Growatt Solar Pump Inverter 750W-5500W User Manual

Introduction

The solar pumping system diagram illustrates the flow: Solar Panel array connects to the Solar Pump Inverter. The inverter then powers the Pump, which draws water from a Groundwater source or Water Tank. The system can also connect to the Utility Grid. The output can be used for Irrigation or Animal Husbandry. The diagram shows arrows indicating the direction of power and water flow.

The manual uses symbols to denote electrical values and safety precautions. These include: Grounding Wire of Equipment (symbol: ⏚), AC Value (symbol: ~), DC Value (symbol: —), Phase (symbol: ⏐), and a warning symbol (symbol: ⓘ) indicating 'Before operating inverter, please read the instruction.' Another symbol (symbol: ⚠) with a 5-minute delay indicates 'In order to avoid electric shock, break off machine with PV terminal and AC terminal for at least 5 minutes, then contact the wire of machine output terminal and input terminal.' A final warning symbol (symbol: ⚠) states 'Warning: when machine works, the temperature of metal shell may be very high.'

This solar pump inverter switches power from solar panels and the grid to the AC power needed to control the pump. It features a Boost circuit for MPPT solar charging to maximize solar power and allows setting the priority of PV and utility grid input. It is suitable for submersible pumps, ground pumps, swimming pool pumps, and other pumps using three-phase asynchronous motors.

Features

  • Rated power 750W to 5500W
  • Inbuilt MPPT solar controller
  • Inbuilt BOOST circuit for broader PV voltage range
  • Automatic selection of photovoltaic and AC power
  • IP65 protection level
  • Built-in full protection and self-diagnosis
  • Soft start function
  • Comprehensive LCD and LEDs display real-time system status
  • Remote monitoring through GPRS/4G (optional)

Product Overview

The Growatt Solar Pump Inverter features a front panel with: 1. LCD display, 2. LED indicators (POWER, ALARM, FAULT), 3. Function buttons, 4. AC input terminal, 5. PV input terminal, 6. Water level sensor port, 7. AC output terminal, and 8. GPRS communication port (optional).

When selecting an installation location, consider the following: Do not mount on flammable materials. Mount on a solid metal surface. Ensure the environment is shady and cool, avoiding direct sunlight. Install in a waterproof and dustproof box. Mount at eye level for easy LCD visibility. The inverter should be adhered to the wall vertically. Maintain sufficient clearance (e.g., ≥100cm above, ≥30cm to sides, ≥300cm below) for heat dissipation and wire access.

The mounting dimensions for different models are provided: Single phase 220V 750W-2.2kW and 3 phase 220V 750W-2.2kW models have dimensions of 252x220mm (WxH) with mounting holes at 220x220mm. Single phase 220V 4kW and 3 phase 380V 2.2kW-5.5kW models have dimensions of 272x230mm (WxH) with mounting holes at 220x260mm. Mounting is suitable for concrete or other non-combustible surfaces only.

A safety nut installation is depicted.

Installation

Unpacking and Inspection

Before installation, inspect the unit and package contents. The package should include: The unit (x1), User manual (x1), and Attachment (x1).

Wiring Introduction

The inverter features AC input, DC input, water level sensor connection terminals, GPRS (optional), and AC output terminals.

The terminal introduction table details the connections: PV (PV+, PV-), AC Input (L, N, PE), AC Output (1, 2, L, PE for 3PH; 1, L, PE for 1PH), COM terminal (1, 2 for water tank sensor 2; 3, 4 for water well sensor 1; 5, 6 are unused), and GPRS connection terminal (1: +5V, 2: TXD-232, 3: RXD-232, 4: GND).

Note that input socket polarity and AC output socket sequencing may differ between models. Risk of electric shock: disconnect solar panel, pump inverter AC and DC, and allow 5 minutes for internal capacitance discharge before any work.

Assemble DC Connector

To assemble the DC connector: Strip the cable (6-8mm), insert the bare wire into the core tube of the connector, crimp using a hex crimping die, and insert the core tube into the slot until it clicks. Tighten nuts to finish wiring.

