KM75V61
KM75V61 Us er Ma nual

http://www.klha.com/

KM75V61
User Manual
File Version: V21.6.10

KM75V61 using the standard RS485 bus MODBUS-RTU protocol,easy access to PLCDCS and other instruments or systems for monitoring illuminance state quantities.The internal use of high -precision sensing core and related devices to ensure high reliability and excellent long-term stability,can be

ShanghaiSonbest Industrial Co., Ltd KLHA Brand Division

Page1

KM75V61 Us er Ma nual

http://www.klha.com/

customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and other output

methods.

Technical Parameters

Technical parameter

Parameter value

Brand

KLHA

Illuminance measuring range

0~65535Lux

Illuminance allow deviation

±7%

Repeatability test

±5%

Illuminance detection chip

Import digital

Wavelength range

380nm~730nm

Communication Interface

RS485

Default baud rate

9600 8 n 1

Power

DC9~24V 1A

Running temperature

-40~80°C

Working humidity

5%RH~90%RH

Product Size

How to wiring?

ShanghaiSonbest Industrial Co., Ltd KLHA Brand Division

Page2

KM75V61 Us er Ma nual
Application solution

http://www.klha.com/

How to use?

Communication Protocol
ShanghaiSonbest Industrial Co., Ltd KLHA Brand Division

Page3

KM75V61 Us er Ma nual

http://www.klha.com/

The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands

are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is

9600, 8, n, 1
1. Read Data (Function id 0x03)

Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the

command:01 03 00 00 00 01 84 0A .

Device ID

Function id

Start Address

Data Length

CRC16

01

03

00 00

00 01

84 0A

For the correct query frame, the device will respond with data:01 03 02 00 79 79 A6 , the response

format is parsed as follows:

Device ID

Function id

Data Length

 1

Check Code

01

03

02

00 79

79 A6

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is

converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21.

Others and so on.

2. Data Address Table

Address

Start Address

Description

Data type

Value range

40001

00 00

1#illuminanceregister Read only

0~65535

40101

00 64

model code

read/write

0~65535

40102

00 65

total points

read/write

1~20

40103

00 66

Device ID

read/write

1~249

40104

00 67

baud rate

read/write

0~6

40105

00 68

mode

read/write

1~4

40106

00 69

protocol

read/write

1~10

3 read and modify device address (1) Read or query device address

If you don't know the current device address and there is only one device on the bus, you can use the

command FA 03 00 64 00 02 90 5F Query device address.

Device ID

Function id

Start Address

Data Length

CRC16

FA

03

00 64

00 02

90 5F

FA is 250 for the general address. When you don't know the address, you can use 250 to get the real

device address, 00 64 is the device model register.

For the correct query command, the device will respond, for example the response data is: 01 03 02

07 12 3A 79, the format of which is as shown in the following table:

Device ID

Function id

Start Address

Model Code

CRC16

01

03

02

55 3C 00 01

3A 79

Response should be in the data, the first byte 01 indicates that the real address of the current device is,

55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes

00 01 Indicates that the device has a status quantity.

(2)Change device address

For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66

00 02 E8 14 .

Device ID

Function id

Start Address

Destination

CRC16

ShanghaiSonbest Industrial Co., Ltd KLHA Brand Division

Page4

KM75V61 Us er Ma nual

http://www.klha.com/

01

06

00 66

00 02

E8 14

After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format

is parsed as shown in the following table:

Device ID

Function id

Start Address

Destination

CRC16

01

06

00 66

00 02

E8 27

Response should be in the data, after the modification is successful, the first byte is the new device

address. After the general device address is changed, it will take effect immediately. At this time, the user

needs to change the query command of the software at the same time.

4 Read and Modify Baud Rate

(1) Read baud rate

The device default factory baud rate is 9600. If you need to change it, you can change it according to

the following table and the corresponding communication protocol. For example, read th e current device's

baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.

Device ID

Function id

Start Address

Data Length

CRC16

01

03

00 67

00 01

35 D5

Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600;

4 is 19200; 5 is 38400; 6 is 115200.

For the correct query command, the device will respond, for example the response data is: 01 03 02

00 03 F8 45, the format of which is as shown in the following table:

Device ID

Function id

Data Length

Rate ID

CRC16

01

03

02

00 03

F8 45

coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.

(2)Change the baud rate

For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the

command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .

Device ID

Function id

Start Address

Target Baud Rate CRC16

01

03

00 66

00 01

64 15

Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take

effect immediately, at which point the device will lose its response and the baud rate of the device should

be queried accordingly. Modified.

5 Read Correction Value

(1) Read Correction Value

When there is an error between the data and the reference standard, we can reduce the display error

by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that

is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can

correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If

you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of

FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The

correction value starts from 00 6B. We take the first parameter as an example. The correction value is read

and modified in the same way for multiple parameters.

Device ID

Function id

Start Address

Data Length

CRC16

01

03

00 6B

00 01

F5 D6

For the correct query command, the device will respond, for example the response data is: 01 03 02

00 64 B9 AF, the format of which is as shown in the following table:

ShanghaiSonbest Industrial Co., Ltd KLHA Brand Division

Page5

Device ID 01

KM75V61 Us er Ma nual

Function id 03

Data Length 02

http://www.klha.com/
Data value 00 64

CRC16 B9 AF

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the

first state quantity correction value register. If the device has multiple parameters, other parameters

operate in this way. The same, the general temperature, humidity have this parameter, the light generally

does not have this item.

(2)Change correction value

For example, the current state quantity is too small, we want to add 1 to its true value, and the current

value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD .

Device ID

Function id

Start Address

Destination

CRC16

01

06

00 6B

00 64

F9 FD

After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the

parameters take effect immediately after successful change.

Disclaimer

This document provides all information about the product, does not gran t any license to intellectual

property, does not express or imply, and prohibits any other means of granting any intellectual property

rights, such as the statement of sales terms and conditions of this product, other issues. No liability is

assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use

of this product, including the suitability for the specific use of the product, the marketability or the

infringement liability for any patent, copyright or other intellectual property rights, etc. Product

specifications and product descriptions may be modified at any time without notice.

Contact Us

Company: Shanghai Sonbest Industrial Co., Ltd KLHA Brand Division

Address:Building 8,No.215 North east road,Baoshan District,Shanghai,China

Web: http://www.klha.com

Web: http://www.klha.com

SKYPE: soobuu

Email: sale@sonbest.com

Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077

ShanghaiSonbest Industrial Co., Ltd KLHA Brand Division

Page6

