay and that will only close when the demand is present. This eliminates the need for a cycling device to be supplied externally from the module. On a detected tripped or lockout condition, the CoreSense module will de-energize the M1-M2 relay to stop the motor from running.

1. Fixed Capacity Using Demand Input

Figure 11 shows the wiring diagram for a fixed capacity compressor using a demand signal. The demand signal must be supplied from a control relay and wired to the 'D' terminal of the module. It is preferred the demand wired upstream of any other device in the pilot circuit.

NOTE: Referring to Figure 11, the Blue DIP Switch #2 is 'OFF' for fixed capacity.

Figure 11: Fixed Capacity Using Demand Input Wiring Diagram

2. Digital Compressors Using Analog Input for Modulation

Figure 12 shows the wiring for Digital Compressors using analog input for the modulation. The network dip switch #8 must be in the 'OFF' position for the digital control when using a 1-5V analog input. A demand wire is not required to be run to the 'd' terminal. The 1-5V analog signal for the digital will close the module relay from normally open to closed when the compressor is called to run.

NOTE: Referring to Figure 6, Brown DIP Switch #8 is 'OFF' for Digital Operation with Analog Input. Also, referring to Figure 8, Blue DIP Switch #2 is 'ON' for Digital Operation.

Figure 12: Digital Compressors Using Analog Input for Modulation Wiring Diagram

3. Digital and Non-Digital Compressors Using Control Via Communications

Figure 13 shows the wiring diagram for a digital or non-digital application using an E2 controller. Demand is supplied via communications and a wire is not required to be run to the 'd' terminal. The communications must be hooked up to the E2, and the module brown dip switch #8 must be 'ON' and the blue dip switch #2 must be 'ON' for the digital control to work. There is no 1-5 V analog input used to control the digital in this arrangement because digital control is provided via the E2. This is the easiest way of wiring for digital control if an E2 is present.

NOTE: Referring to Figure 6, Brown DIP Switch #8 is 'ON' for Digital Operation via Communications. Also, referring to Figure 8, Blue DIP Switch #2 is 'ON' for Fixed Capacity.

For E2 commissioning please refer to the following instructions.

Figure 13: Compressors Using Control via Communications Wiring Diagram

CoreSense Diagnostics E2 Programming Instructions

1. Press the Menu button to enter the Main Menu. Select 7. System Configuration.

2. From the System Configuration Menu select 7. Network Setup.

E2 System Configuration Menu Screen 1

E2 System Configuration Menu Screen 2

3. From the Network Setup Menu select 2. Connected I/O Boards and Controllers.

4. From the Setup Screen go to the C3: ECT Tab (Press Ctrl + 3).

5. In Option #9, enter the number of K5 compressors being controlled by the E2.

Press the Menu button to save changes and return to the previous screen.

E2 Network Setup Screen 1

E2 Network Setup Screen 2

6. From the Network Setup Menu select 1. Network Summary.

7. The CoreSense™ K5 devices should be present on the Network. Select the CoreSense K5 module to be commissioned. Press F4: Commission.

E2 Network Summary Screen 1

E2 Network Summary Screen 2

8. Select the Modbus® that the CoreSense device is connected to. (If only Modbus® network is connected, this step will automatically complete itself, skip to step 9).

9. From the Modbus® Device Menu select an unused space that matches the DIP switch Address of the CoreSense device and press Enter.

E2 Modbus Device Menu Screen 1

E2 Modbus Device Menu Screen 2

10. Verify the address matches the address assigned by the CoreSense module's DIP switch settings and press Enter.

11. Press the Menu button to return to the Network Summary screen. The device should now be 'Online'. Repeat steps 8-10 to address the remaining CoreSense K5 modules.