Assemble AC Output Connector

For Growatt SPI 750-5500TL series, there are two AC output connector types. Type I (3-phase) uses AC connector 1, 2, L, PE for pump connection via 4 wires (U, V, W, PE). Type II (1-phase) uses AC connector L, 1, PE for pump connection via 3 wires (L, N, PE).

Assembly involves removing connector parts, guiding the pressure screw sealing and threaded sleeve over the cable, inserting stripped conductors into screw terminals (U, V, W, PE for Type I; L, N, PE for Type II), pushing the threaded sleeve into the socket element, screwing the pressure screw tightly, and finally inserting the connector into the inverter receptacle and locking the housing.

Assemble AC Input Connector

Similar to AC output, assembly involves preparing the connector parts, guiding the pressure screw sealing and threaded sleeve over the cable, inserting stripped conductors (L, N, PE) into the socket element's screw terminals, and securing the connector.

Push the threaded sleeve in to the socket element, screw the pressure screw tightly onto the threaded sleeve until it clicks. Insert the AC connection plug into the inverter receptacle and lock the housing.

Wiring of Water Level Sensor

The diagram shows the wiring of water level sensors. Water Level Sensor 2 connects to COM terminals 1 and 2 for the water tank. Water Level Sensor 1 connects to COM terminals 3 and 4 for the water well. The overall system includes Utility Grid, Solar Panel, AC Output, Water Pump, Water Tube, Water Tank, and Water Well.

Connect water level sensor 1 to detect water shortage. It connects to COM terminals 3 and 4. If sensor 1 detects low water level, the inverter delays output for 5s, then turns off pump protection. Normal operation resumes after water recovery and a 20s wait. Connect water level sensor 2 to detect if the water tank is full. It connects to COM terminals 1 and 2. If sensor 2 detects high water level, the inverter delays output for 5s and turns off. When the level drops below the set point, it waits 20s before restarting.

Operation

Display Panel

The solar pump inverter uses an LCD operation panel with 3 LED lights (POWER, ALARM, FAULT) and 5 keys.

The panel includes: POWER (Green LED: inverter running), ALARM (Yellow LED: warning or terminal mode), FAULT (Red LED: system failure). Keys are: Operation/Stop Key (short press to start/stop control, 2s press to stop control), Confirm/Programming Key (short press to enter programming mode or confirm alterations, 2s press to enter programming menu), Increment Key (increase parameter/value, increase output frequency), Decrement Key (decrease parameter/value, decrease output frequency), and Return Key (return to initial display).

LCD Display Information

The LCD displays operation data, control parameters, and historical parameters. Information switches by pressing UP/DOWN keys. Displayed items include: Output frequency (Running/Set), Input PV voltage, Output voltage, Output current, and Relative value of rated power.

Parameters Setting

Work Mode Setting

The inverter supports three work modes: Manual (P00.01=0), Fully-automatic terminal (P00.01=1, default), and GPRS (P00.01=2, optional). Manual mode requires key operation to start/stop. Fully-automatic mode traces maximum power point when sunlight is strong. GPRS mode allows remote control via cellphone.

To set Work Mode: Enter parameter modification interface (long press Enter key). Navigate to P00 group, then P00.01. Press Enter key to view/edit. Use Down key to select value (0 for manual, 1 for terminal). Press Enter key to save.

Rated Parameters Setting for the Motor

Ensure wiring is correct before setting motor parameters. Parameters include: P02.01 Motor rated power, P02.02 Motor rated frequency, P02.04 Motor rated voltage, P02.05 Motor rated current. After setting, set P00.01=1 for automatic mode.

The process involves navigating to the parameter group (e.g., P02), selecting the specific parameter (e.g., P02.01 for Rated Power), editing the value using Up/Down keys, and pressing Enter to save. For example, to set Rated Power to 4.0kW, navigate to P02.01, use Up/Down keys to change the displayed value to 4.0kW, and press Enter to save. Similarly, for Rated Current (P02.05), edit the value and save.

