Greenheck Single Duct VAV Terminals

Installation, Operation and Maintenance Manual

Document 1041402

Models: XG-TH, XG-TL, XG-BP

Introduction

Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.

General - Safety Information

Only qualified personnel should install this unit. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. If more information is needed, contact a licensed professional engineer before moving forward.

  1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Association (NFPA), and the Canadian Electrical Code (CEC), where applicable.
  2. Unit must be securely and adequately grounded.
  3. Verify that the power source is compatible with the equipment.
  4. Electrical equipment should be transported, stored, installed, and operated only in the environment for which it is designed.

DANGER

Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.

WARNING

Always disconnect power before working on or near a unit. Use appropriate lockout tagout procedures to prevent accidental power up.

NOTICE

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

Receiving Inspection and Hanging/Installation Requirements

Prior to removing the shipping materials, visually inspect the packing materials. There should be a black plastic strip wrapped in the clear plastic stretch wrap. If this black plastic strip is missing, the shipment may have been repacked by the shipper and you should make a note of this on the shipping documents and inform the delivering carrier. If any damage or other concerns are present, make a note of this on the shipping documents and inform the delivering carrier.

After unpacking the Single Duct Air Terminals, check for shipping damage. If any shipping damage is found, report it immediately to the delivering carrier.

Always store the product in a clean dry location prior to installation.

Units with controls are not recommended for use in ambient temperatures greater than 95°F. For protection of controls, do not store in temperatures above 135°F.

General - Model Number Code

The model number code provides basic identification of the unit.

Brand Model Series Case Inlet 1 Inlet 2 Attenuator
Greenheck TH, TL, BP 1, 2, 3, 4, 5, 6, 7, 8, 9 01-, 02-, 03-, 04-, 05-, 06-, 07-, 08-, 09-, 10-, 12-, 14-, 16-, 20-, 24- 04-, 05-, 06-, 07-, 08-, 09-, 10-, 12-, 14-, 16-, 120V-, 140V-, 160V-, 14X10-, 16X10-, 20X10-, 22X10-, 8X16-, 18X16-, 20X16-, 24X16- 00-, 04-, 05-, 06-, 07-, 08-, 09-, 10-, 12-, 14-, 16- IDA, NA, IA, DA

Installation

CAUTION: HAZARD OF EQUIPMENT DAMAGE
Do not use the flow sensor, connecting tubing or damper shaft as a lift point. Damage to the components may result.

NOTICE: Unit is not recommended for installation above 2,000 m.

Unless local building codes require hangers, the smaller size basic Single Duct Air Terminals may be light enough to be supported by the ductwork itself. However, when accessory components such as controls, hot water reheat coils, sound attenuators or electric reheat are included, the single duct terminal should be supported directly with straps screwed into the side of the terminal. (See figure 1)

Figure 1 - Hanging Straps

Description of Figure 1: Illustrates metal strap-hangers secured to building structure, supporting the unit. Features include Air Flow Sensor, Compression strap on flexduct to ensure airtight joint, Basic Air Terminal, Damper Shaft, Slip & Drive Connections, Duct, Optional Hot Water Coil. Notes indicate minimum three equivalent (de) duct diameters of straight duct on air terminal inlet recommended, and a method for attaching the coil with a 1/2" long sheet metal screw.

Alternate trapeze hangers or the method prescribed for the rectangular duct on the job specification may be used. (See figure 2)

Figure 2 - Trapeze

Description of Figure 2: Depicts trapeze hangers. Features include Air Flow Sensor, Compression strap on flexduct to ensure airtight joint, Basic Air Terminal, Damper Shaft, Optional Sound Attenuator (SA), Duct. Notes indicate maintaining 10-1/2" clearance from air terminal to support rods for access to controls, 5/16" or 3/8" diameter hanger rods secured to building structure, and 3/4" x 3/4" x 1/8" angles for support.

Figure 3 - Optional Hanger Brackets and Hanger Rods

Description of Figure 3: Shows a diagram of a Single Duct Air Terminal with optional hanger brackets and hanger rods (5/16" minimum). Features include Primary air inlet and the main body of the terminal.

Single Duct Terminal Units are not designed nor suitable for outdoor use.

In advance of start-up, verify all electrical connections are tight and the correct voltage is supplied to the Single Duct Terminal Unit per the rated voltage listed on the unit label. If factory-supplied controls are present, review all wiring diagrams to assure a complete working knowledge.

