Page | 1 DIGITAL MULTIFUNCTION METER User Manual MT-DP96MF Version 1.0

DIGITAL MULTIFUNCTION METER User Manual ...

PDF preview unavailable. Download the PDF instead.

212-manual-mt-dp96mf-short-v02
DIGITAL MULTIFUNCTION METER User Manual MT-DP96MF
Version 1.0 Page |1

Thanks for choosing our product ­ MT-DP96MF, Please read this manual carefully and pay attention to below caution matters.
CAUTION
 This product should be installed and maintained by professional person  Before operating this product inside or outside, please cut off the input
signal and power supply;  Please make sure all parts of the product don't have voltage by suitable
voltage detection device  The power supply should be within the rated range The below situation will result in device damage and abnormal working  Auxilliary power source voltage over range  Distribute system frequence over range  Current, voltage input polarity incorrect  Disconnect the communication plug under charged situation  No according requirement to connect termial
Please don't touch the terminals when the meter is in operation!
Page |2

CONTENTS 1. Function introduction.........................................4 2. Technical parameter..........................................5 3. Installation and correction...................................6-7 4. Display and buttons...........................................8-13 5. Programme operation........................................13-16
Page |3

1. Function introduce Measure function
Three phase voltage (L-L, L-N)

Remark

Realtime measure

Three phase current and neutral current
System Frequence
P, Q, S, PF (per phase & total

Basic function/

Electric energry
Communication Maximum Demand/ Analog output/ Digital input/
Relay output/

KWh import KVARh import KWh export, KVARh export RS485 Port MODBUS-RTU U,I,P,Q
0-20mA/ 4-20mA/ 0-5V/ 0-10V Dry contact type/
AC250V 5A Remote/ Alarm

Expanded option/

Display type/

LCD

Page |4

2. Technical parameter

Signal Input/

Parameter

Connection system 3P3W/ 3P4W

Measurement

range

519V L-L

Voltage Over load Continous: 1.2 Vn; Instantaneous: 2Vn

Power

consumption  1VA

Measurement

Current range

5A/ 1A

Over load Continous: 1.2In; Instantaneous: 2In Power consumption  1VA

Frequence Auxiliary power suply
Communication Analog output Relay output Digital input
Measure class IP protection Evernionment
Safe

45 - 65Hz AC85-265V DC100-300V RS485 communication port, physical layer isolation. According international standard MODBUS-RTU agreement. Communication speed 1200-38400 (Default 9600) Test type N81, E81, 081 (Default N81) 0-20mA/ 4-20mA/ 0-5V/ 0-10V Programme remote/ Alarm switching ouput Capacity 5A at 250VAC/ 30VDC Remote switch input signal, dry contact input. Program relate alarm output Current, Voltage: 0.5S Frequency: ±0.1Hz Active power: 0.5S Reactive power: 1S Energy: 0.5S IP53 for indoor type and PI65 for outdoor type
Working temperature: -10÷55C Store temperature: -20÷75C Relative Humidity:80%RH Isolation: Signal, auxiliary power suply, output terminal crust resistance 5M and withstand voltage pulse >AC2KV

Page |5

3. Installation and correction

LxH (mm) AxB (mm) SxY (mm) SxY (mm) N

IP65

(mm)

96x96

90.5x90.5 91x91

91.5x91.5 94

M (mm)
88

3P4W System: 3PT, Direct Volt input

3P4W System: 3PT, 3VT

3P3W System: 2PT, Direct Volt input

3P3W System: 2PT, 2VT
Page |6

Active Pulse Ep- Ep+
48 47

Reactive Pulse
Ep- Ep+
50 49

RS485 B A 59 58

Aux. Power Suply

N(V-) 2

L(V+) 1

Relay Output

Digital input

Analog output

DO1 DO2 DO3 DO4 COM DI1 DI2 DI3 DI4 A0- A01+ A02+ A03+ A04+

15 16 17 18 19 20 21 22 70 71 72 73 74 30 31 32 33 34

RS485

Power original

MT-

MT-

DP96MF DP96MF

MTDP96MF

Page |7

4. Display & Buttons

1 a

b

c
d
a. Four lines digital display measure information: Three phase voltage, three phase current, active power, reactive power, power factor,frequence, switch input, output, other switch input, two way actice power, two way reactive power, analog input, demand
b. K is light mean practice value is display value is 1.000 times. M is light mean practice value is display value is 1.000.000 times
c. Measure item unit or charactierise: three phase voltage V, three phase current A, active power W, reactive power VAR...
d. Buttons use in change or programme set: is change page button or value increase or decrease button
is enter programme status
is select confirm button If there is no relative symbol display or the set data not working, It means the product without the relative function
Page |8

DISP=1 -Three phase voltage -Forward active energy Kwh
DISP=2 -Three phase voltage -Reverse active energy Kwh
DISP=3 -Three phase current -Forward reactive energy Kvarh

tabe 6
Seperate display voltage Ua, Ub, Uc (in the 3P4W) In left fig. Ua=5774V Ub=5774V Uc=5774V Forward active energy = 2908.05KWh
Seperate display voltage Uab, Ubc, Uca (in the 3P4W) In left fig. Uab=10KV Ubc=10KV Uac=10KV Reverse active energy =1000.02Kwh
Seperate display current Ia, Ib, Ic (in the 3P4W) In left fig. Ia=5A Ib=5A Ic=5A Reverse reactive energy = 50Kvarh
Page |9