After setting parameters, turn off DC and AC switches. Wait for screen to turn off, then turn on DC switch. The inverter will auto-start the pump after 60 seconds.

Warning: Do not change parameters randomly, as it may cause system malfunction.

Function Parameters

The Function Parameters table lists parameters like Operation code channel (P00.01), MAX. Output frequency (P00.03), MAX. running frequency (P00.04), Function restore parameter (P00.18), Rated power of asynchronous motor (P02.01), Rated frequency of asynchronous motor (P02.02), Rated voltage of asynchronous motor (P02.04), and Rated current of asynchronous motor (P02.05), along with their scope, introduction, and default values.

SNNameScopeIntroductionDefault Value
P00.01Operation code channel0~20: keyboard operation code channel (LED is off)
1: terminal operation code channel (LED flashes)
2: communication operation code channel (LED is solid on)
1
P00.03MAX.Output frequencyP00.04~400.00Seting the maximum output frequency50.00Hz
P00.04MAX.running frequency0.00~ P00.03Seting the maximum running frequency50.00Hz
P00.18Function restore parameter0~10: No operation
1: Restore the default value
0
P02.01Rated power of asynchronous motor0.1 ~ 3000.00.1~3000.0kWModel confirmation
P02.02Rated frequency of asynchronous motor0.01 ~ P00.030.01~P00.0350.00Hz
P02.04Rated voltage of asynchronous motor0 ~ 1200V0~1200VModel confirmation
P02.05Rated current of asynchronous motor0.8 ~ 6000A0.8~6000AModel confirmation

Troubleshooting

The inverter has complete protection. When a failure occurs, the inverter will take protective measures. The general protection is to stop the motor from running and forbid it to restart within a certain period.

CodeDescriptionPossible ReasonsCountermeasures
Power offNo failureW
Inc OVP
Dec OVP
Con OVP
OvervoltageInput voltage is too highCheck the voltage of solar array
Vbus lowUndervoltage1. Input voltage is too low;
2. Illumination intensity is too weak
Check the voltage of solar array
Inc OCP
Dec OCP
con OCP
Overcurrent1. The load of pump is too large;
2. The voltage of solar array is too low;
3. The motor wiring is too long
1.Replace for a smaller pump;
2.Check voltage of solar array;
3.Shorten the wiring between inverter and motor
Overload TelWater pump is overloadLoad is too largeDecrease maximum operation frequency
Overload VVVFInverter is overloadThe inverter load is too largeDecrease power grade of water pump
IGBT shortcutModule overcurrentOutput short circuit or grounding module damage1.Check the wiring
2.Get after-sells support
Inv Overtemp
REC Overtemp
Module is overtemperature1. Air flue is blocked
2. Environment temperature is too high
3. The time of overload runing is too long.
1. Clean air flue or improve ventilation
2.Degree the environment temperature
Scarce Phase OutOutput default phaseEquipment or circuit damageGet after-sells support
Shortcut GND 1Grounding short circuitThe output line may be connected with groundCheck the wiring
Curr Test FaultCurrent detection failure1.The control board connection is in poor contact
2.The hall component is damaged
The magnifying circuit is abnormal
Get after-sells support
Lack loadWater pump conducts "dry-operation"Water pump's connection wires are all open circuit. Water pump does not match inverter1. Check water level.
2. Check whether the water pump wiring condition and water pump power meet the requirements of inverter capacity
No WaterWater shortageWater shortage warningWhen water is provided, it can recover automatically
Water FullWater fullWater full warningWhen water level decreases, it can recover automatically
Com FaultCommunication failureDevice or circuit damageReset
Get after-sells support

Warning: Try to find out the failure reason before attempting a reset. If it can't reset or suffers failure again after reset, please try find out the reason first. Continuously resetting could damage the inverter.