12. Once all the devices are addressed, press the Menu button to save changes and exit the Network Summary.

E2 Network Summary Screen 3

13. Press the Menu button to enter the Main Menu. Select 7. System Configuration.

14. From the System Configuration Menu select 7. Network Setup.

E2 System Configuration Menu Screen 3

E2 Main Menu Screen

15. From the Network Setup Menu, select 4. Controller Associations. Then Select 4. Compressor (Press Enter).

E2 Controller Associations Screen 1

E2 Controller Associations Screen 2

16. Highlight the Suction Group field, select F4: Look Up (Press F4) and select the appropriate suction group for the device and press Enter.

E2 Compressor Association Screen 1

E2 Application Selection Screen

17. Scroll over to the Comp Stage and type in the compressor stage. (CoreSense Protection provides proofing only on the compressor.) NOTE: The compressor stage number should correspond to the stage numbers in the suction group setup (Step 7).

E2 Compressor Association Screen 2

Alert Codes & Troubleshooting Tips

Table 2 is an explanation of the alert codes for the CoreSense and what the flash codes mean. It is also available on the inside of the terminal box lid on all 7-15 HP K5 compressors or as part of the 4-7.5 HP kits. Table 3 provides some troubleshooting tips for the alert codes. There are 4 colors that can flash from the module: green - all is okay, yellow - there has been a system trip, and this will auto reset once the trip has cleared, red - is a lockout and will require a manual reset on the contractor's part. This means the power must be cycled to the CoreSense. Blue is used for digital applications and will light up when the scroll set is unloaded. There are also troubleshooting tips to help identify and fix the issue.

Further information and tips are also available at Emerson.com/OPI.

Table 2: Alert Code Descriptions

Alert Code Code Description Protection Shutdown (Default) Protection Off Time (Default) Consecutive Detections Until Lockout
⭐ 1 High Discharge Temp - see diagram for setting Yes 20 Min. 4
⭐ 2 Excess System Limit Trips - 4 consecutive system limit trips having 1-15 min runtime each Yes 5 Min. No Lockout
⭐ 3 Excessive Demand Cycling - Default is 240 cycles per 24 hr. period No - -
⭐ 4 Locked Rotor Yes 20 Min. 4
⭐ 5 Compressor did not start within allotted time No - -
⭐ 6 Phase Loss Detected Yes 20 Min. 10
⭐ 7 Reversed Phase Detected Yes Until Module Is Reset 1
⭐ 8 Welded Contactor - Current detected without demand¹ No - -
⭐ 9 Low Module Voltage Yes 5 Min. No Lockout
⭐ 10 Module Communications Error No - -
⭐ 11 Discharge Temperature Sensor Error No - -
⭐ 12 Current Transducer Error No - -
Digital Alert Codes:
? 1 Loss of analog demand - Check analog voltage
? 2 Network mode ON, 1-5V input present - Check position of DIP switch #8
? 3 Network model OFF, receiving Modbus communication - Check position of DIP switch #8

¹Code 8 displays for 24 hours after last detection.

The M1-M2 relay only opens during a protection shutdown. To reset module, cycle module power. Module must be reset for DIP switch changes to take effect.

For technical support call 1-888-367-9950 or visit Emerson.com/OPI. Refer to AE4-1383 for more details.

