Instruction Manual for NOVUS models including: N1020, Temperature Controller, N1020 Temperature Controller, Controller
NOVUS AUTOMATION 1/8 N1020 Temperature Controller INSTRUCTIONS MANUAL - V1.2x A INTRODUCTION The N1020 is a small and yet powerful temperature controller.
NOVUS AUTOMATION 1/8 N1020 Temperature Controller INSTRUCTIONS MANUAL – V1.2x A INTRODUCTION The N1020 is a small and yet powerful temperature controller.
File Info : application/pdf, 8 Pages, 559.89KB
DocumentDocumentN1020 Temperature Controller INSTRUCTIONS MANUAL V1.2x A INTRODUCTION The N1020 is a small and yet powerful temperature controller. It accepts most of the temperature sensors used in industry and its 2 outputs can be configured independently as control or alarm output. It also embeds an auto-adaptative PID control algorithm for best system performance. Configuration can be performed either directly on the controller or via the USB interface once QuickTune software has been installed on the computer to be used. Once connected to USB, the device will be recognized as a serial communication (COM) port operating with Modbus RTU protocol. Through the USB interface, even if disconnected from the power supply, the configuration performed in a piece of equipment can be can be saved in a file and repeated in other pieces of equipment that require the same configuration. It is important that the users read carefully this manual before using the controller. Verify if the release of this manual matches the instrument version (the firmware version is shown when the controller is energized). The N1020 main characteristics are: · LED Display, red, high brightness; · Multi-sensor universal input: : thermocouples, Pt100 and 50 mV; · Self-tuning PID parameters; · 2 outputs: 1 relay and 1 logical pulse for SSR; · Output functions: Control, Alarm1 and Alarm 2; · 8 distinct alarm functions; · Programmable timer; · Function key for enabling/disabling outputs, resetting the timer or turning the timer ON/OFF; · Programmable soft-start; · Rate function; · Password for parameters protection; · Capability of restoring factory calibration. USB INTERFACE The USB interface is used to CONFIGURE, MONITOR or UPDATE the controller FIRMWARE. The user should use QuickTune software, which offers features to create, view, save and open settings from the device or files on the computer. The tool for saving and opening configurations in files allows the user to transfer settings between devices and perform backup copies. For specific models, QuickTune allows to update the firmware (internal software) of the controller via the USB interface. For MONITORING purposes, the user can use any supervisory software (SCADA) or laboratory software that supports the MODBUS RTU communication over a serial communication port. When connected to a computer's USB, the controller is recognized as a conventional serial port (COM x). The user must use QuickTune software or consult the DEVICE MANAGER on the Windows Control Panel to identify the COM port assigned to the controller. The user should consult the mapping of the MODBUS memory in the controller's communication manual and the documentation of the supervision software to start the MONITORING process. NOVUS AUTOMATION Follow the procedure below to use the USB communication of the device: 1. Download QuickTune software from our website and install it on the computer. The USB drivers necessary for operating the communication will be installed with the software. 2. Connect the USB cable between the device and the computer. The controller does not have to be connected to a power supply. The USB will provide enough power to operate the communication (other device functions may not operate). 3. Run the QuickTune software, configure the communication and start the device recognition. The USB interface IS NOT SEPARATE from the signal input (PV) or the controller's digital inputs and outputs. It is intended for temporary use during CONFIGURATION and MONITORING periods. For the safety of people and equipment, it must only be used when the piece of equipment is completely disconnected from the input/output signals. Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it. When MONITORING for long periods of time and with connected inputs and outputs, we recommend using the RS485 interface, which is available or optional in most of our products. INSTALLATION / CONNECTIONS The controller must be fastened on a panel, following the sequence of steps described below: · Prepare a panel cut-out according Specifications; · Remove the mounting clamps from the controller; · Insert the controller into the panel cut-out; · Slide the mounting clamp from the rear to a firm grip at the panel. RECOMMENDATIONS FOR THE INSTALLATION · All electrical connections are made to the screw terminals at the rear of the controller. They accept wire sizes from 0.5 to 1.5 mm2 (16 to 22 AWG). The terminals should be tightened to a torque of 0.4 Nm (3.5 lb in). · To minimize the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power conductors. If this is impractical, use shielded cables. In general, keep cable lengths to a minimum. · All electronic instruments must be powered by a clean mains supply, proper for instrumentation. · It is strongly recommended to apply RC'S FILTERS (noise suppressor) to contactor coils, solenoids, etc. · In any application it is essential to consider what can happen when any part of the system fails. The controller features by themselves can't assure total protection. 1/8 ELECTRICAL CONNECTIONS The controller complete set of features is drawn in Fig. 01. The features loaded in a particular unit are shown on its label: Fig. 01 - Connections of the back panel Removal of the Controller Back Connector Fig. 02 Back connector removal FEATURES INPUT TYPE SELECTION Select the input type (in parameter "tYPE") from Table 01 below. TYPE CODE RANGE OF MEASUREMENT J Tc j Range: -110 to 950 ºC (-166 to 1742 ºF) K Tc k Range: -150 to 1370 ºC (-238 to 2498 ºF) T Tc t Range: -160 to 400 ºC (-256 to 752 ºF) N Tc n Range: -270 to 1300 ºC (-454 to 2372 ºF) R Tc r Range: -50 to 1760 ºC (-58 to 3200 ºF) S Tc s Range: -50 to 1760 ºC (-58 to 3200 ºF) B Tc b Range: 400 to 1800 ºC (752 to 3272 ºF) E Tc e Range: -90 to 730 ºC (-130 to 1346 ºF) Pt100 Pt Range: -200 to 850 ºC (-328 to 1562 ºF) 0 to 50 mV L0.50 Linear. Programmable indication -1999 to 9999 Table 01 - Input Types OUTPUTS The N1020 offers two output channels, user configurable as Control output, Alarm 1 output or Alarm 2 output. OUT1 - Logical pulse, 5 Vdc / 25 mA, available at terminals 4 and 5. OUT2 - Relay SPST-NA, 1.5 A / 240 Vac, available at terminals 6 and 7. Note: The outputs can be configured independently from each other, for example, both can be control outputs at the same time. CONTROL OUTPUT The control strategy can be configured as ON / OFF or PID. N1020 Temperature Controller ALARM OUTPUT There two alarms available in the N1020. The alarms can be assigned to either output, logical or relay. The alarm functions are described below. ALARM FUNCTIONS The alarms can be configured to operate with nine different functions, as shown in Table 02. off Alarms turned Off. lo Alarm of Absolute Minimum Value. Triggers when the value of measured PV is below the value defined for alarm Setpoint (SPA1 or SPA2). PV SPA1 ki Alarm of Valor Absolute Maximum Value. Triggers when the value of measured PV is above the value defined for alarm Setpoint. PV SPA1 dif Alarm of Differential Value. In this function the parameters SPA1 and SPA2 represent the deviation of PV in relation to the SP of CONTROL. PV PV difl SP SPA1 SP SP + SPA1 SV + SPA1 SP SV SPA1 SPA1 positive SPA1 negative Alarm of Minimum Differential Value. It triggers when the value of PV is below the defined point by (using the Alarm 1 as example): PV PV difk SP SPA1 SP SP SP SPA1 SPA1 positive SPA1 negative Alarm of Valor Maximum Differential Value. Triggers when the value of PV is above the defined point by (using Alarm 1 as example): SP SP + SPA1 PV PV SP + SPA1 SP SPA1 positive SPA1 negative t.0n Timer ON alarm. Sets alarm output ON when timer is runing. t.end Timer end. Configures the alarm to actuate when the timer expires. ierr Sensor Break Alarm. Activated when the input signal of PV is interrupted, out of the range or when Pt100 in short-circuit. Table 02 Alarm functions The above examples also apply to Alarm 2. Important note: Alarms configured with the ki, dif, and difk functions also trigger their associated output when a sensor fault is identified and signaled by the controller. A relay output, for example, configured to act as a High Alarm (ki), will operate when the SPAL value is exceeded and also when the sensor connected to the controller input is broken. NOVUS AUTOMATION 2/8 Alarms Timer Modes (Temporization) The controller alarms can be configured to perform 4 timer modes: MODE Normal Operation A1t1 a2t1 0 A1t2 A2t2 0 ACTION Alarm Output Alarm Event Activation for a defined 1 to 6500 s 0 time Alarm Output T1 Alarm Event Alarm Activation with delay 0 1 to 6500 s Output T2 Alarm Event Intermittent 1 to 1 to Alarm Output T1 T2 T1 Activation 6500 s 6500 s Alarm Event Table 03 - Temporization Functions for the Alarms The signs associated to the alarms will light when the alarm condition is recognized, not following the actual state of the output, which may be temporarily OFF because of the temporization. Initial Blocking of Alarm The initial blocking option inhibits the alarm from being recognized if an alarm condition is present when the controller is first energized (or after a transition from run YES NO). The alarm will be enabled only after the occurrence of a non alarm condition followed by a new occurrence for the alarm. The initial blocking is useful, for instance, when one of the alarms is configured as a minimum value alarm, causing the activation of the alarm soon upon the process start-up, an occurrence that may be undesirable. The initial blocking is disabled for the sensor break alarm function. RAMP AND SOAK FUNCTION Allows reaching the SP value gradually. The value of SP is increased gradually from an initial value (PV value) until it reaches the set value. The rate parameter sets this increase for SP in degrees per minute. The Ramp function will work when turn on the controller, enable control (RUN = YES) or when the SP value is changed. A value equal to zero (0) in the rate parameter disables the Ramp function. TIMER FUNCTION The N1020 embeds a timer function (decreasing) for applications that require particular process duration. Once defined the time interval in the T1me parameter, the timer will START when: · When PV reaches the temperature programmed in the SP parameter. · When enabling the control (RUN = YES). · By pressing the F key when configured to Timer reset mode (the timer is reloaded with the T1me parameter and restarts counting). · By pressing the F key in ON/OFF mode stops the timer counting; pressing it again, resumes the counting. When the timer expires, the two possible actions can be: · Disables de control (RUN NO) or · Activate the alarm. FUNCTIONS FOR THE F KEY The F key on the frontal keypad is meant for special commands, as follows: · Enable outputs (identically to the RUN parameter). · Timer reset: - reloads the timer and initiates a new time counting. · Timer ON/OFF. Timer holds or resumes counting each time the F key is pressed. Keeping the F key pressed for 3 seconds resets the timer (reloads the timer to the value set in T1me), initiating a new time counting. NOVUS AUTOMATION N1020 Temperature Controller Note: when the F key is configured as RUN = YES/NO (RUN = f.key), the controller outputs are born disabled after powers up. SOFT-START The Soft-start function is generally used in processes that require slow start-up, where the instantaneous application of 100% of the available power to the load may cause damages to parts of the system. In order to disable this function, the soft-start parameter must be configured with 0 (zero). OFFSET Allows fine trimming the PV indication to compensate for sensor errors. Default value: zero. SERIAL COMMUNICATION For full documentation download the Registers Table N1020 for Serial Communication on our web site www.novusautomation.com. Fig. 03 Serial Communications Connections The table below helps you connect the RS485 communication interface connectors: D1 D D + B Bidirectional data line D0 D - A Inverted bidirectional data line C Optional connection that improves the GND performance of the communication. OPERATION The controller's front panel, with its parts, can be seen in the Fig. 04: Fig. 04 - Identification of the parts referring to the front panel Display: Displays the current value of PV. When configuring a parameter, the display alternates between the parameter prompt and its value (the parameter value is shown with a light blinking to differentiate it from the parameter prompt). The display contains also the signs AT, OUT, RUN ALM and COM: AT Indicator: Stays ON while the controller is in tuning process. OUT Indicator: For relay or pulse control output; it reflects the actual state of the output. RUN Indicator: Indicates that the controller is active, with the control output and alarms enabled. (RUN=YES). ALM Indicator: Signalize the occurrence of alarm condition. It lights when either alarm is active. COM Indicator: Flashes when there is RS485 activity. P Key: Used to walk through the menu parameters. Increment key and Decrement key: allow altering the values of the parameters. F Key: accesses special functions: RUN (toggles YES/NO) and the two modes of timer control. 