DISP=4
-Total active power
-Total reactive power
-Total apparent power
DISP=5
- Active power phase A
-Reactive power phase A
-Apparent power phase A
DISP=6
- Active power phase B
-Reactive power phase B
-Apparent power phase B

Total active power = 86.6KW Total reactive power = 0000Kvar Total apparent power =86.6KVA Reverse reactive energy =100.08Kvarh
Active power of phase A = 28.87KW Reactive power of phase A = 0000Kvar Apparent power of phase A =28.87KVA Forward active energy =2908.05KWh
Active power of phase B = 28.87KW Reactive power of phase B = 0000Kvar Apparent power of phase B =28.87KVA Reverse active energy =1000.02KWh
P a g e | 10

DISP=7 - Active power phase C -Reactive power phase C -Apparent power phase C
DISP=8 - Average current -Zero sequence current
DISP=9 - Three phase total power factor -Frequence -Voltage unbalance

Active power of phase C = 28.87KW Reactive power of phase C = 0000Kvar Apparent power of phaseCB =28.87KVA Forward reactive energy =50.00KVARh
Average current = 5A Zero sequence current = 0.06A Reverse reactive energy =50.00KVARh
Three phase total power factor =1.000 Frequence = 50Hz Voltage unbalancedness = 9V Forward active energy =2908.05KWh
P a g e | 11

DISP=10 Split phase power factor
DISP=11 Residual current
DISP=12 Digital input infomation from 1 to 12 way channel

Power factor of phase A =0.999 (inductive load) Power factor of phase B =0.999 (inductive load) Power factor of phase C =0.999 (inductive load) Reverse active energy =1000.02KWh
Residual current = 10.09mA
First line: 1-4 way channel Second ine: 5-8 way channel Third line: 9-12 way channel In left fig.: No.5 way, No.6 way, No.8 way chanel are ON, other way channel is OFF
P a g e | 12

DISP=13
Digital output infomation from 1 to 4 way channel

First line: 1-4 way channel Second ine: 5-8 way channel Third line: 9-12 way channel
In left fig.: No.1 way, No.3 way, No.4 way chanel are ON, No.2 way chanel is OFF

5. Programme operation
In programme status, digital interface adopt layers structure menu type, meter supply three lines number display (se fig. 5)

No.1 line is first layer menu information;
No.2 line is second layer menu information;
No.3 line is third layer menu information;
Exp: The fig.5 shown: No.1 layer: INPT = Signal input; No.2 layer: CT = current transformer; No.3 layer: current value is 5, It means ratio of CT is 25/5A.
The digital display interface menu has the following organizational structure, the user can choose the appropriate setting parameters according tho the actual situation.
P a g e | 13

0000 mean automatic cycling display. Each board connect see table 6
0000-0120 is keeing time of LCD back light. 0000 means the backlight keeping ON
1111 means the data clear other value is invalid

Wiring type Net 0000 or other value
Voltage trans. ratio PT
Current trans. rato PT
Address SN
Communication speed
BAUD
Data format DATA

0000 mean 3P4W system. Other value is mean 3P3W system
PT value= PT primary value/ secondary value CT value= CT primary value/ secondary value
Meter address range 1 to 247
0001 is 1200; 0002 is 2400; 0003 is 4800; 0004 is 9600; 00005 is 9200; 00006 is 38400
0000 is E,8, 1; 0001 is 0,8,1; 00002 is N,8,1

Choose alarm item or close alarm

Set alarm item's specitic threshold value

Choose alarm item, and set relative threshold value (when alarm item is digital value, no need set threshol value), once meet alarm condition, switch ouput working

P a g e | 14

Choosen transmitter item or close analog output (refer to 8.2 analog output)

Set the full scale value of analog item

Choose transmitter item's and relative electrical parameter (0-20mA, 4-20mA, 4-12-20mA) For example, set "A0-1" TYPE"0135" UAL"5000", which means A phase current 0-5A corresponds to the transmitter output signal of first loop 4-20mA

Note: The above menu is applied to the product with complete functions. If you find there is no such menu in the product or the menu is not working, It means the product not supporting the function.

Hold SET button in 3 seconds

0000 mean automatic in turn display mode

0001-0003 is LED type light adjust 0000-0120 is LCD apheliotropic display keep time (0000 is apheliotropic normal light)
Rotation interval time

1111 mean energy clear

Password of function setting. Default is 88888888
0000 mean 3P4W system Other value is mean 3P3W system

Voltage multiple rate range 1-9999

(Communicat ion set. Other one way is similar)

Current multiple rate range 1-9999 0000 expression: 3CT 0001 expression: 2CT Meter communication address range 1-247
0000: E,8.1;0001:0,8.1;0002:N,8.1

P a g e | 15

(Zero-position blanking setting)

Zero-position blanking of voltage signal (PT secondary value setting) 0500 means the blanking not display below 05V Zero-position blanking of current signal (CT secondary value setting) 0010 means the blanking not display below 0.01A
Factory reset
Set alarm item When TYPE is 0000, mean "remote control" status (As per table 15)
Set alarm value (CT secondary value) (As per table 15)
Set relay delay time, unit: second

(Analog capacity output: other three ways is similar)

P a g e | 16