Table 3: CoreSense Diagnostics Module Troubleshooting

Status LED Status LED Description Status LED Troubleshooting Information
Yellow Alert LED (4 Flashes) Locked Rotor
Compressor is drawing current without rotating or four consecutive compressor trips after run time of 1-15 seconds
1. Low line voltage (contact utility if voltage at disconnect is low)
2. Verify presence of all legs of power line
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
5. Verify operating current
Yellow Alert LED (6 Flashes) Missing Phase
Demand signal is present but current is missing in one phase
1. Improper wiring. Correct order of phases in wires
2. Failed contactor. Check contacts for pitting
3. Compressor current could be too low. Refer to specifications.
4. Verify presence of all legs of power line
Yellow Alert LED (9 Flashes) Low Voltage Detected
Control voltage dips below 85V for 110V or 170V for 220V
1. Low line voltage (contact utility if voltage at disconnect is low)
2. Check wiring connections
Red Alert LED (1 Flash) LOCKED OUT ON:
High Discharge Line Temperature Trip
See inside label to determine cut out temp.
1. Possible loss of refrigerant charge
2. Blocked condenser
3. Verify that discharge valve is open
4. On low temperature scroll compressors check liquid injection
Red Alert LED (4 Flashes) LOCKED OUT ON:
4 Consecutive Locked Rotors Detected
Compressor is drawing current without rotating or four consecutive compressor trips after run time of 1-15 seconds
1. Low line voltage (contact utility if voltage at disconnect is low)
2. Verify presence of all legs of power line
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
5. Verify operating current
Red Alert LED (6 Flashes) LOCKED OUT ON:
10 Missing Phase Detections
Demand signal is present but current is missing in one phase
1. Improper wiring. Correct order of phases in wires.
2. Failed contactor. Check contacts for pitting.
3. Compressor current could be too low. Refer to specifications.
4. Verify presence of all legs of power line
Red Alert LED (7 Flashes) LOCKED OUT ON:
1 Reverse Phase Detected
Demand signal is present but current is not detected in the correct sequence
1. Improper wiring. Correct order of phases in wires.
2. Compressor current could be too low. Refer to specifications.
3. Verify presence of all legs of power line

Kits & Accessories

Kits and accessories are available through Emerson Distribution Services. Below are references for the kit part numbers you will need when ordering parts. Please note that there are different lists for 7.5-15 HP ZB*K5 & ZF*K5 and 2- 7.5 HP (ZB*KC & ZS*K4 & ZF*K4/KV) scroll compressors when searching for kit numbers. Additional information and kit numbers for 7.5-15 HP ZB*K5 & ZF*K5 scroll compressors can be found in AE4 1383.

Table 4: CoreSense Diagnostics Service Kits for K5 Compressors (ZB*K5 & ZF*K5)

P/NModules
943-0159-00Current Sensing Module
943-0209-00CoreSense Diagnostic Module
P/NCrankcase Heaters
918-0047-00120 V Crankcase Heater 90W 48" Lead Length
918-0047-01240 V Crankcase Heater 90W 48" Lead Length
918-0047-02480 V Crankcase Heater 90W 48" Lead Length
918-0047-03575 V Crankcase Heater 90W 48" Lead Length
998-7029-00Crankcase Heater Enclosure Box
P/NDigital Components
998-0060-03120V Digital Solenoid Coil
998-0060-04240V Digital Solenoid Coil
998-0189-00Closed Loop Digital Controller (Single Compressor Applications)
998-0341-001-5 V Analog Input Wire Kit
998-0342-00Digital Solenoid Coil Wire (CoreSense Module to Digital Solenoid Coil)
P/NDischarge Line Thermostats/Thermistors
998-0176-00Thermistor Kit (Includes Top Cap, and DLT Themistors)
998-0229-00Top Cap Thermistor Kit (Top Cap Thermistor Only)
P/NLiquid Injection Components
998-0177-00DTC Vapor Injection Adapter
998-0340-00Electronic Liquid Injection Valve Kit
998-0359-00Liquid Solenoid Cable Kit
998-0500-03DTC Kit, 250F Set Point DTC With 268F Thermistor for Liquid Injection
P/NMotor Protection
971-0641-00External Motor Protection Module
P/NMounting
527-0116-00Spacer Mounting Kit, 30-35 Durometer, 1.45" OD, 0.44" ID, 0.75" Height
527-0210-00Spacer Mounting Kit, 55-65 Durometer, 1.62" OD, 0.44" ID, 1.75" Height
998-0178-00Hard Mount Kit, 1.87" OD, 0.69" ID, 0.31" Height
P/NOil Management
65365Oil Management Control w/ Junction Box 24V, 50/60Hz
65366Oil Management Control w/ Series Relief Connector 24V, 50/60Hz
66652Oil Management, OMB Adapter (One Piece)
P/NService Valves and Adaptors
998-0034-08Rotalock to Stub Tube Adapter, 1 1/4"-12 Thread to 7/8" Sweat
998-0034-13Rotalock to Stub Tube Adapter, 1 3/4"-12 Thread to 1 3/8" Sweat
998-0034-18Rotalock to Stub Tube Adapter, 1"-14 Thread to 1/2" Sweat
998-0510-39Service Valve Kit, 1 1/4"-12 Thread to 7/8" Sweat
998-0510-46Service Valve Kit, 1 3/4"-12 Thread to 1 3/8" Sweat
998-5100-27Service Valve Kit, 1 3/4"-12 Thread to 13/8" Sweat and 1 1/4"-12 Thread to 7/8" Sweat