3/8 STARTUP When the controller is powered up, it displays its firmware version for 3 seconds, after which the controller starts normal operation. The value of PV is then displayed and the outputs are enabled. In order for the controller to operate properly in a process, its parameters need to be configured first, such that it can perform accordingly to the system requirements. The user must be aware of the importance of each parameter and for each one determine a valid condition. The parameters are grouped in levels according to their functionality and operation easiness. The 5 levels of parameters are: 1 Operation Level 2 Tuning Level 3 Alarms Level 4 Configuration Level 5 Calibration Level The P key is used for accessing the parameters within a level. Keeping the P key pressed, at every 2 seconds the controller jumps to the next level of parameters, showing the first parameter of each level: PV >> atvn >> fva1 >> type >> pass >> PV ... To enter a particular level, simply release the P key when the first parameter in that level is displayed. To walk through the parameters in a level, press the P key with short strokes. The display alternates the presentation of the parameter prompt and its value. The parameter value is displayed with a light blinking to differentiate it from the parameter prompt. Depending on the level of parameter protection adopted, the parameter PASS precedes the first parameter in the level where the protection becomes active. See section CONFIGURATION PROTECTION. At the end of this manual, a table with the complete sequence of levels and parameters is presented. Note: It is recommended to disable/suspend the control (rvn = NO) whenever it is necessary to change the device settings. DESCRIPTION OF THE PARAMETERS OPERATION LEVEL PV Timer SP T1me Rate rvn PV indication Timer remaining time. Only shown when the Timer function is in use. (T1me 0) (HH:MM). Control SP adjustment. Sets the Timer, 00:00 to 99:59 (HH:MM). RATE OF PV RISE: from the current PV to the SP value. In degrees/minute. Enables control outputs and alarms. YES - Outputs enabled. NO - Outputs disabled. f.key -"F" key assumes control over the RUN command. NOVUS AUTOMATION N1020 Temperature Controller TUNING LEVEL Atvn Auto-tune pb Proportional Band Defines the control strategy to be taken: off Turned off. (no PID tuning) Fast Fast automatic tuning. Full More accurate automatic tuning. Self Precise + auto - adaptative tuning Rslf Forces one new precise automatic precise + auto - adaptative tuning. TGht Forces one new precise automatic + auto - adaptative tuning when Run = YES or controller is turned on. Refer to the "DETERMINING PID PARAMETERS" section for further details on tuning strategies. Proportional Band - Value of the term P of the control mode PID, in percentage of the maximum span of the input type. Adjust of between 0 and 500.0 %. Select zero for ON/OFF control. ir Integral Rate Integral Rate - Value of the term I of the PID algorithm, in repetitions per minute (Reset). Adjustable between 0 and 99.99. Displayed only if proportional band 0. dt Derivative Time Value of the term D of the control mode Derivative Time PID, in seconds. Adjustable between 0 and 300.0 seconds. Displayed only if proportional band 0. (t Level Time Pulse Width Modulation (PWM) period in seconds. Adjustable between 0.5 and 100.0 seconds. Displayed only if proportional band 0. kyst Hysteresis Control Hysteresis (in engineering. units): This parameter is only shown for ON / OFF control (Pb=0). Adjustable between 0 and the measurement input type span. A(t Action Control Action: For Auto Mode only. re Control with Reverse Action. Appropriate heating. Turns control output on when PV is below SP. dir Control with Direct Action. Appropriate for cooling. Turns control output on when PV is above SP. sfst Softstart SoftStart Function : Time in seconds during which the controller limits the MV value progressively from 0 to 100 %. It is enabled at power up or when the control output is activated. If in doubt set zero (zero value disables the Soft start function). 