Specifications

The specifications table details various Growatt SPI models (SPI 750TL-G2 to SPI 5500TL3-HV) across DC Input, AC Input, AC Output, Control Performance, Protection Functions, and Others. Key specifications include Max. DC voltage, Recommended MPPT voltage, Max. DC current, Input voltage, Rated input current, Input frequency, Rated output power, Rated output current, Output voltage, Output frequency, Motor type, display type (LCD), communication options (GPRS/WIFI), dimensions, net weight, operating temperature range (-25~60°C, with derating above 45°C), environmental protection rating (IP65), cooling (natural), altitude limit (3000m, with derating above 2000m), and relative humidity (0~100%).

MODESPI 750TL-G2SPI 1500TL-G2SPI 2200TL-G2SPI 4000TL-G2SPI 750TL3-LVSPI 1500TL3-LVSPI 2200TL3-LVSPI 4000TL3-LVSPI 2200TL3-HVSPI 4000TL3-HVSPI 5500TL3-HV
DC INPUT
Max.DC voltage450V450V450V450V450V450V450V450V800V800V800V
Starting voltage80V80V80V80V80V80V80V80V220V220V220V
Recommended MPPT voltage100~400V100~400V100~400V100~400V100~400V100~400V100~400V100~400V220~750V220~750V220~750V
Max. DC current9A12A12A20A9A12A12A20A12A20A20A
Number of input channels11121112222
AC INPUT
Input voltage1PH 220~240V (-15%~+10%)1PH 220~240V (-15%~+10%)1PH 220~240V (-15%~+10%)1PH 220~240V (-15%~+10%)3PH 380V (-15%~+10%)3PH 380V (-15%~+10%)3PH 380V (-15%~+10%)
Rated input current9.5A16A24A38A9.5A16A24A38A6A14A20A
Input frequency47~63 Hz47~63 Hz47~63 Hz47~63 Hz47~63 Hz47~63 Hz47~63 Hz47~63 Hz47~63 Hz47~63 Hz47~63 Hz
AC input terminalL,N, PEL,N, PEL,N, PEL,N, PEL,N, PEL,N, PEL,N, PEL,N, PER,S,T,PER,S,T,PER,S,T,PE
AC OUTPUT
Rated output power750W1500W2200W4000W750W1500W2200W4000W2200W4000W5500W
Rated output current5.1A10.2A14A25A4.2A7.5A10A16A5.5A9.5A14A
Output wiring mode1P1L1P1L1P1L3P3L3P3L3P3L3P3L3P3L3P3L3P3L3P3L
Output voltage0~220V0~220V0~220V0~220V0~220V0~220V0~220V0~220V0~380V0~380V0~380V
Output frequency0~50/60Hz0~50/60Hz0~50/60Hz0~50/60Hz0~50/60Hz0~50/60Hz0~50/60Hz0~50/60Hz0~50/60Hz0~50/60Hz0~50/60Hz
CONTROL PERFORMANCE
Control modeV/FV/FV/FV/FV/FV/FV/FV/FV/FV/FV/F
Motor typeAsynchronous motor (1PH 220V)Asynchronous motor (1PH 220V)Asynchronous motor (1PH 220V)Asynchronous motor (1PH 220V)Asynchronous motor (3PH 220V)Asynchronous motor (3PH 220V)Asynchronous motor (3PH 220V)Asynchronous motor (3PH 220V)Asynchronous motor (3PH 380V)Asynchronous motor (3PH 380V)Asynchronous motor (3PH 380V)
PROTECTION FUNCTIONS
Output overcurrentYESYESYESYESYESYESYESYESYESYESYES
Output overlodeYESYESYESYESYESYESYESYESYESYESYES
Output short-circuitYESYESYESYESYESYESYESYESYESYESYES
Dry/Overflow protectionYESYESYESYESYESYESYESYESYESYESYES
OTHERS
DisplayLCDLCDLCDLCDLCDLCDLCDLCDLCDLCDLCD
ComunicationGPRS/WIFI (OPTION)GPRS/WIFI (OPTION)GPRS/WIFI (OPTION)GPRS/WIFI (OPTION)GPRS/WIFI (OPTION)GPRS/WIFI (OPTION)GPRS/WIFI (OPTION)GPRS/WIFI (OPTION)GPRS/WIFI (OPTION)GPRS/WIFI (OPTION)GPRS/WIFI (OPTION)
Certificate StandardCECECECECECECECECECECE
Dimensions (W×D×H), mm370×335×135370×335×135370×335×135370×335×135450×365×150450×365×150450×365×150450×365×150450×365×150450×365×150450×365×150
Net weight, kg9.59.59.59.516.516.516.516.516.516.516.5
Operation temperature range-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)-25~60°C (with derating above 45°C)
Environmental Protection RatingIP65IP65IP65IP65IP65IP65IP65IP65IP65IP65IP65
CoolingNatural coolingNatural coolingNatural coolingNatural coolingNatural coolingNatural coolingNatural coolingNatural coolingNatural coolingNatural coolingNatural cooling
Altitude3000m (with derating above 2000m)3000m (with derating above 2000m)3000m (with derating above 2000m)3000m (with derating above 2000m)3000m (with derating above 2000m)3000m (with derating above 2000m)3000m (with derating above 2000m)3000m (with derating above 2000m)3000m (with derating above 2000m)3000m (with derating above 2000m)3000m (with derating above 2000m)
Relative humidity0~100%0~100%0~100%0~100%0~100%0~100%0~100%0~100%0~100%0~100%0~100%
Models: SPI 750-4000TL3 750-5500W Solar Pump Inverter, SPI 750-4000TL3, 750-5500W Solar Pump Inverter