Table 5: Compressor Model Identification

Medium Temperature Kit | Part Number 943-0050-00Digital Available (*) 4-7.5 HPDigital Available (*) 2-4 HP
- Includes all parts below -
CoreSense ModuleZBD28KC (Digital Only)ZB12KC ZB28KC
Current Transducer ModuleZB30KCE*ZB15KC ZB29KC*
Top Cap ThermistorZB38KCE*ZB17KC ZS15K4
Syringe - Dielectric GreaseZB42KCEZB19KC ZS19K4
Silicone SealantZB45KCE*ZB20KC ZS21K4
ZB48KCEZB21KC* ZS26K4
ZB57KCE*ZB26KC
Low Temperature Kit | Part Number 943-0051-004-7.5 HP
- Includes all parts below -
CoreSense ModuleZF13KVE*
Current Transducer ModuleZF18KVE*
EXV - 1.3mm Orifice w/ 1" Rota lockZF25KVE*
Stepper MotorZF28KVE
Seal - Rota lock Fitting (3 Pieces)
Tee Fitting
Digital Solenoid Wire
Top Cap Thermistor
Silicone Sealant
Low Temperature Kit | Part Number 943-0051-014-7.5 HP
- Includes all parts below -
CoreSense ModuleZF13K4E
Current Transducer ModuleZF15K4E
Exv - 1.3mm Orifice w/ 11/16" Rota lockZF18K4E
Stepper MotorZF25K4E
Seal - Rota lock Fitting (3 Pieces)ZF28K4E
Digital Solenoid Wire
Top Cap Thermistor
Silicone Sealant
Syringe - Dielectric Grease
Digital KitsKit NumberFor use on these 4-7.5 HP modelsDigital Models
110 V Solenoid923-0058-08ZBD30KCE-TFD ZFD13KVE-TFD
220 V Solenoid923-0058-09ZBD38KCE-TFD ZFD18KVE-TFD
Digital Tubing Kit998-0073-00XZBD45KCE-TFD ZFD25KVE-TFD
ZBD57KCE-TFD
Digital KitsKit NumberFor use on these 2-4 HP modelsDigital Models
110 V Solenoid923-0058-08XZBD21KC*-TFD
220 V Solenoid923-0058-09ZBD21KC*-TF5
Digital Tubing Kit998-0066-09ZBD29KC*-TFD
ZBD29KC*-TFD
Extension Harnesses ComponentsLengthKit Number
Current Transducer Module Extension Cable3'529-0297-00
Current Transducer Module Extension Cable10'529-0297-01
EXV Extension Cable for Liquid Injection8'543-0253-00
EXV Extension Cable for Liquid Injection10'543-0253-01
EXV Extension Cable for Liquid Injection12'543-0253-02
EXV Extension Cable for Liquid Injection15'543-0253-03
EXV Extension Cable for Liquid Injection18'543-0253-04
EXV Extension Cable for Liquid Injection20'543-0253-05
Top Cap Thermistor Extension Cable8'529-0299-00
Top Cap Thermistor Extension Cable10'529-0299-01
Top Cap Thermistor Extension Cable12'529-0299-02
Top Cap Thermistor Extension Cable15'529-0299-03
Top Cap Thermistor Extension Cable18'529-0299-04
Top Cap Thermistor Extension Cable20'529-0299-05
Digital Tray Cable8'529-0300-00
Digital Tray Cable10'529-0300-01
Digital Tray Cable12'529-0300-02
Digital Tray Cable15'529-0300-03
Digital Tray Cable18'529-0300-04
Digital Tray Cable20'529-0300-05
Digital Capacity Control Cable998-0341-00
Liquid Line Solenoid Cable (non-digital)998-0359-00
1-5V Analog Input Wire with Butt Splice
Miscellaneous KitsKit Number
CoreSense Module943-0223-00
Current Transducer (Only contains Mounting kit)943-0159-00
EXV Liquid Injection kit for ZF**K4/ ZB*KC/ ZS*K4 11/16" Rotalock998-0740-00
EXV Liquid Injection kit for ZF**KVE /ZF*K5 1" Rotalock998-0741-00