0ut1 0ut2 Outputs 1 and 2 function: Off not used; (trl control output. A1 Alarm 1. A2 Alarm 2. A1a2 Alarm 1 AND Alarm 2 at the same time. ALARMS LEVEL Fva1 Functions of Alarms. Defines the functions for the alarms Fva2 among the options of the Table 02. Function Alarm Sp.a1 Sp.a2 Alarm Setpoint: Tripping points for alarms 1 and 2. Value that defines the point of activation for the programmed alarms with the functions Lo or ki. For the alarms configured with Differential type functions, this parameter defines deviation (band). Not used for the other alarm functions. bla1 bla2 Blocking Alarm Block Alarm 1 and 2: This function blocks the alarms when the controller is energized. YES - enables initial blocking NO - inhibits initial blocking xya1 Alarm Hysteresis. Defines the difference between the xya2 value of PV at which the alarm is triggered and the value at which it is turned off. Hysteresis of Alarm A1t1 Defines the temporization time t1, for the alarms. A2t1 In seconds. Alarm Time t1 4/8 A1t2 A2t2 Alarm Time t2 flsh Defines the temporization time t2, for the alarms. In seconds. Allows you to identify the occurrence of alarm conditions by flashing the PV indication on the display screen. YES- Enables alarm signaling flashing PV NO - Disables alarm signaling flashing PV CONFIGURATION LEVEL Type Type fltr Filter Input Type: Selects the input signal type to be connected to the process variable input. Refer to Table 1 for the available options. Digital Input Filter - Used to improve the stability of the measured signal (PV). Adjustable between 0 and 20. In 0 (zero) it means filter turned off and 20 means maximum filter. The higher the filter value, the slower is the response of the measured value. Dp.po Selects the decimal point position to be viewed in both Decimal Point PV and SP. vni t Unit Unit. Temperature indication in °C or °F. Not shown for linear inputs. 0ffs Offset Sensor Offset: Offset value to be added to the PV reading to compensate sensor error. Default value: zero. Spll Defines the SP lower limit. SP Low Limit To 0-50 mV input type sets the lower range for SP and PV indication. Spxl Defines the SP upper limit. SP High Limit To 0-50 mV input type sets the upper range for SP and PV indication. T1me Timer Time. Adjustment. 00:00 to 99:59 (HH:MM). (same function as the one presented in the operation level) Tm.en Timer Enable Shows a copy of the Timer parameter in the operating level. En - enables T1me parameter to the operating level Dis - doesn't show the T1me parameter in the operating level T.str Timer Start Defines the mode for starting the Timer. sP- when PV reach the temperature value in SP rvn - when RUN YES f.rst - "F" key (reset timer) f.stp - "F" key (start/stop the timer). T.e.(.0 Control behavior when the timer expires: Timer End Control YES - disables the outputs (RUN = NO). Off NO - outputs continue to operate. Rate Ramp function. Establishes the rate of increase of PV, in degrees/minute. Same Rate function as showed in the operating level. rT.en Rate Enable Shows a copy of the Rate parameter in the operating level. En - enables the Rate parameter to the operating level. Dis - doesn't show the Rate parameter in the operating level rvn Enables the control and alarm outputs. YES NO f.key - outputs enabled. - outputs disabled. - outputs enabled/disabled function assigned to the F key. Same rvn function as showed in the operating level. NOVUS AUTOMATION N1020 Temperature Controller rn.en Run Enable bavd Baud Rate prty Parity Addr Address Shows a copy of the rvn parameter in the operating level. En - enables the rvn parameter in the operating level Dis - doesn't show the rvn parameter in the operating level Baud Rate serial communication. In kbps, with the following speeds available 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 and 115.2 Parity of the serial communication. none Whitout parity Ewem Eve parity 0dd Odd parity Communication Address. Identifies the controller in the network. The possible address numbers are from 1 to 247. CALIBRATION LEVEL All of the input and output types are calibrated in the factory. If a recalibration is required, this should be carried out by a experienced personnel. If this level is accidentally accessed, pass through all the parameters without pressing the or keys