IMPORTANT

If equipped with pneumatic controls, the orientation of the Single Duct Air Terminal unit is critical. The pneumatic controls must be mounted right side up. The Single Duct Terminal must be level within + or – 10 degrees of horizontal, both parallel to the airflow and at right angle of airflow. The control side of the Single Duct Terminal is labeled with an arrow indicating up. Unless otherwise noted, most electric, analog electronic and digital controls are not position sensitive and may be installed in any orientation.

MINIMUM CLEARANCE FOR ACCESS

Single Duct Air Terminals require sufficient space to allow servicing of the controls and electric reheat power hookup (if applicable). Horizontal clearance requirements are dependent upon access panel dimensions which are indicated on the appropriate submittal. For control panel access, a minimum of 18" is recommended. See the appropriate submittal for control panel location.

CAUTION
These clearance recommendations are not meant to preclude NEC requirements or local building codes that may be applicable, which are the responsibility of the installing contractor.

CONNECTING DUCT WORK

NOTICE: Do not insert duct work inside the inlet collar of the Single Duct Air Terminal. Inlet duct should be installed in accordance with SMACNA guidelines.

  1. Slip each inlet duct over the inlet collar of the Single Duct Air Terminal.
  2. Fasten and seal the connection by method prescribed by job specification.
  3. The diameter of the inlet duct in inches must be equal to the listed size of the Single Duct Air Terminal; e.g., a duct that actually measures 8 inches must be fitted to a size 8-inch Single Duct Air Terminal. The inlet tube of the Single Duct Air Terminal is manufactured 1/8" smaller than the listed size in order to fit inside the duct.
  4. If an inlet airflow sensor is installed, it is recommended the installer provide a minimum of 3 duct diameters of straight duct at the Single Duct Air Terminal inlet.
  5. The outlet end of the Single Duct Air Terminal is designed for use with slip and drive duct connections (flanged outlets optional).
  6. A rectangular duct the size of the Air Terminal outlet should be attached. (Refer to submittal for correct size.)

FIELD ELECTRICAL WIRING

DANGER
High voltage electrical supply is needed for this equipment. The control cabinet contains live electrical parts. Contacting these parts with power applied may cause serious injury or even death. This work should only be performed by a qualified electrician.

All field wiring must comply with local building codes and NEC. (ANSI/NFPA 70).

When applicable, electrical control and piping diagrams are attached to the inside of the control enclosure cover of the Single Duct Air Terminal.

Use copper only conductors with insulation rated 75°C.

The Single Duct Air Terminal must be properly grounded per NEC 424-14 and 250.

Always check product label for voltage and current data to determine the proper wire size and over current protection.

The control panel cover must be closed or in place before applying electric power to the Single Duct Air Terminal.

These recommendations are not meant to preclude NEC requirements or other applicable local building codes and are the sole responsibility of the installing contractor.

NOTICE: If the unit is not ordered with an internal disconnecting device then a disconnection device that shall disconnect all phases must be provided by the customer and incorporated in the fixed wiring.

SINGLE DUCT AIR TERMINALS WITH ELECTRICAL REHEAT

WARNING
Single Duct Air Terminals must not be operated without downstream ductwork in place. Failure to have downstream ductwork installed will expose the line voltages and high temperature present in the operating heater elements. Contact with these heater elements may cause serious injury or death.

SINGLE DUCT AIR TERMINALS WITH HOT WATER COILS

CAUTION: HAZARD OF EQUIPMENT DAMAGE
The copper tubing should not be used as lift points. Always inspect the hot water coils for damage prior to installing the Single Duct Air Terminal.

CONTROLS

NOTICE: Single Duct Air Terminals with digital controls, if factory programmed, incorporate specific communication addresses. Installing the Single Duct Air Terminal in a different location than noted on the Single Duct Air Terminal label and building plans may result in excessive start-up labor and is the sole responsibility of the contractor.

For information on controls provided by other manufacturers and installed on the Air Terminals, contact the local branch or dealer.

INLET FLOW SENSOR

Single Duct Air Terminals are shipped with factory-installed (where applicable) pressure differential inlet flow sensors in the primary inlet. See figure 4 for calibration curve and K factors. Bypass Air Terminals offer an optional downstream flow sensor for field installation a minimum of 3 feet downstream of box discharge.