PDF preview unavailable. Download the PDF instead.

ae-bulletin-ae81424-coresense-diagnostics-for-copeland-scroll-compressors-en-5245874 Microsoft Word 2016

Related Documents

Preview Copeland Scroll™ Compressors: Continuing Innovations in Refrigeration Reliability | Emerson
Explore the advancements in Copeland Scroll™ compressors by Emerson, focusing on enhanced efficiency, reliability, and smart diagnostics for commercial refrigeration. Learn about their wide application range, robust design, and support network.
Preview Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors - Emerson Copeland
This Emerson Application Engineering bulletin (AE4-1327 R14) details the Economized Vapor Injection (EVI) technology for Copeland Scroll compressors, specifically the ZF*KVE and ZF*K5E series. It explains the principles of EVI, its advantages in improving capacity and energy efficiency, and provides comprehensive technical information on system configuration, design guidelines, safety instructions, and component selection. The document serves as a guide for engineers and technicians working with these advanced refrigeration compressor systems.
Preview Emerson Ovation I/O Modules Technical Specifications
Detailed technical specifications and configuration options for Emerson's Ovation series of Input/Output (I/O) modules, including analog, digital, and relay modules for industrial automation.
Preview Ovation I/O Reference Manual: Emerson Process Control Modules
Comprehensive guide to Emerson Ovation I/O modules (R3-1150), covering analog, digital, high-speed, and specialty modules for industrial process control and automation. Includes installation, configuration, and troubleshooting.
Preview Emerson Water-Cooled Scroll Condensing Unit User Manual
Comprehensive user manual for Emerson's Water-Cooled Scroll Condensing Units, featuring Copeland Scroll Compressors. This guide covers installation, commissioning, operation, safety information, technical specifications, and maintenance for optimal performance.
Preview Copeland Scroll ZB Series Large Refrigeration Compressors | Emerson Technical Specifications
Explore the technical specifications, features, and protection systems of Emerson's Copeland Scroll ZB Series large refrigeration compressors. This document details models, performance data, CoreSense and Kriwan protection modules, and essential safety controls for commercial refrigeration applications.
Preview CoreSense Diagnostics v2.11 for Copeland Discus Compressors - Installation and Service Manual
This Application Engineering Bulletin provides comprehensive installation, operation, and troubleshooting guidance for Emerson's CoreSense Diagnostics v2.11 system, designed for Copeland Discus compressors, enhancing system reliability and performance.
Preview DeltaV M-series Traditional I/O Product Data Sheet
This document provides detailed information on the DeltaV M-series Traditional I/O subsystem, including its benefits, product description, various I/O card specifications, terminal block compatibility, system compatibility, certifications, and ordering information. It covers analog input, analog output, discrete input, and discrete output cards, along with their technical specifications and application guidelines.