pass Password (alib Calibration? inL( Input Low Calibration ink( Input High Calibration rstr Restore Input of the Access Password. This parameter is presented before the protected levels. See item Protection of Configuration. Enables or disables instrument calibration by the user, YES: shows calibration parameters No: Hides the calibration parameters See section MAINTENANCE / Input Calibration. Enter the value corresponding to the low scale signal applied to the analog input. Only showed if (alib = YES See section MAINTENANCE / Input Calibration. Enter the value corresponding to the full scale signal applied to the analog input. Only showed if (alib = YES Restores the factory calibration for all inputs and outputs, disregarding modifications carried out by the user. ovll Lower limit for the control output - Minimum percentage Output Low Limit value assumed by the control output when in automatic mode and in PID. Typically configured with 0 %. Default value: 0 % ovkl Upper limit for the control output - Maximum percentage for Output High Limit the control output when in automatic mode and in PID. Typically configured with 100 %. Default value: 100 %. (j Cold junction temperature controller. Cold Junction Pas.( Password Change Allows defining a new access password, always different from zero. Prot Sets up the Level of Protection. See Table 04. Protection Freq Mains frequency. This parameter is important for proper Frequency noise filtering. snk Shows the four first digits of the controller serial number. snL Shows the four last digits of the controller serial number. CONFIGURATION PROTECTION The controller provides means for protecting the parameters configurations, not allowing modifications to the parameters values, avoiding tampering or improper manipulation. The parameter Protection (PROt), in the Calibration level, determines the protection strategy, limiting the access to particular levels, as shown by the Table 04. 5/8 Protection Level Protection Levels 1 Only the Calibration level is protected. 2 Calibration and Tuning levels. 3 Calibration, Tuning and Alarms levels 4 Calibration, Tuning, Alarms and Configuration levels 5 Calibration, Tuning, Alarms, Configuration levels Table 04 Levels of Protection for the Configuration ACCESS PASSWORD The protected levels, when accessed, request the user to provide the Access Password for granting permission to change the configuration of the parameters on these levels. The prompt PASS precedes the parameters on the protected levels. If no password is entered, the parameters of the protected levels can only be visualized. The Access Password is defined by the user in the parameter Password Change (PAS.(), present in the Calibration Level. The factory default for the password code is 1111. PROTECTION ACCESS PASSWORD The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password. MASTER PASSWORD The Master Password is intended for allowing the user to define a new password in the event of it being forgotten. The Master Password doesn't grant access to all parameters, only to the Password Change parameter (PAS(). After defining the new password, the protected parameters may be accessed (and modified) using this new password. The master password is made up by the last three digits of the serial number of the controller added to the number 9000. As an example, for the equipment with serial number 07154321, the master password is 9 3 2 1. DETERMINATION OF PID PARAMETERS The determination (or tuning) of the PID control parameters in the controller can be carried out in an automatic way and auto-adaptative mode. The automatic tuning is always initiated under request of the operator, while the auto-adaptive tuning is initiated by the controller itself whenever the control performance becomes poor. Automatic Tuning: In the beginning of the automatic tuning the controller has the same behavior of an ON/OFF controller, applying minimum and maximum performance to the process. Along the tuning process the controller's performance is refined until its conclusion, already under optimized PID control. It begins immediately after the selection of the options FAST, FULL, RSLF or TGHT, defined by the operator in the parameter ATUN. Auto-adaptative Tuning: Is initiated by the controller whenever the control performance is worse than the one found after the previous tuning. In order to activate the performance