Troubleshooting

Investigating Noise Complaints

Discharge Noise

Radiated Noise

Electric Duct Heater

CAUTION
Use extreme care if testing the electric heater with power on. The control cabinet contains live electrical parts. Contacting these parts with the power applied may cause serious injury or death. This unit should be serviced by a licensed electrician or a similarly qualified electrical service technician.

If the electric heater does not operate:

If the electric heater cycles on and off:

If conditioned space fails to warm up:

If condition space overheats:

Specific Electric Heater Troubleshooting Procedures: PROBLEM: Heater Does Not Energize

Cause Solution
Power not properly connected to the heater 1. With a voltmeter, check the power wiring terminals to ensure proper voltage is available to the heater element side of the power terminal block or to the field side of the disconnect switch, power fusing or circuit breaker.
2. If proper voltage is not present, check the terminal studs for proper wiring and check power source for power.
Disconnect switch, toggle switch or circuit breaker are set to OFF position 1. Set disconnect switch, toggle switch or circuit breaker to ON position.
Power fuses are blown or circuit breaker is tripped 1. Replace fuse(s) with same type and amperage as those provided with the heater from the manufacturer or reset circuit breaker by first setting circuit breaker to OFF position then resetting to ON position.
2. With an ammeter, check amp draw on the power lines.
3. For heaters with fusing, amp draw should not exceed the fuse amperage.
4. Amp draw should not exceed the circuit breaker rated value.
5. If the amp draw is excessive, check the power supply as described above for power voltage.
6. If fuses blow or circuit breaker trips again, check for a short.
7. If no short is present and the power supply wiring/voltage are correct, contact factory for further assistance.
Manual reset safety switch has tripped 1. Push the reset safety button on back of safety reset. The manual safety reset is located inside the control enclosure cover near the bottom on the heater element header.
Airflow/static switch is not engaging 1. Jumper out the airflow/static switch by connecting the lead attached to the normally open terminal to the normally closed terminal.
2. If the heater starts operating, two conditions could exist.
A. The airflow/static switch may be defective.
B. There is insufficient airflow to make the switch.
3. To verify available static pressure, disconnect the pneumatic tubing from the HI side of the airflow/static switch and connect to a magnehelic gauge.
4. Available static pressure should be 0.05 in. wg +/- 0.03 in. wg to be safe.
5. If available static pressure is in a dead band, between the two ranges, the airflow/static switch will not engage and could cause chattering of the contacts. Some method must be devised to increase the available static pressure.
6. If sufficient static pressure is available, check to ensure the pneumatic tubing is connected to the correct port (HI) on the airflow/static switch.

Specific Electric Heater Troubleshooting Procedures: PROBLEM: Heater Does Not Energize

Cause Solution
Automatic Safety Reset Switch is bad 1. Allow the duct temperature to cool down below 90°F.
2. If the heater still does not energize, jumper out the automatic safety reset switch.
3. If the heater now energizes, contact the factory for a replacement automatic safety reset switch.
Manual Safety Reset Switch is bad 1. Allow the duct temperature to cool down below 90°F.
2. If the heater still does not energize, perform the following:
A. On heaters with the manual safety reset switch connected in the backup contact circuit, jumper out the manual safety reset switch.
B. If the backup contactor now engages, contact the factory for a replacement manual safety reset switch.
C. If the backup contactor fails to engage, there is a problem in the backup contactor holding coil.
D. Use an ohmmeter to check continuity of the holding coil on the backup contactor.
E. If bad, contact factory for replacement backup contactor.
Insufficient airflow across the electric heating elements 1. The minimum allowable airflow across the heating elements is 70 cfm/kW.
2. Unless this recommended minimum airflow is met, the leaving air temperature of the heater will be greater than the safety reset switch limits. This will cause nuisance tripping of the safety reset switch.
3. Reset the minimum airflow across the heating elements during a call for heat at 70 cfm/kW.

WARNING
On all troubleshooting that requires working inside the heater casing, disconnect the power first! Jumpers used for diagnostic purposes should be removed before returning the heater to normal operation.

Figure 4 - Multi-Quadrant Averaging Flow Sensor

This section details the Multi-Quadrant Averaging Flow Sensor, including model compatibility, inlet sizes, and K-factors. The K-factor is defined as the calibration flow constant at 1 in. wg delta P.

