Metering Module of Basic local monitored PDU
Manual DN-95623

Safety and Grounding:
Read the following information before installing or operating your DIGITUS Power Distribution Unit:  This PDU is intended for indoor use only.  This PDU must not be must not be operated one behind the other!  Operation only in dry and closed rooms.  This PDU may not be operated covered. Always ensure free accessibility.  The maximum power stated on the rating plate must not be exceeded.  Plug this PDU into a three-wire, grounded power outlet only.
The power outlet must be connected to appropriate branch circuit/ mains protection (fuse or circuit breaker). Connection to any other type of power outlet may result in a shock hazard.  Use only the supplied brackets of mounting.  Check that the power cord, plug, and socket are in good condition.  Voltage free only when the power plug is unplugged.  Disconnect the PUD from the power outlet before you install or connect equipment to reduce the risk of electric shock when you connot verify grounding. Reconnect the PDU to the power outlet only after you make all connections.  Operation under unfavorable environmental conditions must be avoided. (Humidity over 80% relative, wet, ambient temperatures above 50 ° C, solvents, flammable gases, dust, vapors).  If external damage to this PDU is detected, do not operate this PDU. Take this PDU immediately out of service if external damage is detected.  Do not pour liquids over the power strip. There is a high risk of fire or life-threatening electric shock.  When opening the power strip, live parts can be exposed. There is a risk of electric shock. The power strip may only be opened by a specialist. When opening the power strip, live parts can be exposed. There is a risk of electric shock. The power strip may only be opened by a specialist.
2

I Overview
Basic Metered PDU is a data center power distribution device with local monitoring function. It can accurately monitor voltage, current, power and electrical energy with an accuracy of ±1%, providing customers with safe and stable power distribution services.
II Hardware Introduction
1Product sketch
Basic Metered PDU is equipped with a hot-swappable monitoring module, which can be replaced without power interruption of the devices when necessary.

1. Screen: LCD screen

2. RUN: Run indicator

1

(flashes at intervals of 1

second during normal operation)

3. BUTTON: Button key

2

3

(switch display content)

4

4. RESET: Restart the module

2Interactive display
2.1 Single phase two way monitoring module (AC) Press the "BUTTON" key to turn the pages, the first to sixth screens will display the current (00.00A), voltage (225.5V), active power (00.00kW), and electrical energy (00007.7kWh) of L, C1 circuit and C2 circuit in sequence, and the seventh screen displays version number (VEr1.5.9), as shown below.
3

III Technical Specification

Input Output

Single phase

Rated voltage Maximum total load
current

Threephase

Rated voltage Maximum total load
current

Direct current

Rated voltage Maximum total load
current

Overload protection

Input current detection and display

Input voltage detection and display

Single phase
Threephase

Rated voltage Maximum total load
current Rated voltage Maximum total load
current

100-240VAC 50~60Hz
16A/ 32A
200-400VAC 50~60Hz
3×16A, 3×32A
240VDC/ 336VDC
40A/ 60A
Circuit breaker (optional) Detection accuracy: ±1%; Display accuracy: 0.01A Display modeliquid crystal display; Display direction: vertical/horizontal; Detection accuracy: ±1%; Display accuracy: 0.1V Display mode: liquid crystal display; Display direction: vertical/horizontal; 100-240VAC 50~60Hz
16A/ 32A
100-240VAC 50~60Hz
3×16A, 3×32A

4

Direct current

Rated voltage Maximum total load
current

Output socket system

Output unit specification Monitoring function (Local)

Alarm
Physical characteristics
Environment

Alarm condition
Alarm method Product dimensions Properties of shell material
Case color
Mounting Style
Working temperature Relative humidity
Storage temperature

240VDC/ 336VDC
40A/ 60A
See "Socket Standard and Output Unit Configuration Table" for details. Accept customized production Voltage (V), Current (A), Active Power(kW), Energy (kWh) When total load current/voltage current exceed the rated value Buzzer alarm Depends on the actual model ABS & PC Black Side brackets mounting/ Rear button mounting 0~45 30~90% -20 ~ +70

This is a Class A product. In home environment, this product may cause radio interference. In this case, the user may be required to take appropriate measures. Hereby Assmann Electronic GmbH, declares that the Declaration of Conformity is part of the shipping content. If the Declaration of Conformity is missing, you can request it by post under the below mentioned manufacturer address.
www.assmann.com Assmann Electronic GmbH Auf dem Schüffel 3 58513 Lüdenscheid Germany