PDF preview unavailable. Download the PDF instead.

1PH Growatt SPI 750-5500W- MANUAL Corel PDF Engine Version 14.0.0.701 CorelDRAW

Related Documents

Preview Growatt MAX 80KTL3 LV Series PV Grid Inverter Compliance Certificate
This document is a compliance certificate issued by SGS for Growatt MAX 80KTL3 LV series PV Grid Inverters. It confirms adherence to the NRS 097-2-1:2017 standard for grid interconnection of embedded generation.
Preview Growatt MAX 185~253KTL3-X HV Solar Inverter Datasheet
Technical datasheet for the Growatt MAX 185~253KTL3-X HV series of solar inverters, detailing specifications, features, and protection devices.
Preview Growatt MIC TL-X Series PV Grid Inverter Installation and Operation Manual
Comprehensive guide for installing, operating, and maintaining the Growatt MIC TL-X series PV grid inverters. Includes safety instructions, technical specifications, troubleshooting, and compliance information.
Preview Growatt Introduction and Warranty Procedures for the UK and Ireland Market
This document provides an overview of Growatt's warranty procedures, product warranty periods, scope, and claim process for the UK and Ireland market. It details customer and installer responsibilities, contact information, and online claim submission guidelines.
Preview Growatt Energy Storage Configuration Checklist
A comprehensive checklist detailing the configuration and compatibility of Growatt's energy storage systems, including ARK LV, ARK HV, AXE LV, ML33RTA, GBLI 6532, ARK XH, and APX HV series with various inverters and battery modules.
Preview Growatt MOD 3-15KTL3-HU Series Hybrid Solar Inverter User Manual
Comprehensive user manual for the Growatt MOD 3-15KTL3-HU series of hybrid solar inverters. Covers installation, electrical connection, operation, maintenance, troubleshooting, and specifications for efficient solar energy management.
Preview Growatt SPH TL3 BH-UP Series Installation and Operation Manual
Comprehensive guide for installing and operating the Growatt SPH TL3 BH-UP Series hybrid solar inverters and energy storage systems. Covers safety, product description, installation, commissioning, operation, maintenance, and specifications.
Preview Growatt SPH TL3 BH-UP Series Installation and Operation Manual
This manual provides detailed product information and installation instructions for the Growatt SPH TL3 BH-UP Series hybrid inverters. It covers safety precautions, product descriptions, installation procedures, commissioning, operation modes, troubleshooting, and technical specifications.