MODEL INLET SIZE K FACTOR
XG-TH, XG-FCI, XG-FCQ04 Rnd300
XG-FVI, XG-DD05 Rnd375
XG-DH, XG-BP06 Rnd540
XG-RT, XG-RA07 Rnd760
XG-TL (4 to 10)08 Rnd990
XG-FCI C2 (4 to 8)09 Rnd1250
XG-FVL C2 (4 to 8)10 Rnd1640
12 Rnd2350
XG-TL (12)14 Rnd3250
16 Rnd4100
XG- TL (14) & XG-FVL C612 Flat Oval2270
XG- TL (16)14 Flat Oval2850
XG-FVL C416 Flat Oval3550
XG-FCI C414x8 Rect2450
XG-FCI, XG-FCQ, & XG-FVI C716x8 Rect2770
18x16 Rect6200
XG-TH 2020x16 Rect6430
XG-TH 2424x16 Rect7270

Shape Dimensions:

Round:

SIZED (in.)
04 Rnd4
05 Rnd5
06 Rnd6
07 Rnd7
08 Rnd8
09 Rnd9
10 Rnd10
12 Rnd12
14 Rnd14
16 Rnd16

Flat Oval:

SIZEW (in.)H (in.)
12 FLat Oval1310
14 FLat Oval16.2510
16 FLat Oval16.2510

Rectangle:

SIZEW (in.)H (in.)
14x8 Rect1410
16x8 Rect1610
20x16 Rect2010
24x16 Rect2416

Formula: Cfm = √Δp x K Factor

Description of Graph: "Logarithmic Flow Rate vs Pressure Drop" shows multiple lines representing different models/sizes, plotting Flow Rate (cfm) on the x-axis against Sensor AP (in. wg) on the y-axis (logarithmic scale).

Our Commitment

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.

Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature section of the website at Greenheck.com/Resources/Library/Literature.

Models: XG-TH, XG-TL, XG-BP, XG-TH Single Duct Vav Atu, XG-TH, Single Duct Vav Atu, Duct Vav Atu, Vav Atu, Atu

File Info : application/pdf, 11 Pages, 1.26MB

PDF preview unavailable. Download the PDF instead.

1041402 SingleDuct iom

References

Adobe PDF Library 17.0

Related Documents

Preview Greenheck Diffuser Selection Guide: Perforated, Square, and Louvered Ceiling Diffusers
A comprehensive selection guide for Greenheck's range of perforated, square, and louvered ceiling diffusers, detailing material options, frame styles, and available module sizes.
Preview Greenheck Quick Reference Guide: HVAC Air Distribution Products
A comprehensive quick reference guide from Greenheck detailing various HVAC terminal units, diffusers, grilles, and supply/return components, including model numbers from Greenheck, Krueger, and Titus.
Preview Greenheck XG-5500 Louver Face Ceiling Diffusers - Technical Specifications
Detailed technical specifications for Greenheck's XG-5500 series of square and rectangular louver face ceiling diffusers, made from extruded aluminum with a removable core. Includes information on models, dimensions, options, accessories, and construction details.
Preview Greenheck Ceiling Diffuser Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Greenheck ceiling diffusers. Learn about model nomenclature, lay-in installation, baffle installation for cone diffusers, blank-off installation for plaque diffusers, and general maintenance procedures.
Preview Greenheck Quick Reference Guide for HVAC Air Distribution Components
A comprehensive quick reference guide from Greenheck detailing various HVAC terminal units, diffusers, grilles, and air distribution products, including model numbers from Greenheck, Krueger, and Titus.
Preview Greenheck XG-6600-LS Light Shield - Non Insulated Submittal
Submittal document for the Greenheck XG-6600-LS Light Shield, a non-insulated aluminum light shield. Includes dimensions and available options for various models.
Preview GREENHECK DG, DGX, TSU, VSU Direct Gas Make-Up Air & Industrial Space Heat Installation, Operation, and Maintenance Manual
Official Installation, Operation, and Maintenance Manual for GREENHECK Direct Gas Make-Up Air and Industrial Space Heat units (Models DG, DGX, TSU, VSU). Covers safety, installation, operation, maintenance, and troubleshooting for industrial and commercial HVAC applications.
Preview Greenheck Packaged DX Module Installation, Operation, and Maintenance Manual
This manual provides comprehensive instructions for the installation, operation, and maintenance of the Greenheck Packaged DX Module. It covers safety precautions, component descriptions, installation procedures, start-up checklists, troubleshooting, and routine maintenance.