supervision and autoadaptative tuning, the parameter ATUN must be adjusted for SELF, RSLF or TGHT. The controller's behavior during the auto-adaptative tuning will depend on the worsening of the present performance. If the maladjustment is small, the tuning is practically imperceptible for the user. If the maladjustment is big, the auto-adaptive tuning is similar to the method of automatic tuning, applying minimum and maximum performance to the process in ON/OFF control. N1020 Temperature Controller Fig. 05 Example of auto tuning Fig. 06 Example of auto-adaptative tuning The operator main select through the ATUN parameter, the desired tuning type among the following options: · OFF: The controller does not carry through automatic tuning or auto-adaptative tuning. The PID parameters will not be automatically determined nor optimized by the controller. · FAST: The controller will the process automatic tuning one single time, returning to the OFF mode after finishing. The tuning in this mode is completed in less time, but not as precise as in the FULL mode. · FULL: The same as the FAST mode, but the tuning is more precise and slower, resulting in better performance of the P.I.D. · SELF: The performance of the process is monitored and the auto-adaptative tuning is automatically initiated by the controller whenever the performance poorer. After a tuning level, the controller starts collecting data from the process for determining the performance benchmark that will allow evaluate the need for future tunings. This phase is proportional to the process response time and is signaled by the flashing TUNE indication on the display. It is recommended not to turn the controller off neither change the SP during this learning period. It is recommended not to turn the controller off neither change the SP during this learning period. · rSLF: Accomplishes the automatic tuning and returns into the SELF mode. Typically used to force an immediate automatic tuning of a controller that was operating in the SELF mode, returning to this mode at the end. · TGHT: Similar to the SELF mode, but in addition auto-adaptative tuning, it also executes the automatic tuning whenever the controller is set in RUN=YES or when the controller is turned on. Whenever the parameter ATUN is altered by the operator into a value different from OFF, an automatic tuning is immediately initiated by the controller (if the controller is not in RUN=YES, the tuning will begin when it passes into this condition). The accomplishment of this automatic tuning is essential for the correct operation of the auto-adaptative tuning. The methods of automatic tuning and auto-adaptative tuning are appropriate for most of the industrial processes. However, there may be processes or even specific situations where the methods are not capable to determine the controller's parameters in a satisfactory way, resulting in undesired oscillations or even taking the process to extreme conditions. The oscillations themselves imposed by the tuning methods may be intolerable for certain processes. These possible undesirable effects must be considered before beginning the controller's use, and preventive measures must be adopted in order to assure the integrity of the process and users. The AT signaling device will stay on during the tuning process. NOVUS AUTOMATION 6/8 In the case of PWM or pulse output, the quality of tuning will also depend on the level time adjusted previously by the user. If the tuning does not result in a satisfactory control, refer to Table 05 for guidelines on how to correct the behavior of the process. PARAMETER Proportional Band Rate of Integration Derivative Time VERIFIED PROBLEM Slow answer Great oscillation Slow answer Great oscillation Slow answer or instability Great oscillation SOLUTION Decrease Increase Increase Decrease Decrease Increase Table 05 - Guidance for manual adjustment of the PID parameters MAINTENANCE PROBLEMS WITH THE CONTROLLER Connection errors and inadequate programming are the most common errors found during the controller operation. A final revision may avoid loss of time and damages. The controller displays some messages to help the user identify problems. MESSAGE DESCRIPTION OF THE PROBLEM ---- Open input. No sensor o signal. Err1 Err6 Connection and/or configuration errors. Check the wiring and the configuration. N1020 Temperature Controller Other error messages