Technical Specifications

Operating Conditions

Minimum Differential Pressure (ApVmin)

Flow Rates (qmax)

The following table shows flow rates in liters per hour (l/h) and US gallons per minute (US gpm) for various settings (Pos) and valve sizes (DN).

Pos DN 10 LF
3/8" LF
[l/h]
[US gpm] DN 15 LF
1/2" LF
[l/h]
[US gpm] DN 15
1/2"
[l/h]
[US gpm] DN 20
3/4"
[l/h]
[US gpm] DN 25
1"
[l/h]
[US gpm] DN 32
1 1/4"
[l/h]
[US gpm]
1 17 0.075 38 0.17 92 0.41 200 0.88 340 1.50 720 3.17
2 27 0.12 53 0.23 114 0.50 260 1.14 440 1.94 960 4.23
3 39 0.17 68 0.30 140 0.62 360 1.59 600 2.64 1350 5.94
4 51 0.22 85 0.37 170 0.75 460 2.03 810 3.57 1750 7.71
5 62 0.27 104 0.46 210 0.92 565 2.49 1010 4.45 2150 9.47
6 76 0.33 125 0.55 265 1.17 670 2.95 1200 5.28 2530 11.1
7 89 0.39 146 0.64 325 1.43 770 3.39 1350 5.94 2850 12.5
8 101 0.44 168 0.74 390 1.72 850 3.74 1520 6.69 3130 13.8
9 111 0.49 197 0.87 445 1.96 920 4.05 1640 7.22 3380 14.9
10 120 0.53 230 1.01 480 2.11 975 4.29 1750 7.71 3600 15.8

Note: Flow rates (l/h) are at each pre-setting and fully open valve plug.

Dimensions and Configurations

TA-Modulator + EMO TM

DN H1 H2
10-15 55 107
20 64 107
Size H1 H2
3/8"-1/2" 2.17" 4.21"
3/4" 2.52" 4.21"

Approximate dimension: ~15 mm (~0.59")

TA-Modulator + TA-Slider 160

DN H1 H2
10-15 55 119
20 64 119
25 64 130
32 78 133
Size H1 H2
3/8"-1/2" 2.17" 4.68"
3/4" 2.52" 4.68"
1" 2.52" 5.12"
1 1/4" 3.07" 5.24"

Approximate dimension: ~15 mm (~0.59")

TA-Modulator + TA-TRI

DN H1 H2
10-15 55 122
20 64 122
25 64 132
32 78 132
Size H1 H2
3/8"-1/2" 2.17" 4.80"
3/4" 2.52" 4.80"
1" 2.52" 5.20"
1 1/4" 3.07" 5.20"

Approximate dimension: ~15 mm (~0.59")

EMO TM/TA-Slider 160/TA-TRI Details

Installation and Operation

The document includes visual guides for the installation and adjustment of the TA-Modulator. These guides illustrate the process of setting the valve and connecting it to the system. Key steps involve:

Example illustrations show the adjustment mechanism and the final installation.

Models: DN 10-32 Balancing And Control Valve, DN 10-32, Balancing And Control Valve, Control Valve, Valve

File Info : application/pdf, 2 Pages, 1.54MB

PDF preview unavailable. Download the PDF instead.

TA-Modulator DN10-32 instruction

References

Adobe PDF Library 16.0.7 Adobe InDesign 17.4 (Windows)

Related Documents

Preview IMI TA TA-Modulator: Combined Control & Balancing Valves
Comprehensive technical guide for the IMI TA TA-Modulator, a pressure-independent control and balancing valve. Features include precise temperature control, quick hydronic balancing, and easy troubleshooting. Details technical specifications, materials, dimensions, flow ranges, installation, and operating procedures for various models.
Preview TA-SCOPE: Guía de Usuario y Manual de Instrucciones
Explore el TA-SCOPE, un instrumento avanzado para el equilibrio y diagnóstico de sistemas hidráulicos. Este manual proporciona información detallada sobre sus funciones, operación y mantenimiento.
Preview IMI TA-Slider 750/1250 & 750/1250 Plus Actuator Installation and Operation Manual
Comprehensive guide for the IMI TA-Slider 750/1250 and 750/1250 Plus actuators, covering specifications, installation, wiring, operation, and troubleshooting. Includes technical details, safety information, and quick start instructions.
Preview TA-Dongle Hard-Reset Function Guide
Instructions on how to perform a hard-reset on the TA-Dongle by IMI Hydronic Engineering.
Preview IMI TA-SCOPE Quick Guide - Hydronic Measurement System
A concise guide to the IMI TA-SCOPE system, detailing its components, handheld and DpS-Visio unit operations, measurement procedures for flow, pressure, and temperature, PC communication, care instructions, and technical specifications.
Preview IMI Hydronic Engineering STAP Differential Pressure Regulators
Discover the STAP differential pressure regulators from IMI Hydronic Engineering, designed for efficient and stable regulation in heating and cooling systems. Learn about key features, technical specifications, installation, and application examples.
Preview TA-Smart BACnet MS/TP Protocol Implementation Conformance Statement
This document provides the Protocol Implementation Conformance Statement (PICS) for the TA-Smart BACnet MS/TP device, detailing its supported BACnet features, objects, and configuration parameters.
Preview TA-Smart Register Selection Help | IMI Hydronic Engineering
Comprehensive guide to TA-Smart valve registers for flow, power, differential pressure, and temperature control modes. Details Modbus and BACnet communication protocols.