may indicate hardware problems requiring maintenance service. CALIBRATION OF THE INPUT All inputs are factory calibrated and recalibration should only be done by qualified personnel. If you are not familiar with these procedures do not attempt to calibrate this instrument. The calibration steps are: a) Configure the input type to be calibrated. b) Enter in Calibration Level. c) At the input terminals, apply a signal corresponding to a value slightly above the lower input limit. d) Access the parameter inLC. Using the and keys, adjust the display reading such as to match the applied signal, then press the P key e) At the input terminals, apply a signal corresponding to a value slightly below the upper input limit. f) Access the parameter inkC. Using the and keys, adjust the display reading such as to match the applied signal, then press the P key. g) Return to the Operation level and check the calibration result. Note: When checking the controller calibration with a Pt100 simulator, pay attention to the simulator minimum excitation current requirement, which may not be compatible with the 0.170 mA excitation current provided by the controller. N1020 PARAMETER TABLE OPERATING LEVEL PV indication Timer indication SP T1me Rate RvN TUNING LEVEL atvn pb ir dt (t kyst ACt sfst 0UT1 0UT2 ALARMS LEVEL Fv.a1 Fv.a2 Sp.a1 Sp.a2 Bl.a1 Bl.a2 Xy.a1 Xy.a2 A1.t1 A2.t1 A2.t2 flsh ( * ) The PASS prompt precedes the parameters on the protected levels. CONFIGURATION LEVEL CALIBRATION LEVEL Type fltr Dp.po vnI t 0ffs Sp.ll Sp.xl T1me Tm.en T.str T.e.(.0 Rate rt.en RvN rn.en bavd prty Addr Pass ( * ) (alib In.L( In.k( rstr ovll ovkl (j Pas.( Prot Freq Snk Snl NOVUS AUTOMATION 7/8 SPECIFICATIONS DIMENSIONS:........................................25 x 48 x 105 mm (1/32 DIN) Panel Cutout:......................................23 x 46 mm (+0.5 -0.0 mm) Approximate Weight: .............................................................. 75 g POWER SUPPLY:.....................100 to 240 Vac/dc (±10 %), 50/60 Hz Maximum consumption:......................................................... 5 VA CONDITIONS ENVIRONMENTAL: Operation Temperature: ............................................... 0 to 50 °C Relative Humidity:......................................................... 80 % max. INPUT..............................T/C, Pt100 an voltage (according Table 01) Input Resolution: ....................................... 32767 levels (15 bits) Resolution of Display:...... 12000 levels (from -1999 up to 9999) Rate of input reading:.................................. up to 55 per second Accuracy: ..Thermocouples J, K, T, E: 0.25 % of the span ±1 ºC ...................Thermocouples N, R, S, B: 0.25 % of the span ±3 ºC ............................................................... Pt100: 0.2 % of the span .......................................................................................mV: 0.1 % Input Impedance: ................Pt100 and thermocouples: > 10 M Measurement of Pt100: ....................... 3-wire type, (=0.00385) With compensation for cable length, excitation current of 0.170 mA OUTPUT OUT1: ..................................................Voltage pulse; 5 V / 25 mA OUT2: ................................Relay SPST, 1.5 A / 240 Vac / 30 Vdc FRONT PANEL: ..................................IP65, Polycarbonate (PC) UL94 V-2 ENCLOSURE: .......................................................IP30, ABS+PC UL94 V-0 ELECTROMAGNETIC COMPATIBILITY: ............... EN 61326-1:1997 and EN 61326-1/A1:1998 EMISSION: ............................................................ CISPR11/EN55011 IMMUNITY:......................EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-8 and EN61000-4-11 SAFETY: .......................... EN61010-1:1993 and EN61010-1/A2:1995 (UL file E300526) USB INTERFACE 2.0, CDC CLASS (VIRTUAL COMMUNICATIONS PORT), USB CONECTOR: MINI B, MODBUS RTU PROTOCOL. SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS; PROGRAMMABLE LEVEL OF PWM DE 0.5 UP 100 SECONDS; STARTS UP OPERATION AFTER 3 SECONDS CONNECTED TO THE POWER SUPPLY; CERTIFICATIONS: CE, UKCA and UL. IDENTIFICATION N1020 - A - B - C A: Output: PR: OUT1= Pulse / OUT2= Relay B: Digital Communication: 485: Interface communication RS485 C: Power Supply: 100~240 Vac/dc; 50~60 Hz WARRANTY Warranty conditions are available on our website www.novusautomation.com/warranty. NOVUS AUTOMATION 8/8